Mounting
Mount the unit in a DRY and WELL VENTI-
LATED location with at least 4 inches of
clearance all around it. The ideal mount-
ing configuration is to mount the unit flat
on a horizontal surface. #10 screws are
recommended for attaching the unit to the
surface.
There is 1500 volts of isolation between
the input and output, and the input and
case. There is 500 volts (1500V for 48V
output units) of isolation between the output and case. Therefore, the unit may be mounted on
any surface without fear of electrolysis or ground fault.
Installation
All connections should be made inside an appropriate junction box with appropriately rated
circuit breakers used in the circuit panel to feed power to the BCA 610. See
Specifications
for
the maximum input current and recommended fuses.
AC Input Connection
The unit is equipped with a 5-foot long power cable terminating in either a North American
outlet compatible NEMA 5-15 plug or European outlet compatible CEE-7/7 plug to serve as an AC
Input Connection.
If you must extend the power cable be sure to use a 3 conductor grounded type extension
cable. For hard wiring to a source of power, cut off the plug, and strip the wires as necessary.
The wire colors are:
110 VAC
Brown - AC Hot
Blue - AC Neutral
Green - Ground
220 VAC
Brown - AC Hot / Phase 1
Blue - AC Neutral / Phase 2
Green/Yellow - Ground
DC Output Connection
This unit is equipped with a Molex 4-pin BEAU Terminal Strip to serve as a DC Output Connec-
tion. This connector has two positive output terminals and two negative output terminals. See
the unit’s label for the wiring of this connection.