4-2
Using Quick CFIG to Autoconfigure a Panel
Using Quick CFIG to
Create a New Job
The AUTOPULSE Z-28 FACP includes the Quick CFIG utility, an automatic configuration
tool that detects AUTOPULSE Z-28 points. For most new installations, it is more efficient to
run AUTOPULSE Z-28 Quick CFIG from the front panel and then upload the CFIG from the
AUTOPULSE Z-28 to the PC Programmer, where changes to point types, custom labels, and
system options can be made.
Using Quick CFIG on a new panel configures the panel for general alarm operation as follows:
•
All initiating devices found by Quick CFIG are assigned a FIRE point type.
•
SIG1 and SIG2 are set to point type SSIGNAL. SIG3 and SIG4 are set to RSIGNAL.
•
AUX1 is set to point type RRELAY. AUX2 is set to TRELAY.
•
Remote annunciators are detected at their set address.
Hardware that is not automatically configured includes:
•
Graphic annunciators
•
Suppression points
Quick CFIG Reconfigure
All Hardware Option
The Quick CFIG Reconfigure All Hardware option, described in this section, creates a new
AUTOPULSE Z-28 configuration.
Notes:
•
If a configuration exists and this option is selected, it clears the current configuration and
adds all currently connected devices to the CFIG.
•
Quick CFIG terminates if duplicate SLCnet devices are detected. If this happens, run
Quick CFIG again and watch the LCD. Before the program terminates, it will list the first
seven duplicate addresses found.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and then press
<ENTER>. A warning appears, indicating that the AUTOPULSE Z-28 is no longer in the
Fire Alarm Operation mode.
Continued on next page
Figure 4-1. Wait Screen
Please Wait . . .
Fire Alarm Operation Suspended