Specifications
Input
Nominal Voltage
12 Vdc
24, 28, 32 or 36 Vdc
48 or 72 Vdc
Actual Voltage
11 - 15 Vdc
20 - 50 Vdc
40 - 90 Vdc
Input Amps (max)
120
60
30
Input Fuse
None, external fuse or breaker required
Output
Voltage
110 +/- 2 Vac
220 +/- 4 Vac
Output Amps)
10A (cont) / 12A (peak)
5A (cont) / 6A (peak)
Output Frequency
50.00 or 60.00 Hz ± 0.01 Hz (user selectable)
Output Distortion
<2% at 1200 Watts into resistive load
Regulation (Line & Load)
< +/- 2.0%
Duty Cycle Continuous
100% for 24 hours per day
* Specifications subjects to change without notice.
General
Efficiency
> 90% @ maximum output
Temp. Range
-25 to +40 deg. C° @ maximum output
Isolation
Input-Output, Input-Case & Output-Case 1500Vdc Input
Length
13.0 in / 33.0 cm
Width
9.0 in / 22.9 cm
Height
7.8 in / 19.8 cm
Clearance
1 Inch (2.5 cm) all around
Material
Marine Grade Aluminum
Finish
Black Powder Epoxy/Black Anodized
Fastenings
18-8 Stainless
Weight
30 lb / 13.6 kg
Connections
DC In – Marathon ST722B2502UH, 175 Amp, 300V Rating c/w Protective Snap On Cover
AC Out – 1 x NEMA 5-15 receptacle or 1 x 16A 250V CEE 7/7 receptacles with circuit breaker
protection, plus one 30A hardwire connection
AC In – one 30A hardwire connection (with Off-Line UPS Option)
Designed and manufactured by:
ANALYTIC SYSTEMS WARE (1993) LTD.
8128 River Way
Delta, BC V4G 1K5 Canada
p. 604.946.9981 f. 604.946.9983
tf. 800.668.3884 US/Canada
www.analyticsystems.com