andrews PAC15 Operating Instructions  & Safety Manual Download Page 2

Operating Instructions - 

PAC15

Click

 www.andrews-sykes.com 

or Call Us Free

 0800 211 611

only be determined by the user. However, you should never allow more than two 
months to elapse between cleaning. The probable life of the filter will be about one 
year and spares are available from the supplier of the unit itself. Failure to have filter 
fitted during operation will cause serious damage. 

The refrigeration circuit inside the room unit is fitted with a HIGH and a LOW 
pressure sensing switch. They are both manually re-settable. Necessary access is 
provided either via the lower front panel or through the control console. A pencil or 
screwdriver with gentle pressure on the knob behind is all that is required to re-set.

HOWEVER, DO NOT ATTEMPT TO RE-sET WITHOUT FIRsT DIsCOVERING 
WHY THE TRIP OCCURRED IN THE FIRsT PLACE

Installation 

UsE THE CHAINs PROVIDED TO sUPPORT THE HEAT EXCHANGER - IT 
WOULD bE HIGHLY DANGEROUs TO sUPPORT THE HEAT EXCHANGER bY 
MEANs OF THE FLEXIbLE LINEs ALONE.

In operation the room unit is constantly condensing water vapour out of the 
atmosphere (reducing relative humidity). This water has to be drained away, An 
automatic condensate pump is fitted inside the room unit. The flexible hose outlet 
from the condensate pump runs to the outside, inside the flexible sheath and the 
condensate is deposited in the base of the heat exchanger, but please remember 
that there will also be a degree of dripping through the base of the heat exchanger. 

HAVE GREAT REGARD FOR THIs CHARACTERIsTIC WHEN POsITIONING THE 
EXTERNAL HEAT EXCHANGER

The flexible water pipes should be routed so as to avoid any possibility of kinking 
or unnecessary restrictions to the flow of water inside. Also, remember that plastic 
and rubber becomes much more flexible when warm and. as a result, much more 
susceptible to distortion.

Machine Link-Up

Ensure the mains supply lead to the room unit is disconnected, A 5m (extendable 
to 30m) line set to connect all services between the room unit and the external 
heat exchanger will have been suppled. The water pipe connections are by means 
of ‘quick connect  couplers’ . These are simple ‘push-on’ connectors which, 
when disconnected (after pulling back sprung loaded locking ring), re-seal the 
water system on either side. The complete system will have been filled with the 
necessary amount of water/ antifreeze prior to its arrival on site. A water proof 3 
pin quick connect electrical coupler (push fit with screw lock ring, hand tight only), 
and condensate drain pipe coupler 6mm clear polythene (push fit), should also be 
connected. Having made the couplings, the system is operational immediately.

Room Water Levels

The water system in the room unit will be to the correct level when delivered. 

However if for some reason the level has fallen, antifreeze (33%) and water will have 
to be added. The header tank filler and level indication is located to the rear of the 
room unit and can be accessed by removing the two screws holding the security 
plate over the filter tank cap. Ensure the machine is running in cooling mode 
before removing the header tank cap, and as with all the pressure caps, remove 
slowly. It is recommended that a mixture, by volume,  of one part antifreeze to two 
parts water is utilised, this will prevent freezing down to an external temperature 
of -20C/-5F. The approximate total volume of both the available systems, large or 
small room unit with external heat exchanger and lines is as follows. 

This unit MUsT be transported and operated in the upright position at all times.

Electrical Supply

WARNING! As standard this unit requires a 13 amp fused electrical supply rated at 
230 volts. -1N, 50Hz.

The unit will operate from a standard 13A wall socket. The size of any extension 
cable that may be 2-5mm2 minimum up to a maximum length of 10 metres. For 
longer lengths 4mm² cable must be used.  If the cable is on a ‘cable drum’ then 
ensure that it is completely unwound; serious complications will occur otherwise.

System Description

The system comprises a room unit cooling section, an external heat exchanger 
and the two are interconnected by means of a flow and return water pipe and 
an electrical supply to the heat exchanger fan. The room unit is fitted with an 
automatic condensate disposal pump which discharges the condensate via a small 
plastic pipe into the base of the external heat exchanger and all interconnecting 
pipes and electrics are enclosed in a flexible plastic sheath. In addition, both ends 
of each pipe are fitted  with ‘quick connect’ couplings that open on coupling but 
reseal to become water tight on disconnect. 

Airflow

The angled air outlets at the top of the room unit are fitted with air grilles that allow 
the angle of air outlet to be adjusted vertically and horizontally and, in conjunction 
with the fan speed control switch, the air velocity and direction can be carefully set 
up to obtain maximum coverage of the area being cooled without causing drafts. 
Care should be taken to avoid outlet air being obstructed as this will cause the air 
to ‘eddy’ around the unit resulting in recirculation and short/inaccurate cycling of 
the machine. Ideally, cold air should be directed to create a ‘blanket’ all across the 
ceiling area allowing natural convection to drop the air over the whole area at very 
low velocity. 

Siting

Ideally, the room unit should be positioned equidistant along he shortest wall in the 
room blowing down the length of the room. Of there is more than one unit in the 
same area, then they would normally be positioned side by side, and equidistant 
along the long wall, all pointing in the same direction. sometimes it may be 

filler cap

necessary to position units around the perimeter of an area but, in this case, great 
care should be taken to avoid one unit blowing cold air straight into another which 
will adversely affect the machine operation. Good and correct air flow is, perhaps, 
the single most important aspect of satisfactory applying portable air conditioners. 
If in doubt seek the advice of your supplier. 

The heat exchanger must stand external to the area being cooled and, preferably, 
in the outside atmosphere. It can stand freely on a flat surface or may be hung in 
the upright position, from a window-sill, balcony etc (see fig. 1).

1. Revolve thermostat knob fully 
CLOCKWIsE to the number ‘8’ position
2.  Plug in the room unit mains cable, and 

switch on the electricity, red mains light 
will illuminate.

3.  select ‘Fan Only’ with the mode switch. 

The fan will start.

4.  select ‘Fan speed’ with the fan speed 

switch, high or low depending on air 
velocity required. 

5.  select ‘Cooling’ with the mode switch, 

and revolve the thermostat knob fully 
ANTI-CLOCKWIsE to he number ‘1’ 
position. If fitted the external heat 
exchanger fan and the water pump in 
the room unit will start. After a delay of 
10 mins the green ‘Cooling’ light will 
illuminate and the machine will proceed 
to cool the air. 

Monitor the room temperature and when it has reduced to the desired level, very slowly 
revolve the thermostat knob back, clockwise until the green ‘Cooling’ light goes out. The 
room unit will now control the room temperature cooling automatically at this setting. 

Fig. 1

Fig. 2

Reviews: