The model VTC615R Rackmount Voltage Converter supplies either 12V, 24V, or 48 VDC from a 

24V, 48V or 72VDC power source.

All new Current Mode switching design offers increased power and reliability in a compact 

package. Extra input and output filtering reduce EMI to extremely low levels. Reliability 

features include an input fuse, thermal shutdown, current limiting, reverse battery hookup 

protection and output short circuit shutdown with automatic recovery. The output voltage is 

easily adjusted 1.0 volts above or below the standard output voltage. Devices connected to 

the converter 

are protected by an output overvoltage crowbar circuit. 

All rackmount units come standard with High quality digital output meters to allow monitoring 

of output current and output voltage. An optional Battery Back-up is also available. 

Specifications

Electrical (Input)

Nominal (ip)

24

36

48              

72

Actual (Vdc)

20-35           

**30-45

40-60           

65-90      

Input Amps (max)

39.5             

27.1

20.3             

12.6

Input Fuse (ATC)

3 x 15          

2 x ATC-15

1 x 25          

1 x 20

Noise on Input

< 50 mV

Electrical (Output)

Output Nominal (op)

12

24

48

Output Volts (DC)

13.6 ± 0.05      

27.2 ± 0.05      

54.4 ± 0.05      

Output Amps

40 cont. / 45 peak                    20 cont. /  25 peak                  10 cont. /  12.5 peak 

Output Crowbar

16.0 ± 0.5V      

32.0 ± 1.0V      

63.9 ± 2.0V                   

Output Adjustment

± 1.0 V

Switching Frequency

60 ± 2.0 KHz       

Idle Power

< 10 Watts

Output Ripple & Noise

< 10 Watts

Transient Response

< 2V for 50% Surge (Output Amps/2)

Regulation (Line & Load)

< +/- 0.5%

Duty Cycle

Peak 20% for 10 min max  
Continuous 100% for 24 hours per day

Efficiency

> 85% @ Maximum Output

Summary of Contents for VTC615R

Page 1: ...D DC DC VOLTAGE CONVERTER 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Page 2: ...Copyright 2005 2014 Analytic Systems Ware 1993 Ltd ...

Page 3: ...ttery acid to drip on converter when reading gravity or filling battery 7 O P CONNECTION PRECAUTIONS Connect and disconnect DC output connections only after setting the I P power switch to the off position Analytic Systems does not recommend the use of the VTC615 Series Voltage Converters in life support applications where failure or malfunction of this product can be reasonably expected to cause ...

Page 4: ...it All rackmount units come standard with High quality digital output meters to allow monitoring of output current and output voltage An optional Battery Back up is also available Specifications Electrical Input Nominal ip 24 36 48 72 Actual Vdc 20 35 30 45 40 60 65 90 Input Amps max 39 5 27 1 20 3 12 6 Input Fuse ATC 3 x 15 2 x ATC 15 1 x 25 1 x 20 Noise on Input 50 mV Electrical Output Output No...

Page 5: ... 87 600 hrs Isolation Input Case Input Output 1500VDC 500V 24V I P Output Case 500VDC 1500VDC 48V O P Mechanical Specification Depth 13 5 in 34 3 cm Width 19 0 in 48 3 cm Height 2u 3 5 in Material Marine Grade Aluminium Finish Black Anodize Fastenings All 18 8 Stainless Steel Weight 12 0 lb 5 5 kg Connections Four contact output terminals Warranty 3 years Safety Designed to meet CSA 22 2 107 1 UL4...

Page 6: ...sent the terminals will measure as a short circuit Assuming the output isolation diodes are present connect one 4 foot piece of 14 AWG red wire to each positive output terminal Connect all the positive wires to a distribution bus or connect them together and then connect from the common point to the load using the correct gauge of wire for the total output capability of all the supplies running in...

Page 7: ...ry small flat blade screwdriver to rotate the potentiometer Clockwise increases the output voltage and counter clockwise decreases it METERS The meter shows simultaneous voltage and current It features bright red LED readouts to permit easy monitoring from many feet or meters away Operation The dry contact output fail relay is accessed through the small 3 connection terminal block at the back of t...

Page 8: ...e maximum level The input voltage is not high enough for unit to operate LOW INPUT Indicates that the input voltage is below normal because The input voltage is not in the correct range for proper operation of the unit OVERTEMP Indicates that the voltage converter is running too hot because Too much power is being drawn turn off or unplug some devices The voltage converter is located in a poorly v...

Page 9: ...mp Components Conformal Dipping and RTV Compound Option w Wide Temperature Operation 40 to 55 C incl Option SM High Voltage Protection on the DC Input Side Option d Paralleling Diodes Option FI Forklift Modifications Option F Open Frame No chassis just heat sink bars not for all products Special Input There is no charge for nominal output voltages ie 12 0 24 0 48 0 but this must be noted at the ti...

Page 10: ...10 ...

Page 11: ...ing will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse neglect improper installation environmental conditions non autho rized repair alteration or accident 7 No refund of t...

Page 12: ... Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Reviews: