3.3 Information on EMC 

In order to warranty electromagnetic compatibility (EMC) in your switch cabinets in an 
electrically raw environment, the following EMC rules are to be observed during construction 
and set-up: 
 

  All metallic parts of the switch cabinet are to be connected flatly and in a well-conducting 

manner (not lacquer on lacquer!). If necessary, use contact or scraper wafers. The 
cabinet door is to be connected with as short a circuit as possible via the metal powder 
tapes (upper, middle, lower). 

  Signal lines and power cables are to be laid separated from each other in order to avoid 

coupling intervals. Minimum distance: 20 cm: 

  Signal lines should be led to the cabinet from only one level, if possible. 

Unshielded lines from the same electrical circuit (outgoing and return circuit) are to be 
transposed, if possible. 

   Contactors, relays and magnetic valves in the switch cabinet, if necessary in the adjacent 

cabinets, are to be wired with suppressor combinations, e.g. with RC elements, varistors 
or diodes. 

  The braiding from signal lines are to be laid two-way (source and target), large-area and 

well-conducting to a ground

1

. In case of poor potential equalization between shielded 

connections, an additional balancing network of at least 10 mm² must be laid parallel to 
the braiding to reduce the current. 

  Wiring is not to be laid freely in the cabinet, but should rather lead as tightly as possible to 

the cabinet frame or to installation plates. This also applies to reserve cables. At least one 
end of them must be grounded, but preferably both (additional shield effect). 

  Unnecessary wire lengths are to be avoided. Coupling capacities and coupling 

inductance’s are thereby kept small. 

  The braiding from leads, such as resolver or incremental tachometer cables, must be laid 

to the frame grounding. Approximately 2 cm of the insulation is to be removed in the area 
where the cable is to be led into the frame in order to expose the braided cable. The 
braided cable may not be damaged while removing the insulation. The cable is to be led 
at the position where the insulation has been removed by grounded terminals or taut 
supports. 

 

 

cable 

clamping y

ok

e

 

 

 

 
 
 
 
                                                

1

Generally all metallic conducting parts which can be connected to a protective conductor, 

such as cabinet frames, motor frames, foundation grounding, etc. are designated as a 
ground.

 

Summary of Contents for ECD3AM-00-00

Page 1: ...Operating Manual ECD3AM 00 00 Page 1 of 13 07 16 R0117AGB Operating Manual Retrofit Speed Controller Type ECD3AM 00 00 Replacement for ECdrive Type D400B001 Ziehl Abegg...

Page 2: ...LECTRICAL INSTALLATION 6 3 3 INFORMATION ON EMC 7 3 4 ELECTRICAL CONNECTION CONTROLLER 8 3 5 OPERATING AND DISPLAY ELEMENTS 9 3 6 ADJUSTMENT 9 3 7 ADJUSTMENTS INTERNAL 10 3 8 CODING JUMPERS INTERNALLY...

Page 3: ...thoroughly Ensure that the voltage is less than 60V before touching electrical contacts The user must use independent monitoring units in order to ensure that a malfunctioning drive is stopped safely...

Page 4: ...0 90 UZK Max output current IMmax 6 5 A Phase Continuous output current IM 3 A Phase Rated output power 1 SN 0 9 kVA Efficiency ca 95 Power loss idling2 PV0 ca 18 W Power loss full load PV ca 50 W Ma...

Page 5: ...Operating Manual ECD3AM 00 00 Page 5 of 13 07 16 R0117AGB 2 2 Dimensions...

Page 6: ...tricity The discharging can be achieved by touching a grounded metal surface beforehand Due to the leakage currents of the controller 3 5 mA via the protective conductor PE must be in accordance with...

Page 7: ...nes are to be laid two way source and target large area and well conducting to a ground1 In case of poor potential equalization between shielded connections an additional balancing network of at least...

Page 8: ...nes Motor 1 RLG U 2 RLG V 3 RLG W 4 Encoder active High n c 5 Encoder active Low 6 Supply voltage 7 Supply voltage 8 Shield X8 Connectors for signal lines 1 15 V 2 0 V 3 Com Opt out 4 Ready 5 Stand st...

Page 9: ...N Controller ready OFF Controller collective fault Intermediate circuit 450 V Intermediate circuit 150 V Heat sink temperature 80 C If there is a fault the output stage is disabled immediately The fau...

Page 10: ...the engine at standstill n n max Sollwert 10V 0V I max Internal factory setting may not be changed tH Ramp up time of the set point integrator tR Return time of the set point integrator Setting the s...

Page 11: ...SET n max PI tH tR STB1 Jumper position a Brake A cut off of the control voltage on connecting terminal 2 5 and or X2 6 causes the motor to come to a standstill This is the normal operation mode of th...

Page 12: ...STB1 S1 L2 UZK Rotation direction logic Set point intergator Drehzahlregelung monitoring heatsink temperature UZK switching power internal voltage supply counter clockwise clockwise Output stage enge...

Page 13: ...hnical documentation the measures are described with which the drive regulator complies with the EMC limiting values The electromagnetic compatibility of the machine is based on the method and thoroug...

Reviews: