Maintenance:
1.
This luminaire contains no serviceable parts.
2.
If replacing the LED Driver, please ensure the driver is the correct physical size for the housing and the secondary output / wattage is correct
matching that of
the existing LED Driver
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Page No. 2
www.anselluk.com
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the Environment Agency for
further information.
RoHS -
All components and materials used in this product are
RoHS
2002/95/EC compliant.
MONTH
TEST
Signed
Date
Signed
Date
Signed
Date
Signed
Date
Signed
Date
1
FUNCTIONAL
2
FUNCTIONAL
3
FUNCTIONAL
4
FUNCTIONAL
5
FUNCTIONAL
6
FUNCTIONAL
7
FUNCTIONAL
8
FUNCTIONAL
9
FUNCTIONAL
10
FUNCTIONAL
11
FUNCTIONAL
12
3 HOUR
FIFTH YEAR
FIRST YEAR
SECOND YEAR
THIRD YEAR
FORTH YEAR
Should a fault occur then the following can be observed:
If there is a failure of the battery such that it becomes disconnected then there will be a continuous red LED
If the system fails the 3 hour duration test then the red LED will flash slowly
If the LED
’s fail the red LED will flash quickly.
Operating and recommended Routine Test Procedure
Follow these instructions carefully to ensure safe and reliable operation of this emergency luminaire. The following testing is designed to ensure the
continued protection of your premises and occupants, in the event of the possibility of a failure of the normal lighting supply.
Testing should be carried out in accordance with the recommendations of BS5266-8-2004.
A daily check
– check LED charge indicator is illuminated
Every 30 days
–
the fixture will be tested for 10 minutes functional emergency operation.
Every year, a full three hour duration test
– the luminaire will simulate a mains supply failure for a three hours continuous test.
To assist with this testing, a test record is included. If the luminaire fails any of the above tests, please contact a qualified electrician.
Warning
Disconnect the mains supply and unplug the battery leads before working on the unit.
Failure to comply with these instructions may result in irreparable damage to the emergency control gear.
This product must not be modified in any way as this will negate any Safety approvals, and may render the product inoperable or
unsafe. The product must be installed in accordance with the instructions. Operating and Recommended Routine Test Procedure
IP20