34
Parameters for Digital Channel Configuration
(channel numbers 1-50 are pre-defined digital channels)
Parameter
Code
Reference
Description
Default
Modbus
Function
Code
0 – None
1 – Read Coil
2 – Read Status
5 – Write Coil
7 – Read Packed digitals and select
individual bit (16-bit)
9 – Read Packed digitals and select
individual bit (32-bit)
30 – Read Packed Bit in Input (16-bit)
32 – Read Packed Bit in Input Double
(32-bit)
23
Bit
Number
When reading holding registers as
packed digitals, this defines the bit
number to monitor.
1
Range 1-32 where 1 is LSB
7.8
Report Flag Configuration – Type 12
There are several report types that can be generated by the Messenger, each with a
unique trigger mechanism. Report flags are used to enable specific channel data to be
included in specific report types.
Parameters for Report Flag Configuration
Parameter
Code
Report
Type
Description
Trigger
3
Standard
(PER)
Include all channels that have a
PER report flag set.
By default all channels.
Standard Report
Interval (time
based only)
4
End of Day
(EOD)
Include all channels that have an
EOD report flag set.
By default no channels
Midnight (UTC
Time)
5
Demand
(DEM)
Include all channels that have a
DEM report flag set
Request from the
web server