Analytic Systems BCD605 Installation & Operation Manual Download Page 1

Installation & 

Operation Manual

BCD605

DC Battery Charger

8128 River Way, Delta B.C. V4G 1K5 Canada   T. 604.946.9981    F. 604.946.9983     TF. 1.800.668.3884  (US/CANADA)

www.analyticsystems.com

Summary of Contents for BCD605

Page 1: ...Installation Operation Manual BCD605 DC Battery Charger 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 1 800 668 3884 US CANADA www analyticsystems com...

Page 2: ...2 Copyright 2005 2013 Analytic Systems Ware 1993 Ltd...

Page 3: ...DURING NORMAL BATTERY OPERA TION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING EQUIPMENT IN THE VICINITY OF THE BATTERY YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EX...

Page 4: ...TION i Never place battery charger directly above battery gases from battery will corrode and damage converter ii Never allow battery acid to drip on battery charger when reading gravity or filling ba...

Page 5: ...indicators for low input voltage low output voltage and over temperature Safety features include reverse input protection over temperature shutdown current limiting short circuit protection with autom...

Page 6: ...charging current 10 5 13 6 x 40 30 8 amps Specifications Model BCD605 12 12 BCD605 12 24 Input Volts DC 10 5 14 10 5 28 Input Amps max 50 Output Volts DC 13 6 0 5 V 27 2 0 5 V Charging Amps 42 21 Outp...

Page 7: ...n 15 volts Note that the current specifications are for input current To obtain the maximum output current capability at any given input voltage use the following formula Output Current Input Volts Ou...

Page 8: ...t rating the fuse will blow If the fuse blows with no load connected check that the power leads are connected to the battery with the correct polarity if they are then the unit is damaged and must be...

Page 9: ...tely as well as duplicating all the diagnostic indicators and audible alarm REMOTE CONNECTOR This connector is located on the side of the unit Important To prevent the possibility of High Voltage Elec...

Page 10: ...urchas ers name address and telephone number b Call Analytic Systems at 800 668 3884 or 604 946 9981 and request a return material authorization number RMA c Return the defective part or unit along wi...

Page 11: ...tability fitness for the ordinary purposes for which such goods are used or fitness for a particular purpose or any other obligations on the part of the Warrantor or its employees and representatives...