Analytic Systems BCD315 Series Installation & Operation Manual Download Page 10

10

Troubleshooting

If the red 

OVERTEMP LED 

and the audible alarm come on, the unit has overheated, and it 

will shut down until it cools off sufficiently. You may not have allowed sufficient space around 

the unit for cooling, or there may be too many devices connected to the output of the unit. 

Either reduce the number of devices connected to the unit, or reposition the unit for better 

cooling. If necessary, direct a stream of moving air over the unit. 

If the yellow 

LOW INPUT LED

 and the audible alarm comes on, the input voltage has 

dropped to below a usable level. 

If the 

LOW OUTPUT LED

 and the audible alarm come on, and the green 

OUTPUT ON LED

 

is completely off, the output of the unit has been shorted out, or there has been an internal 

failure. Turn the unit off, disconnect all the loads connected to it, and turn it back on again. If 

it comes on normally, turn it off again, reconnect one load, and turn it back on. Continue recon-

necting loads until the short circuit condition returns. Turn the unit off, disconnect the faulty 

load, and reconnect it only after the fault is found and rectified. If the condition still exists 

even after all the loads have been disconnected, the unit is defective, and must be returned to 

the factory or an authorized service center for repair. 

If the unit will not turn on at all, check the input fuse. To do this, first turn off the unit and 

disconnect the power cord. Next, remove the negative battery lead and cover the end with non 

conductive material such as tape. Repeat this with the other battery lead. This will prevent an 

accidental discharge from the battery. Remove the fuse and check it with an ohmmeter. If it is 

blown, replace it with a new one. If that fuse blows as well or the unit still will not turn on, it 

is defective, and must be returned to the factory or an authorized service center for repair. 

If the batteries are hooked up backwards the output fuses will blow. To change them follow 

the same procedure as for the input fuse. 

If both the input and output fuses are good and the unit still does not function it must be 

returned to the factory for servicing.

Summary of Contents for BCD315 Series

Page 1: ...C Battery Charger 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Page 2: ...Copyright 2005 2014 Analytic Systems Ware 1993 Ltd ...

Page 3: ... NORMAL BATTERY OPERATION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING EQUIPMENT IN THE VICINITY OF THE BATTERY YOU READ THIS MANUAL AND FOL LOW THE INSTRUCTIONS EXACTLY b To reduce risk of battery explosion follow these instructions and those published by battery manufacturer and manufacturer of any equipment you intend to use in vicinity of battery Review cautionary...

Page 4: ...a Never place battery charger directly above battery gases from battery will corrode and damage converter b Never allow battery acid to drip on battery charger when reading gravity or filling battery 9 O P CONNECTION PRECAUTIONS a Connect and disconnect DC output connections only after setting battery charger switch to off position Analytic Systems does not recommend the use of the BCD315 Series B...

Page 5: ...protection and output overvoltage crowbar Optional features include a high quality digital volt ammeter factory install only and remote panel monitoring with On Off control Specifications Input Voltages Nominal ip 24 36 48 72 Actual Vdc 20 35 30 45 40 60 65 90 Input Amps max 18 7 12 5 9 4 5 7 Input Fuse slow blow MDA 25 MDA 20 MDA 15 MDA 10 Output Voltages Nominal op 12 36 24 48 Float Vdc 13 6 0 0...

Page 6: ...utput and case Therefore the unit may be mounted on any surface without fear of electrolysis or ground fault General Efficiency 80 maximum output Stages 2 or 3 Temp Range 25 to 40o C maximum output Isolation Input Output Input Case 1500 Vdc 500 Vdc 24 V In Output Case 500 VDC 1500Vdc 48 V Out Length 9 6 in 24 4 cm Width 8 2 in 20 8 cm Height 3 5 in 6 4 cm Clearance 1 Inch 2 5 cm all around Materia...

Page 7: ...arging profile 2 or 3 stage charging to use To help you decide please see the following section entitled 2 or 3 Stage Charging to determine the charging profile Once you have decided on the charging profile you must set the switch to the correct posi tion The switch is located to the right of the output terminal on the front panel Set the switch to the correct position as shown on the label To tur...

Page 8: ...stic discharge of unused batteries A load can be put on the battery or batteries without altering its ability to keep the battery at optimal charge 100 75 50 25 0 Bulk Constant Current Absorption Constant Volts Maintenance Constant Volts Time Three Stage Charger Volts Amps this voltage at the output terminals of the unit with a good digital voltmeter As shipped from the factory the unit is preset ...

Page 9: ...rter factory installed only The meter shows simultaneous voltage and current on either of the two output terminals A toggle switch permits selection between the output terminals The meter features bright red LED readouts to permit easy monitoring from many feet or meters away Special Services Options Conformal Coating INCLUDED ON ALL UNITS UNLESS REQUESTED NOT TO as of April 1 2014 Option c Rugged...

Page 10: ...he short circuit condition returns Turn the unit off disconnect the faulty load and reconnect it only after the fault is found and rectified If the condition still exists even after all the loads have been disconnected the unit is defective and must be returned to the factory or an authorized service center for repair If the unit will not turn on at all check the input fuse To do this first turn o...

Page 11: ...ing will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse neglect improper installation environmental conditions non autho rized repair alteration or accident 7 No refund of t...

Page 12: ... Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters ...

Reviews: