VENTING REQUIREMENTS

IMPORTANT:

A  minimum  of  6”  round  or  3-1/4  x  10”  rectangular  duct  (purchased  separately)  must  be  used  to

maintain maximum airflow efficiency.

Always use rigid type metal/aluminum ducts if available to maximize airflow when connecting to

provided duct.

Please  use  Duct  Run  Calculation  below  to  compute  total  available  duct  run  when  using  elbows,

transitions and caps.

ALWAYS, when possible, reduce the number or transitions and turns. If long duct run is required,

increase duct size from 6” to 7” or 8”.  If a reducer is used, install a long reducer instead of a pancake

reducer.  Reducing duct size will restrict airflow and decrease airflow, thus reduce duct size as far

away from opening as possible.

If turns or transitions are required, install as far away from opening and as far apart, between two

(2), as possible.

Minimum mount height between stove top to hood bottom should be no less than 24-inches and

no higher than 30-inches.

 •

It is important to install the hood at the proper mounting height.  Hoods mounted too low could result

in heat damage and fire hazard; while hoods mounted too high may be hard to reach and will lose its

performance and efficiency.

If available, also refer to stove top manufacturer’s height clearance requirements and recommended

hood mounting height above range.

CALCULATING VENT SYSTEM LENGTH:

To calculate the length of the system you need, deduct the equivalent feet for each vent piece used in the

system from the recommended maximum duct run.

Duct Run Calculation example:

One roof cap, two 90º elbows, and one 45º

elbow use

0ft + 9ft + 9ft + 5ft = 23ft used.

Deduct 23ft from 30ft, 7ft maximum

available for straight duct run.

-

Summary of Contents for Advanta Pro III 30

Page 1: ...II 30 36 o r P a t n a v d A l e d o M IMPORTANT SAFETY INSTRUCTIONS Carefully read the following important information regarding installation safety and maintenance Keep these instructions for future...

Page 2: ......

Page 3: ......

Page 4: ......

Page 5: ...ire nuts to connect incoming ground neutral and hot Push wires into the junction box and replace cover Be sure wires are not pinched C INSTALLATION DISTANCE Hood should be placed at a minimum distance...

Page 6: ...itions are required install as far away from opening and as far apart between two 2 as possible Minimum mount height between stove top to hood bottom should be no less than 24 inches and no higher tha...

Page 7: ...e unit and set in place with screws provided See Pic 1 a b c Connect duct work to damper Use Duct Tape to ensure joint is sealed and air tight Pic 1 A Top venting using rectangular damper If you requi...

Page 8: ...front facing you See pic 3 Remove the 2 filters to allow access to the inside of the unit See Pic 3 Cut tie wraps so wires are free to move and be relocated See Pic 4 Pic 3 Pic 4 Step 2 Remove rear ve...

Page 9: ...ast screw in place may break under the weight of the motor Once the motor is set free from the hood rotate motor clock wise to position venting outlet with rear rectangular hole ensuring that o Electr...

Page 10: ...d in step 2 to block top venting hole o Put plate in position and put in 4 screws from step 2 See Pic 10 Install rectangular air damper outlet on the rear vent location See Pic 11 Connect duct work to...

Page 11: ...7 185 mm m m 5 6 1 6 1 8 28 mm 7 185 mm 27 708 mm or 33 3 8 848 mm 7 8 m m 5 3 2 9 1 38 mm 90 mm 27 708 mm 4 108 mm 11 280 mm and 36 900mm width 27 7 8 708 mm or 33 3 8 848 mm 11...

Page 12: ...5 mm m m 5 6 1 6 1 8 28 mm 7 185 mm m m 5 3 2 9 1 38 mm 11 280 mm m m 8 0 1 4 1 8 28 mm 7 185 mm m m 5 3 2 9 1 38 mm top and 36 900mm width 27 7 8 708 mm or 33 3 8 848 mm 27 7 8 708 mm or 33 3 8 848 m...

Reviews: