Connectors 

A 7-pin connector rests on top of the 

STF-502C series

 

and provides connections for dual DC power input as 

well as for the alarm relay contacts. 

Power 

STF-502C series

 supports dual power inputs for 

redundant operation. PWR1 and PWR2 are the 

designations for the individual power inputs. Follow 

the DC voltage polarity as indicated for the connector 

markings. 

Alarm 

This is one electrical relay that can be wired into an 

alarm circuit. From the common pin (COM), the relay 

can be connects as Normally Open (NO) or Normally 

Closed (NC). 

RS-485/422 Serial 

A 5-pin connector provides the balanced transmit and 

receive for RS-485/422 along with an isolated ground 

connection. For 2-wire RS-485, make connections only 

to RX- and RX+ pair. 

RS-232 

A female DB9 provides two RS-232 channel 

connections with isolated ground. The first channel, 

using pins 2 (TD), 3 (RD) and 5 (SG) mirror the RS-485 

channel. Both of these may transmit simultaneously, 

but only one can receive at one time. The second RS-

232 channel uses the non-standard pin assignment of 

pin 7 (RD), pin 8 (TD) and pin 5 (SG). This second RS-

232 channel can run completely independently of the 

main RS-485 channel at up to 115.2k. 

 

 

 

 

 

 

 

 

LED Indicators 

The 

STF-502C series

 has a nine LED matrix, with the 

following indications. 

 

 

 

 

 

 

 

 

 

 

Alarm

: This red LED will light if the power or fiber has 

an alarm condition. Alarm conditions are also 

dependent on the setting of DIP switch poles no. 1 & 2. 

PWR2

: This green LED will light if power is connected 

and active at the PWR2 terminal connection. 

PWR1

: This green LED will light if power is connected 

and active at the PWR1 terminal connection. 

TD and RD

: These green LEDs represent binary '1' 

(mark) when off or binary '0' (space) when lit for either 

transmit or receive signals. 

Master

: This green LED is lit when DIP switch no. 3 is 

on, the mode is set to 'master'. 

Ring

: When connected in a ring topology and with no 

fiber faults, this green LED will be illuminated. 

Fiber 2

: This green LED will light when the 2nd fiber 

port has an optical link. 

Fiber 1

: This green LED will light when the 1st fiber 

port has an optical link. 

 

Operation Mode Switch 

STF-502C series

 uses a 6-pole DIP switch for 

configuration. Each switch has the following functions. 

 

 

 

 

 

 

1. 

Power Alarm

: When 'On' this switch will enable 

alarm relay if either power input loses power. If only 

using single power input, leave this switch 'Off'. 

2. 

Fiber Alarm

: When 'On' this switch will enable alarm 

relay if either fiber port loses link. If only one fiber port 

is being used, leave this switch 'Off'. 

3. 

Mode

STF-502C series

 can operate in point to 

point, point to point with redundant fiber link, with 

fiber cascaded or with fiber forming a ring topology. In 

each case, one unit will be configured as a 'master' 

(this switch 'On') and any other unit(s) will be 

configured as 'slave' (this switch 'Off'). 

4. 

2W/4W

: This switch determines if the RS-485 will 

operate in 4-wire mode (switch 'Off') or in 2-wire half 

duplex (switch 'On'). 

5. 

Ring Alarm

: When operating in ring topology, 

enabling this switch 'On' will provide an alarm 

indication if the fiber ring connection has a fault. Leave 

this switch 'Off' for non-ring applications. 

6. 

Termination

: In RS-485 communications, 

termination at the ends of copper links is required to 

avoid electrical reflections that would cause data 

errors. This switch, when 'On', will enable a 120 ohm 

terminator on the RS-485. 

 

 

 

 

 

Pull High / Pull Low 

Pull up or pull down resistors are established to fail-

safe bias of each data line/wire when the lines are not 

being driven by any device. The lines will be biased to 

known voltages and nodes will not interpret the noise 

from un-driven lines as actual data.  

 

STF-502C series

 uses rotary switches to select from ten 

different bias resistor values. The factory default 

setting is at position 4, and provides bias resistors of 

1KΩ in the pull high and pull low positions. When 

changing the rotary switches, it is important to 

maintain the same setting on both switches. 

 

 

 

 

 

 

 

Position  Resistance 

(Ohms) 

100K 

9.9K 

5K 

3.3K 

1K (default) 

920 

840 

774 

500 

475 

 