5
FCA250
Specifications
Safety Considerations
WARNING:
The FCA250 & FCA500 series frequency converters generate 115VAC (or 230VAC) power – the same voltage
coming out of a standard wall outlet. This voltage can be hazardous and has to be treated with the same cau-
tion as with a regular electrical outlet.
As with any other electrical equipment, the frequency converter must be protected from water and moisture
at all times.
INPUT
Input Voltage:
115/230 VAC +/- 20%, auto-ranging, 47 to 410Hz
Input Protection:
Inrush current limiting & thermal fuse
Input Isolation:
2250 Vdc input to output, input to chassis & output to chassis
RFI Suppression:
Meets requirements of FCC 20780 Class B and EN55022 Class B con-
ducted emissions as a minimum
OUTPUT
Output Voltage / Current:
115 VAC / 60 Hz / 2.1 Amp continuous (250 Watts)
230 VAC / 50 Hz / 1.05 Amp continuous or
any combination including frequency up to 400Hz
Wave Form:
Sinusoidal
Total Harmonic Distortion:
Better than 5% at full load
Line Regulation:
Maximum 0.5%
Load Regulation:
Maximum ± 6% from 10% load to full load
GENERAL
Temperature Drift:
0.05% per º C over operating temperature range
Operating Temp. Range:
0º C to +50º C for full specification (no fan)
Humidity:
5 - 95 % non-condensing
Output Protection:
Current limiting with short-circuit protection. Thermal shutdown with
automatic recovery in case of continuous overload or insufficient airflow
Output Overload Protection:
Hiccup at 300 W
Output Over-voltage Protection: By internal supply voltage limiting at 120% V out, nominal level
Load Crest Factor:
Maximum 2.5 at 90% load
Efficiency:
Minimum 78% at full load
Cooling:
By convection / conduction
Input Connection:
Screw-type terminal block
Output Connection:
Standard AC Receptacle (North American Type)
Package Size / Weight:
5.0 x 5.3 x 15.5 Enclosed case, 9 pounds ( 4.1 kg )