NFPA Applications
NFPA 72 Proprietary Fire Alarm Systems
138
IQ-301 PN 50036:F 10/29/2001
B.4.3 Using an RTM-8 Module
Figure 134 shows typical wiring for an RTM-8 module to a UL-listed Fire•Lite RS-82
Remote Station Receiver. For this application, note the following:
•
RTM-8 jumper JP2 must be in position AL/TR REV. POL. for use in alarm and
trouble transmission
or
AL ONLY for alarm transmission only.
•
For additional information on the RS-82, refer to the Fire•Lite Alarms, Inc. RS-82
Instruction Manual.
•
The RTM-8 is not suitable for separate transmission of both alarm and trouble
signals to a remote station.
•
Cut jumper JP5 on control panel CPU board.
Figure 134 Remote Station Connections Using an RTM-8 Module
B.5 NFPA 72 Proprietary Fire Alarm Systems
Figure 135 shows typical connections between an AUTOPULSE IQ-301 control panel
and receiving unit (NIB-96 in an AM2020) for a proprietary fire alarm application.
Table 51 lists wiring connections for the NIB-96, AM2020, and IQ-301.
•
Program the IQ-301 for ACS annunciation mode and set switch (SW2) on the CPU
board for ACS mode. The ACS interface will automatically transmit General
Alarm, General Trouble and General Supervisory signals and will receive
Acknowledge, Silence, and Reset commands automatically from the
AM2020/AFP1010 control panel. Zone alarm and zone trouble information may
be transmitted by programming the IQ-301 points to software zones 1 through 88.
•
Up to ten IQ-301 Protected Premises Units may be monitored by one
AM2020/AFP1010 Receiving Unit using ten SLC loops and ten NIB-96 modules.
•
Disable the ground fault circuit on the IQ-301 by cutting jumper JP9 because the
AM2020/AFP1010 performs ground fault protection for the control panel circuits.
RTM-8 Relay Transmitter Module
Jumper Settings:
Alarm/Trouble Polarity
Reversal
Remote Station
JP1 must be cut
Alarm only Polarity Reversal
Remote Station
JP1 must be cut
Polarity Shown
is Non-Alarm
Polarity Shown is Non-Alarm
JP1
JP2
Fire•Lite RS-82 Remote Station Receiver
Summary of Contents for AUTOPULSE IQ-301