Ansul AUTOMAN II-C Installation, Operation And Maintenance Manual Download Page 5

INSTALLATION INSTRUCTIONS

UL R5998      6-16-95      Page 3

MOUNTING “ANSUL AUTOMAN” II-C RELEASE
(Continued)

FIGURE 4

001805

4. Use one of the 1/2 in. (13 mm) knockouts provided in

the top, bottom or side of the release enclosure to exit
the pipe and install balance of pipe, fittings and pressure
relief valve as shown in Figure 5. Wrench tighten all pipe
joints to prevent leakage of gas. All applications will
require an actuation line pressure relief device, such as
a line vent or pressure relief valve. The type of pressure
relief device used will be determined by the type of sup-
pression system. Refer to the Installation, Operation and
Maintenance Manual provided with the Ansul Fire
Suppression System for the correct actuation line vent
or pressure relief valve.

FIGURE 5

001806

5. If remote manual cable pull station is to be installed,

complete the steps in the following section. Otherwise,
go to WIRING THE ANSUL AUTOMAN II-C RELEASE
on page 4.

REMOTE MANUAL PULL STATION INSTALLATION
(CABLE TYPE)

The remote pull station, (Part No. 4835) allows the ANSUL
AUTOMAN II-C to be manually actuated from some point
distant from the release. Refer to appropriate NFPA
Standards and the ADA (Americans with Disabilities Act) for
mounting guidelines.

1. Select location for mounting manual remote cable pull

station. (Pull station must be located within 100 feet
(30.5 m) of the release or as stated in the Installation,
Operation and Maintenance Manual provided with the
Ansul Fire Suppression System.)

2. Fasten 4 in. (102 mm) junction box (not furnished)

where pull station is to be mounted. (Position the junc-
tion box with printing right side up.)

3. Install and secure 1/2 in. (13 mm) rigid conduit from

ANSUL AUTOMAN II-C release assembly to pull station
using pulley elbows (Part No. 45771) for changes in
direction. (Do not use more than 8 pulley elbows
between the release and the pull station.)

4. Feed wire rope through pull station junction box and

conduit into release. Make sure wire rope rides on top of
and in center of pulley sheave. If the 50 ft. (15.2 m) wire
rope provided is not long enough, obtain wire rope (Part
No. 4595) and splice lengths with two sleeves (Part No.
4596). Do not allow wire rope splice to be within 12 in.
(30.5 cm) of any pulley elbow.

5. Fasten pull station assembly cover to junction box.

6. Thread wire rope through rear guide hole in manual trip

lever on release. See Figure 6.

7. Pull slack out of wire rope and thread end through

sleeve (Part No. 4596).

8. Loop the wire rope back up around and through top of

sleeve.

9. Position sleeve approximately 1/2 in. (13 mm) from trip

lever and crimp to secure wire rope.

10. Make certain ring pin is not installed in release puncture

pin assembly.

11. Remove red glass indicator rod from pull station by

removing set screws on side of stud and slide rod out.

12. Pull ring on pull station. If release mechanism is tripped

easily, pull station is properly installed. If release does
not trip easily, remove pulley covers and check to see
that wire rope is correctly positioned in pulley elbow
sheave.

13. Cut off excess wire rope 3/4 in. (19 mm) below sleeve

assembly.

14. Reinstall glass indicating rod.

15. Proceed to “WIRING THE ANSUL AUTOMAN II-C

RELEASE.”

1/4 IN. (6.4 mm) CLOSE NIPPLE

45° ELBOW, 1/4 IN. (6.4 mm)

90° ELBOW, 1/4 IN. (6.4 mm)

3/8 IN. X 1/4 IN.
(9.5 mm X 6.4 mm)
REDUCING BUSHING

ACTUATION
LINE VENT

PRESSURE
RELIEF VALVE

CAUTION

!

Do not install cartridge until all testing has been completed
and the system is ready to be armed as instructed on
page 6.

Summary of Contents for AUTOMAN II-C

Page 1: ...INSTALLATION ANSUL OPERATION AND AUTOMAN II C MAINTENANCE RELEASING MANUAL DEVICE ANSUL 001799...

Page 2: ...icular interest depending upon one s responsibility ANSUL AUTOMAN II C is an electrical mechanical device It requires periodic care Maintenance to provide maximum assurance that your releasing device...

Page 3: ...remote manual cable pull station ANSUL AUTOMAN II C RELEASING DEVICE FIGURE 1 004300 1 VISUAL INDICATOR WINDOW 2 WIRING INSTRUCTIONS 3 RELEASE MECHANISM 4 RESET LEVER 5 STRIKE BUTTON 6 ELECTRIC SWITC...

Page 4: ...tion Operation and Maintenance Manual pro vided with the Ansul Fire Suppression System for the maximum allowable length of actuation line piping INSTALLATION INSTRUCTIONS UL R5998 6 16 95 Page 2 TO EX...

Page 5: ...secure 1 2 in 13 mm rigid conduit from ANSUL AUTOMAN II C release assembly to pull station using pulley elbows Part No 45771 for changes in direction Do not use more than 8 pulley elbows between the r...

Page 6: ...d install jumper J2 across terminals 4 and 5 Terminals 1 through 3 are provided for auxiliary device con nections Auxiliary equipment is controlled through the action of switch S1 Refer to the followi...

Page 7: ...the Installation Operation and Maintenance Manual s furnished with the Ansul Fire Suppression System and disarm remove the agent tank assembly actuation mechanism before test firing 2 Check ANSUL AUTO...

Page 8: ...and replace if cartridge weight is 1 4 oz 7 1 g or more below weight stamped on car tridge Install fully charged cartridge and hand tighten Refer to the Installation Operation and Maintenance Manual p...

Page 9: ...TRIKE button and open enclo sure 2 Insert ring pin as shown in Figure 9 3 Remove cartridge and install safety shipping cap 4 Perform steps 2 through 4 in the TEST OF WIRING section on page 5 5 Perform...

Page 10: ......

Page 11: ......

Page 12: ...Part No 17788 09 1995 Ansul Incorporated Litho in U S A ANSUL INCORPORATED ONE STANTON STREET MARINETTE WI 54143 2542...