Analytic Systems IVS1000 Installation & Operation Manual Download Page 4

4

System Description

The IVS1000 inverter series was designed electrically and mechanically to achieve optimal ruggedness 

required for industrial, telecommunications, military and airborne applications.  

Electrical Connections

The input can be grounded either on the positive or negative, or may be left floating.  The output is normally 

grounded, although it can be floating if required for specific applications.

Mount the unit as close to the battery as possible to avoid voltage drop and losses on the wires.  The input 

connections are via a 3-pole terminal block.  GND, POS and NEG are clearly labeled.  Although the unit 

is reverse polarity protected, ensure that input is connected correctly.  (On some models, the internal fuse 

blows when reverse polarity occurs).

If operating the inverter from a power supply (instead of a battery), ensure that this source is capable of sup-

plying a significantly higher current than is actually required.  It is preferable to turn on the inverter first, and 

connect the load after the inverter is already running.  

Input Wire Sizes

Input wire size is crucial for maximum efficiency and safety.  For best results, the shortest length and largest 

gauge wire should be used.  Marine type battery terminals are recommended for attaching connectors to the 

battery.  Keep all connectors clean and free of corrosion.  Refer to the following table for proper sizing.  The 

following values are to be used for guidelines only!  The actual application must be considered for selecting 

wire gauge, insulation, as well as EMI considerations for wire routing and shielding where necessary.  For 

longer wire lengths, larger gauge wire may be needed to minimize line losses.

RECOMMENDED INPUT WIRE SIZES

DISTANCE FROM BATTERY

MODEL

5’

10’

15’

20’

IVS1000-24V to 36V

AWG 4

AWG 2

AWG 0

AWG 00

IVS1000-48V

AWG 8

AWG 8

AWG 6

AWG 6

IVS1000-125V

AWG 10

AWG 10

AWG 10

AWG 10

IVS1000-250V

AWG12

AWG12

AWG12

AWG12

Summary of Contents for IVS1000

Page 1: ...Installation Operation Manual 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 1 800 668 3884 US CANADA www analyticsystems com IVS1000 Pure Sinewave Inverter...

Page 2: ...2 Copyright 2005 2013 Analytic Systems Ware 1993 Ltd...

Page 3: ...er is equipped with electric receptacles capable of accepting an equipment grounding conductor and a grounding plug DANGER Never alter AC cord or plug provided if it will not fit outlet have proper co...

Page 4: ...is capable of sup plying a significantly higher current than is actually required It is preferable to turn on the inverter first and connect the load after the inverter is already running Input Wire...

Page 5: ...no damage occurs whilst reverse polarizing the input On some models the internal input fuse may blow when reverse polarity occurs Input and output filtering All IVS1000 series inverters have a double...

Page 6: ...mum 0 5 Load Regulation Maximum 6 from 10 load to full load Output Noise High frequency ripple is better than 500 mVrms 20 MHz BW GENERAL Temperature Drift 0 05 per C over operating temperature range...

Page 7: ...ional charges and are the responsibility of the Purchaser 5 Analytic Systems reserves the right to void the warranty if a Identification marks or serial numbers are removed or altered in any way b Our...

Page 8: ...y other consequential or resulting damage which may be claimed to have been incurred through the use or sale of the equipment including any possible failure of malfunction of the equip ment or part th...

Reviews: