ANTAIRA STM-60 C Series Hardware Manual Download Page 5

Antaira Technologies 

– Industrial Modbus Gateway 

STM-60XC(-T) Series Hardware Manual V1.1 

 

 

 

1. Introduction 

The STM-60XC series Modbus gateways are bi-directional gateways for integrating new and existing 

Modbus/RTU and Modbus/ASCII serial devices to newer TCP/IP networked-based devices. The STM-

601C/602C/604C feature two independent Ethernet ports and MAC addresses to provide redundancy 

and reliability. They provide a simple and cost-effective way to bring remote management and data 

accessibility to thousands of devices that cannot connect to a network. STM-601C/602C/604C provide 

a feature that can allow users to select either master or slave operation mode for each serial port. 

They not only allow an Ethernet master to control serial slaves, but also allow serial masters to control 

Ethernet slaves. 

1.1 Product Overview 

Antaira’s STM-60XC series of Modbus Gateways are a robust, feature-rich, and cost-effective way to 

integrate Ethernet and Serial Modbus devices. The STM-60XC series provides one, two, or four serial 

ports, two Ethernet ports, a wide range of power inputs, and a compact slim design, making them an 

ideal solution for connecting multiple Modbus/RTU and Modbus/ASCII serial devices to Modbus TCP 

(Ethernet). 

 

Originally developed for PLCs in industrial automation and manufacturing control applications, 

Modbus is one of the most popular open standard protocols in use today. The communication mode 

can be Modbus RTU/ASCII (Serial) or Modbus TCP (Ethernet). Many industrial devices use Modbus 

as their communication standard. However, the Ethernet-based Modbus protocol is different from the 

original serial-based protocols in that a Modbus Gateway is needed to be a bridge for integration. 

 

The two Ethernet ports allow the STM-60XC series to establish two separated Ethernet connections 

to two Ethernet domains or two Ethernet switches in the same domain. Through a dual Ethernet 

connection, the STM-60X series greatly improves the device connectivity reliability, increases system 

stability, and simplifies the redundant configuration. 

 

The Mo

dbus/RTU and Modbus/ASCII protocols define how a “master” device pulls one or more 

“slave” devices and writes real-time data over RS-232, RS-422, or RS-485 serial data communication. 

The STM-60XC series provides a feature that can allow users to select either master or slave 

operation for each serial port. The STM-60XC series not only allows Ethernet masters to control serial 

slaves, but also allow serial masters to control Ethernet or serial slaves. Furthermore, the STM-60XC 

series can allow both Ethernet and serial slaves to be controlled by both Ethernet and serial masters. 

 

The STM-60XC series supports various operating modes: RTU Master, RTU Slave, ASCII Master, 

and ASCII Slave 

 

Summary of Contents for STM-60 C Series

Page 1: ...Antaira Technologies Industrial Ethernet Switches LMX 1202G SFP Series User Manual V1 0 STM 601C 602C 604C T Series 1 2 4 Port Modbus Gateway Version 1 1 Hardware Manual...

Page 2: ...Notice Copyrights 2018 by Antaira Technologies LLC All rights reserved Reproduction adaptation or translation without prior permission of Antaira Technologies LLC is prohibited except as allowed under...

Page 3: ...rence by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit d...

Page 4: ...3 Product Hardware Features 2 1 4 Package Contents 3 1 5 Safety Precaution 3 2 Hardware Description 4 2 1 Physical Dimensions 4 2 2 Front Panel 6 2 3 Top View 9 2 4 Rear View 10 2 5 LED Indicators 10...

Page 5: ...rial automation and manufacturing control applications Modbus is one of the most popular open standard protocols in use today The communication mode can be Modbus RTU ASCII Serial or Modbus TCP Ethern...

Page 6: ...otection for all serial signals Automatic RS 485 data flow control Supports surge protection for D C power ports with line to line 2 KV and line to earth 4 KV for signal ports to 4KV 1 3 Product Hardw...

Page 7: ...it please use a protection device on the power supply input The industrial Ethernet switch s hardware specs ports cabling information and wiring installation will be described within this user manual...

Page 8: ...Series Hardware Manual V1 1 4 14 90 17 83 150 47 05 140 149 80 47 95 2 Hardware Description 2 1 Physical Dimensions The following view in Figure 2 1 shows the STM 601C and STM 602C 3 3 3 5 1 5 104 95...

Page 9: ...Industrial Modbus Gateway STM 60XC T Series Hardware Manual V1 1 5 140 47 05 1 47 951 149 80 23 83 14 70 The following view in Figure 2 2 shows the STM 604C 33 35 15 104 95 30 50 40 48 65 Figure 2 2...

Page 10: ...bus Gateway is shown below in Figure 2 3 Figure 2 3 The Front Panel of STM 601C T Series No Item Description 1 System LED panel See LED Indicators on page 13 for further details 2 Default Button Press...

Page 11: ...T Series Figure 2 4 The Front Panel of STM 602C T Series No Item Description 1 System LED panel See LED Indicators on page 13 for further details 2 Default Button Press for at least 10 secs to reset d...

Page 12: ...gure 2 5 The Front Panel of STM 604C T Series No Item Description 1 System LED panel See LED Indicators on page 13 for further details 2 Default Button Press for at least 10 secs to reset device to de...

Page 13: ...Top View Figure 2 6 Top Panel View of STM 60XC Series No Item Description 1 Ground Terminal Screw terminal used to ground chassis 2 Terminal block Connect cabling for power and alarm wiring 3 Wall mo...

Page 14: ...cators There are LED light indicators located on the front panel of the industrial Modbus Gateway that display the power status and status of the device Each LED indicator has a different color and ha...

Page 15: ...components except those specifically designated for the serial device server Caution Disconnect the power cord before installation or cable wiring The STM 60XC series supports dual 12 to 48 VDC power...

Page 16: ...N Rail Mounting Kit 1 Push the server down to free the bottom of the plate from the DIN Rail 2 Rotate the bottom of the device towards you and away from the DIN Rail 3 Once the bottom is clear of the...

Page 17: ...e wall mount plates as a guide to mark the locations of the screw holes 8 Drill four holes over the four marked locations on the wall keeping in mind that the holes must accommodate wall sinks in addi...

Page 18: ...Technologies Industrial Modbus Gateway STM 60XC T Series Hardware Manual V1 1 14 2 1 2 Figure 3 5 Wall Mount Installation 13 Once the device is installed on the wall tighten the screws to secure the...

Page 19: ...ual V1 1 15 4 Serial Connection STM 60XC series provides up to four ports DB9 male connectors RS 232 422 485 pin assignments as below 1 5 6 9 Figure 4 1 DB9 Pin Assignment Pin 1 2 3 4 5 6 7 8 9 RS 232...

Page 20: ...er lines should be properly insulated as well as other cables Be careful when handling them so as to not trip over Do not under any circumstance insert foreign objects of any kind into the heat dissip...

Page 21: ...ting hardware Installation DIN Rail and Wall mount Dimensions WxHxD STM 601C STM 602C 37 x 140 x 95mm 1 46 x 5 51 x 3 74 STM 604C 55 x 140 x 95mm 2 17 x 5 51 x 3 74 LED Display System LED Power 1 Powe...

Page 22: ...eration Modes Modbus RTU Master Slave mode Modbus ASCII Master Slave mode Configuration Windows utility Web Browser Management SNMP MIB II Regulatory Approvals EMC CE FCC Part 15 Subpart B Class A Saf...

Reviews: