Installation
STEP 5
Venting Installation Guidelines
•
The following steps are for exterior ventilation.
Height and Clearance
IMPORTANT:
•
Vent system must terminate to the outside (roof or side wall).
• DO NOT
terminate the vent system in an attic or other
enclosed area.
• DO NOT use 4 in (10.2 cm) laundry-type wall caps.
• Use metal/aluminum vent only. A rigid metal/aluminum
vent is recommended.
• DO NOT use a plastic vent.
• Always keep the duct clean to ensure proper airflow.
• Calculate the following figures before installation:
1. Distance from the floor to the ceiling
2. Distance between the floor and the countertop/stove
3. A distance of 24 in to 30 in (61 cm to 76.2 cm) is
recommended between stove top and the bottom of
range hood. 30 in (76.2 cm) minimum is required for
gas stove tops.
4. Height of hood and duct cover.
For the most efficient and quiet operation:
• It is recommended that the range hood be vented
vertically through the roof through 6 in. (15.3 cm) or
bigger round metal/aluminum vent work.
• The size of the vent should be uniform.
• Use no more than three 90° elbows.
•
Make sure there is a minimum of 24 in (61 cm) of
straight vent between the elbows if more than one
elbow is used.
• DO NOT install two elbows together.
•
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
• The vent system must have a damper. If roof or wall
cap has a damper, you may remove damper flaps from
damper to increase air flow.
• Only one flange is needed in the air duct system, either
on top of the motor or outside.
•
Use silver tape or duct tape to seal all joints in the
vent system.
•
Use caulking to seal exterior wall or roof opening
around the cap.
24 in. (610 mm) Min / 30 in. (762 mm) Max
The minimum hood distance above cooktop must
not be less than 24 in (61 cm). A maximum of 30 in
(76 cm) above cooktop is highly recommended for
best capture of cooking impurities. Distances over
30 in are at the installer and user’s discretion.