Anybus X-gateway IIoT User Manual Download Page 17

Configuration

15 (30)

Network Configuration

Fig. 14

Configuration page

IP Configuration

TCP/IP network settings. These parameters can also be configured using

IPconfig

.

Ethernet Configuration

Port 1/2

10 HDX = 10 Mbit/s half duplex

10 FDX = 10 Mbit/s full duplex

100 HDX = 100 Mbit/s half duplex

100 FDX = 10 Mbit/s full duplex

Auto = Automatic mode (default)

MQTT Configuration

Broker URL

The URL of the MQTT broker.

Client identifier

The MQTT ClientID of the Anybus X-gateway IIoT Interface.

Keep alive time (s)

The time interval in seconds between the keep alive messages sent from the client
to the broker.

Broker username/
password

Authentication to send to the MQTT broker (if required).

Base topic

The base topic name to use in MQTT messages.

Quality of service

The MQTT QoS level to use.

OPC UA Configuration

TCP port

The TCP port to use for OPC UA. Default = 4840.

Discovery server URL

The URL of the OPC UA discovery server (required for timestamp information).

IIoT User Manual

SCM-1202-109 1.0 en-US

Summary of Contents for X-gateway IIoT

Page 1: ...IIoT Anybus X gateway Network Interface USER MANUAL SCM 1202 109 1 0 en US ENGLISH ...

Page 2: ...umstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features timing or functional side effects found outside the documented scope of this product The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e g compatibility issues and stability issues The examples and illustrations i...

Page 3: ...cument Conventions 4 2 Description 5 2 1 Overview 5 2 2 Connectors 5 2 3 LED Indicators 6 3 Installation 7 3 1 Installation Overview 7 4 Configuration 8 4 1 TCP IP Configuration 8 4 2 Anybus Configuration Manager X gateway 11 4 3 Anybus Configuration Manager IIoT 12 4 4 Web Interface 14 5 Technical Data 16 A License Information 17 ...

Page 4: ...This page intentionally left blank ...

Page 5: ...uct requires a basic knowledge of industrial network technology and of the MQTTand OPC UA protocols For additional documentation and software downloads FAQs troubleshooting guides and technical support please visit www anybus com support 1 2 Document history Version Date Description 1 00 2018 10 29 First release IIoT User Manual SCM 1202 109 1 0 en US ...

Page 6: ...ace Monospaced text is used to indicate program code and other kinds of data input output such as configuration scripts This is a cross reference within this document Document Conventions p 4 This is an external link URL www hms networks com This is additional information which may facilitate installation and or operation This instruction must be followed to avoid a risk of reduced functionality a...

Page 7: ...D Use ESD prevention measures to avoid damage Fig 1 IIoT interface Ethernet Connectors The IIoT interface contains a dual port Ethernet switch with RJ45 type connectors The two Ehernet ports are labeled X1 1 and X1 2 if the interface is top mounted and X2 1 and X2 2 if the interface is bottom mounted Pin Signal Description 1 TD Transmit data 2 TD Transmit data 3 RD Receive data 4 reserved 5 reserv...

Page 8: ...d Link established 10 Mbit s Red flickering Link activity 10 Mbit s NS Off Offline or no power Green Online IP address assigned Green flashing Online no IP address assigned Red Fatal error IP address conflict Alternating Red Green Firmware update in progress MS Off No power Green Normal operation Red Fatal error Alternating Red Green Firmware update in progress The LINK ACT LED indicators will sho...

Page 9: ...ation steps 1 Connect the Anybus X gateway IIoT Interface to the Ethernet network 2 Connect a computer to the USB connector on the X gateway 3 Power on the X gateway 4 Use IPconfig to configure the TCP IP settings for the IIoT interface 5 Use Anybus Configuration Manager X gateway to configure the data exchange options for the two interfaces in the Anybus X gateway 6 Use Anybus Configuration Manag...

Page 10: ...ontents of the zip archive and run the installer program 4 1 2 Scanning for Connected Devices When IPconfig is started it will automatically scan all available local networks for HMS devices Detected devices will be listed in the main window To refresh the list click on Scan Fig 3 IPconfig main window IP IP address of the device SN Subnet mask GW Default gateway DHCP Automatically managed IP confi...

Page 11: ... device in the Hostname field Only characters a z A Z 0 9 and _ underscore are allowed The default password for changing IP settings is blank no password If a password has been set for the device you must enter it to be able to change the settings To set a new password check the Change password box and enter the current password in the Password field then enter the new password in the New password...

Page 12: ... been set to use DHCP but there is no DHCP server on the network the device may not be detected by IPconfig To recover access to the device an internal DHCP server in IPconfig can be temporarily activated 1 Click the checkbox for Internal DHCP Server then click OK IPconfig will automatically refresh the scan and list the missing device in the main window 2 Select the device and configure it to use...

Page 13: ...on that the X gateway will take if the IIoT network goes offline Freeze keep the current value Clear reset all values to zero The input and output data sizes for the other network interface should be configured according to the actual PLC setup Refer to the documentation for the PLC and the built in help in Anybus Configuration Manager X gateway for help regarding the specific network interface Th...

Page 14: ...match the IO data mapping set up with Anybus Configuration Manager X gateway Fig 9 Adding tags 3 Optionally select File Save to save the current configuration project Note The project file saves the current settings in Anybus Configuration Manager IIoTand can be used as a starting point when creating configurations It cannot be used as a configuration file by the Anybus X gateway IIoT Interface Wh...

