Once you have answered the individual points, a report is printed out with the following information:
anapol
EU-50
CH-2555 Brügg, Switzerland
V3.00 SN 50xxx
Plant No.
000123
Measurement
No. 1
---------------------------------
TIME :
11:55:40
DATE :
04.03.04
---------------------------------
Fuel:
HEATING OIL EL
CO
2
max = 15.5 %
A2 = 0.68
B = 0.007
---------------------------------
Measurements:
TG :
38
°C
TA :
19
°C
TG - TA
:
19
°C
O
2
:
7.3
%
CO
2
:
10.1
%
CO
:
6 mg
3%O
2
NO
2
59 mg
3%O
2
Lambda
:
1.54
1.1
%
qAF
0.6
%
---------------------------------
Nominal output
: 400 kW
Boiler temp.
:
96°C
Full load
1. Re-check
---------------------------------
SAMPLE company
XY Anystreet
0000 Sampletown
Only the options that have also been declared appear on the report.
Options skipped with the
key do not appear
2.4.2
Save measurements
If you want to save your measurements:
Select
and continue with
. Data logging
= Yes.
If the measurements should also be printed out:
Select
with print-out
= Yes and continue with
.
1)
NO2+ g: calculated
2)
Calculation of exhaust losses
3)
Calculation of exhaust losses qA-F. See also explanations in "Evaluation of measurements qA-F"