Analytic Systems VTC1000 Series Installation & Operation Manual Download Page 8

8

Dry Contact Relay

To use your dry contact output fail relay you must connect a 9-pin D connector to the unit. You 

must use pins one and six as is indicated on page 6 in the remote connector diagram.

The relay is factory preset to fail in the closed position when the low output LED and buzzer 

come on. If you wish to have the relay fail in the open position when the low output LED and 

buzzer come on, you must take the cover off the unit and move the jumper on J10 to the other 

position. J10 is located next to the relay K1.

To change the position of the jumper, first turn the unit off and disconnect the unit from both 

the power and load(s). Next, turn the unit on for 30 seconds to discharge the capacitors, then 

turn it off again. Remove the eight screws holding on the cover. Turn the unit upside down, 

remove the cover and locate J10. It will be next to the relay K1 as is shown in the above 

diagram. Simply move the jumper to the desired position as is shown in the above diagram. 

Replace the cover and re-install the eight cover screws. Reconnect the unit to the power and 

load(s).

Remote Control Option

Remote Connector

This connector is located on the side of the unit. Important: To prevent the possibility of High 

Voltage Electrical Shock, do not power up the Voltage Converter unless all wiring from the unit 

to the remote is securely connected. Do not remove the dust cover from the DB-9 connector if 

the remote is not being used.

IMPORTANT: 

 This remote is to be used only on 

Voltage Converters manufactured by Analytic Systems.

A remote control panel may be connected to the voltage converter using a 9-pin D-connector 

that attaches to the side of the voltage converter. The remote control panel and D connector 

are part of the remote control option. The remote control panel allows the unit to be operated 

remotely as well as duplicating all the diagnostic indicators and audible alarm.

Summary of Contents for VTC1000 Series

Page 1: ...es Voltage Converter 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers I...

Page 2: ...Revised Dec 18 2017 Copyright 2005 2017 Analytic Systems Ware 1993 Ltd...

Page 3: ...voltage con verter to OFF will not reduce this risk 5 Never place the voltage converter directly above a battery gasses from the battery will corrode and damage the voltage converter 6 Never allow bat...

Page 4: ...The VTC1000 Series Voltage Converter supplies either 12 24 32 or 48 VDC from a 110 250 or 300 VDC power source Other input voltages up to 300 volts or output voltages up to 48 volts are also availabl...

Page 5: ...Inch 2 5 cm all around Material Marine Grade Aluminum Finish Black Anodized Fastenings 18 8 Stainless Weight 12 lbs 5 5 kg Specifications subjects to change without notice Actual startup is at 22 42 o...

Page 6: ...ing of the circuit breaker in the distribution panel A ground stud is provided to bond the chassis to local ground to reduce or eliminate EMI OUTPUT CONNECTIONS Two Positive output terminals and two N...

Page 7: ...or meters away LOAD SHARE OPTION The units may be configured for load sharing if they are equipped with the optional output isolation diodes To confirm that your unit has these diodes use an ohmmeter...

Page 8: ...e next to the relay K1 as is shown in the above diagram Simply move the jumper to the desired position as is shown in the above diagram Replace the cover and re install the eight cover screws Reconnec...

Page 9: ...Batt 3 Turn the unit ON Battery Backup Optional 27 2V 1A Charger In Out Main PCB Chassis DC Output 28V Battery To Load 27 2V Batt Batt OP OP The Battery Backup circuit is designed so the battery is no...

Page 10: ...tage to drop to maintain the current at the maximum level The input voltage is not high enough for unit to operate LOW INPUT Indicates that the input voltage is below normal because The input voltage...

Page 11: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed o...

Page 12: ...ms com support warranty registration DESIGNED AND MANUFACTURED BY 800 668 3884 604 946 9983 sales analyticsystems com www AnalyticSystems com 8128 River Way Delta BC V4G 1K5 Canada Battery Chargers In...

Reviews: