30-3001-702
Continuum Power Supply Reference Rev A
Technical Manuals Online! - http://www.tech-man.com
Page 1: ...Technical Manuals Online http www tech man com...
Page 2: ...wners Continuum Power Supply Reference Version A Feb 1998 Andover Controls part number 30 3001 702 The information in this book is furnished for informational purposes only is subject to change withou...
Page 3: ...e to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expen...
Page 4: ...Andover Controls Corporation Technical Manuals Online http www tech man com...
Page 5: ...ion 1 Power Module Characteristics 2 Mechanical Installation 3 Input Power Connection 6 UPS Connections 9 External Power Indicator Connections 10 Output Power Connection 11 Operation 15 Troubleshootin...
Page 6: ...Andover Controls Corporation Technical Manuals Online http www tech man com...
Page 7: ...ttery back up system with integral charger Another allows 48VDC power based industries such as telecommunications to provide uninterrupted power to critical environmental monitoring and control equipm...
Page 8: ...modules for up to 60 minutes at 35 watts power consumption full operation of the CPU module only including modem and network interface with no I O power for 4 hours and backup of DRAM and real time c...
Page 9: ...mounted to a panel using screws Hardware facilitating both mounting methods is included as an integral part of the case design On the back of each module are molded DIN rail guide fingers The design...
Page 10: ...After the bottom is secure press the top clamp inward to complete the operation These clamps when extended provide an alternative method of mounting to the DIN rail You can mount the module directly t...
Page 11: ...ontinuum Power Supply Reference 5 Overall Dimensions The overall dimensions of the power supply unit are as shown 9 0 228 7 mm 6 70 170 2 mm 2 50 63 5 mm Technical Manuals Online http www tech man com...
Page 12: ...and a third wire tied to a common Earth ground High voltage AC Power wiring should be routed to the conduit opening nearest the AC power terminals Do not bundle or route AC Power wiring with low volta...
Page 13: ...ough the Andover Controls system The surge of current can destroy electronic components on the controller board Surges of much lower potential than lightning also impact the reliability of the equipme...
Page 14: ...50 power supply module is powered by an external 2 Amp 41 to 53 VDC source This source is connected via three screw terminals located at the bottom of the unit as shown below Earth Ground VIN VIN 48VD...
Page 15: ...to provide the hold up time specified by system requirements Using standard 12V or 24V batteries 120 to 160 W Hr the built in UPS circuitry provides a backup time of 60 minutes 35 Watts power consump...
Page 16: ...ower supply is turned on and receiving input power AC or DC Connection is via a two pin removable female Molex connector 14 56 7022 not supplied Wire the external LED as follows An optional cable asse...
Page 17: ...wo power status signals on pins 1 and 2 Their function is as follows AC Power is a logic signal that is intended to communicate to an attached CPU module that AC power is available When AC is interrup...
Page 18: ...plugs and jacks All modules except the power supply include two complementary module inter connectors The power supply becomes the first module feeding the CPU All other modules are then connected to...
Page 19: ...ely located group of I O modules The I O modules that are to be powered by the auxiliary supply still connect to the other modules so that data may flow between the functional blocks of the system how...
Page 20: ...the power supply In order to access these components you must remove the plastic cover from the case 1 Press both cover removal tabs inward simultaneously 2 Locate the two jumper components using the...
Page 21: ...e power on To remove power press the side marked O Status Indicators The power supply includes a green Main Power indicator which when illuminated indicates that primary power AC or DC is applied and...
Page 22: ...k that power is available and connected properly to the AC or DC Input power terminals This can be done using a multimeter If input power appears to be OK remove power and all other connections from t...
Page 23: ...model includes a separate Picofuse for the battery The fuse is inserted into socket holes on the board To remove gently pull the fuse from the board 3 Amp 250 VDC Slow Blow Fuse 5 Amp Pico Fuse For E...
Page 24: ...trols PS 48 DC 50 The 48V model includes a Picofuse The fuse is inserted into socket holes on the board To remove gently pull the fuse from the board 7 Amp 90 VDC Fuse Technical Manuals Online http ww...
Page 25: ...30 3001 702 Continuum Power Supply Reference Rev A Technical Manuals Online http www tech man com...