Page 15: ... on OK to close the confirmation dialog The X gateway will apply the new configuration and restart automatically Generating a configuration file and applying it using an external FTP client 1 Select File Generate configuration 2 Save the generated configuration file to your computer 3 Open an FTP client and connect to the IP address of the IIoT interface The default username is ABX and the passwor...

Page 16: ...be in the same Ethernet subnet as the IIoT interface Overview Fig 11 Overview page This page provides basic information about the IIoT interface including the serial number and the installed firmware version Parameters Fig 12 Parameter page This page shows the current data values for the configured IIoT tags Network Status Fig 13 Status page This page shows the current network settings and communi...

Page 17: ... MQTT broker Client identifier The MQTT ClientID of the Anybus X gateway IIoT Interface Keep alive time s The time interval in seconds between the keep alive messages sent from the client to the broker Broker username password Authentication to send to the MQTT broker if required Base topic The base topic name to use in MQTT messages Quality of service The MQTT QoS level to use OPC UA Configuratio...

Page 18: ... Data 16 30 5 Technical Data Data sheets and additional documentation including technical specifications and compliance information are available at www anybus com support IIoT User Manual SCM 1202 109 1 0 en US ...

Page 19: ...ER IN CONTRACT STRICT LIABILITY OR TORT INCLUDING NEGLIGENCE OR OTHERWISE ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE ftpd c This file is part of the FTP daemon for lwIP Print formatting routines Copyright C 2002 Michael Ringgaard All rights reserved Redistribution and use in source and binary forms with or without modification are permitted...

Page 20: ...opyright notice this list of conditions and the following disclaimer Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other materials provided with the distribution Neither the name of nor the names of its contributors may be used to endorse or promote products derived from this software withou...

Page 21: ...RCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE AND NON INFRINGEMENT THIS SOFTWARE IS PROVIDED ON AN AS IS BASIS AND THE AUTHORS AND DISTRIBUTORS HAVE NO OBLIGATION TO PROVIDE MAINTENANCE SUPPORT UPDATES ENHANCEMENTS OR MODIFICATIONS GOVERNMENT USE If you are acquiring this software on behalf of the U S government the Government shall have only Restricted Rights in the software and related document...

Page 22: ...T WARRANTY OF ANY KIND EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY CLAIM DAMAGES OR OTHER LIABILITY WHETHER IN AN ACTION OF CONTRACT TORT OR OTHERWISE ARISING FROM OUT OF OR IN CONNECTION WITH THE SOFTWARE OR THE USE OR OTHER DEALINGS IN TH...

Page 23: ...AND ON ANY THEORY OF LIABILITY WHETHER IN CONTRACT STRICT LIABILITY OR TORT INCLUDING NEGLIGENCE OR OTHERWISE ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE lwIP is licenced under the BSD licence Copyright c 2001 2004 Swedish Institute of Computer Science All rights reserved Redistribution and use in source and binary forms with or without modi...

Page 24: ...NG BUT NOT LIMITED TO PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES LOSS OF USE DATA OR PROFITS OR BUSINESS INTERRUPTION HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY WHETHER IN CONTRACT STRICT LIABILITY OR TORT INCLUDING NEGLIGENCE OR OTHERWISE ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Author David van Moolenbroek david minix3 org MD5 routi...

Page 25: ...ents of the University of California All rights reserved Redistribution and use in source and binary forms with or without modification are permitted provided that the following conditions are met 1 Redistributions of source code must retain the above copyright notice this list of conditions and the following disclaimer 2 Redistributions in binary form must reproduce the above copyright notice thi...

Page 26: ...utions of source code must retain the above copyright notice this list of conditions and the following disclaimer Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other materials provided with the distribution Neither the name of the Eclipse Foundation Inc nor the names of its contributors may ...

Page 27: ...tions distributed in accordance with this Agreement Recipient means anyone who receives the Program under this Agreement including all Contributors 2 GRANT OF RIGHTS a Subject to the terms of this Agreement each Contributor hereby grants Recipient a non exclusive worldwide royalty free copyright license to reproduce prepare derivative works of publicly display publicly perform distribute and subli...

Page 28: ...ed warranties or conditions of merchantability and fitness for a particular purpose ii effectively excludes on behalf of all Contributors all liability for damages including direct indirect special incidental and consequential damages such as lost profits iii states that any provisions which differ from this Agreement are offered by that Contributor alone and not by any other party and iv states t...

Page 29: ...ted to those performance claims and warranties and if a court requires any other Contributor to pay any damages as a result the Commercial Contributor must pay those damages 5 NO WARRANTY EXCEPT AS EXPRESSLY SET FORTH IN THIS AGREEMENT THE PROGRAM IS PROVIDED ON AN AS IS BASIS WITHOUT WARRANTIES OR CONDITIONS OF ANY KIND EITHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTIES OR COND...

Page 30: ...o publish new versions including revisions of this Agreement from time to time No one other than the Agreement Steward has the right to modify this Agreement The Eclipse Foundation is the initial Agreement Steward The Eclipse Foundation may assign the responsibility to serve as the Agreement Steward to a suitable separate entity Each new version of the Agreement will be given a distinguishing vers...

Page 31: ...This page intentionally left blank ...

Page 32: ...last page 2018 HMS Industrial Networks Box 4126 300 04 Halmstad Sweden info hms se SCM 1202 109 1 0 en US 2018 10 29 10377 ...

Reviews: