Analytic Systems IPSi1200 Series Installation & Operation Manual Download Page 4

4

Specifications

Input

Nominal Voltage

12 Vdc

24, 28, 32 or 36 Vdc 

48 or 72 Vdc

Actual Voltage

11 - 15 Vdc

20 - 50 Vdc

40 - 90 Vdc

Input Amps (max)

120

60

30

Input Fuse

None, external fuse or breaker required

Output

Voltage

110 +/- 2 Vac

220 +/- 4 Vac

Output Amps)

10A (cont) / 12A (peak)

5A (cont) / 6A (peak)

Output Frequency

50.00 or 60.00 Hz ± 0.01 Hz (user selectable)

Output Distortion

<2% at 1200 Watts into resistive load

Regulation (Line & Load) 

< +/- 2.0%

Duty Cycle Continuous

100% for 24 hours per day

* Specifications subjects to change without notice.

General

Efficiency

> 90% @ maximum output

Temp. Range

-25 to +40 deg. C° @ maximum output

Isolation

Input-Output, Input-Case & Output-Case 1500Vdc Input

Length

13.0 in / 33.0 cm

Width

9.0 in / 22.9 cm

Height

7.8 in / 19.8 cm

Clearance

1 Inch (2.5 cm) all around

Material

Marine Grade Aluminum

Finish

Black Powder Epoxy/Black Anodized

Fastenings

18-8 Stainless

Weight

30 lb / 13.6 kg

Connections

DC In – Marathon ST722B2502UH, 175 Amp, 300V Rating c/w Protective Snap On Cover
AC Out – 1 x NEMA 5-15 receptacle or 1 x 16A 250V CEE 7/7 receptacles with circuit breaker 
protection, plus one 30A hardwire connection
AC In – one 30A hardwire connection (with Off-Line UPS Option)

Designed and manufactured by: 

ANALYTIC SYSTEMS WARE (1993) LTD.

8128 River Way 
Delta, BC  V4G 1K5  Canada

p. 604.946.9981  f. 604.946.9983 
tf. 800.668.3884 US/Canada

www.analyticsystems.com

[email protected]    Revised February 2016

Summary of Contents for IPSi1200 Series

Page 1: ...es PURE SINE INVERTER 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers...

Page 2: ...Inverters should be grounded to reduce risk of electric shock This inverter is equipped with a chassis grounding stud and electric receptacles capable of accepting an equipment grounding conductor and...

Page 3: ...xactly the same as commercial AC Crystal controlled for precise frequency 0 01 Hz at either 50 or 60 Hz 1200 Watts output power sufficient for a complete computer workstation and more State of the art...

Page 4: ...t Isolation Input Output Input Case Output Case 1500Vdc Input Length 13 0 in 33 0 cm Width 9 0 in 22 9 cm Height 7 8 in 19 8 cm Clearance 1 Inch 2 5 cm all around Material Marine Grade Aluminum Finish...

Page 5: ...osive gases may accumulate as a slight arc may occur when the power leads are connected and in the unlikely event of a failure sparks may be generated inside the unit INPUT CONNECTION Prepare a circui...

Page 6: ...ircuit breaker protected 15 Amp AC receptacle is provided for connection In addition a 30 amp 250V rated CSA UL approved terminal block is provided for wiring to a distribution panel This terminal blo...

Page 7: ...erature of the inverter is approaching the safe limit The inverter will reduce its maximum power rating to try to maintain the tempera ture within safe limits The LED will glow Red if the inverter is...

Page 8: ...c Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse negl...

Reviews: