Installation Guide

RE-DM4 

Radia Eclipse 4-Channel Dimmer Module (120 or 240 volts)

Overview

The RE-DM4 RADIA Eclipse 4-Channel Integrated Dimmer Module (120 VAC: 

FG706-01

; 240 VAC: 

FG706-02

) controls up to six circuits with four 1200-watt onboard 

dimmers and two satellite connectors for RDM series dimmer or switch modules 
(FIG. 1). The RE-DM4 is designed for use with the RDA series of enclosures in an 
AMX Lighting™ modular digital dimming system. The RE-DM4 is controlled by AXLink 
or by dry (contact) closures.

Specifications

Suggested Loads 

Caution: Pre-Installation Notes

WARNING

: This unit should be installed only by qualified electrical personnel, and in 

compliance with all national electrical codes, local codes and ordinances.To prevent 
possible personal injury or death, disconnect power to the enclosure 

at the breaker 

box 

before attempting to work with any AMX Lighting modules.

All Class 1 and 2 wiring must be connected to their dedicated terminals.

Class 1 wiring should be connected through the top of the enclosure, and Class 

2 wiring through the bottom.

Load conductors must be same size as line conductors, regardless of 

connected load.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times, and maintain 12” (30.48 cm) 

clearance around the top and bottom.

Test loads for shorts before connecting.

Class 2 wiring must be rated 300V or higher.

For indoor use only.

AC lighting loads only.

This module may require extra power from the AXLink connection or an external 

power supply connected to the control card.

For more information, refer to the RE-DM4 instruction manual available at 

www.amx.com

.

Radia Lighting System Configuration Pages

The AMX Radia Web pages provide a simple interface for users of the Radia Duet 
module. The web pages reside on the AMX master when running the Radia Duet 
module and may be accessed through Internet Explorer or Mozilla Firefox. The RE-
DM4 may also be configured using NetLinx code or a terminal. For more information, 
refer to the RE-DM4 instruction manual available at 

www.amx.com

.

High-Voltage Connections

Each AMX Lighting module has its high-voltage connectors marked on its circuit 
board. Line, load, and neutrals are also clearly marked.

Line-in Connections

Using two feeds for Line 1 and Line 2 provides two 2400 W inputs.

With a jumper, Line 1 and Line 2 provides a single 2400 W input (FIG. 3).

  

FIG. 1  

RE-DM4 4-Channel Integrated Dimmer Module

RE-DM4 Specifications

Dimensions (HW)

5.75" x 10.0" (146.05 mm x 254.00 mm)

Weight

4.5 lbs (2.04 kg)

Line Input

• 120, 240 VAC, single phase, 2W+G, 50/60 Hz, 2400 W, 

one feed

• 120, 120/240, 240 VAC, single phase, 3W+G, 50/60 

Hz, 4800 W, dual feed

Output

• 1200 W max. per channel @120, 240 VAC
• 2400 W max. total, all four channels on with single 

2400 W feed

• 4800 W max. total, all four channels on with dual 

2400 W feeds

• Line input #1 goes to dimmer 1 and 3; line input #2 

goes to dimmer 2 and 4

• All electrical ratings are for continuous duty

Wire rating

Use only copper wires rated at 75°C (167°F) min.

Torque terminals

To 20 in-lbs (2.3 N/M)

Maximum wire size

10 AWG (4 mm²)

Wire stripping length

0.5" (13 mm)

AXLink Port

4-pin 3.5mm black captive wire connector. AXLink 
communication signaling with 12VDC power in.

Aux Power

2-pin 3.5mm green captive wire connector. This is a 
12VDC power input that supplies additional power to the 
Radia PCB and connected Radia modules.

Dry Contacts

• Emergency fire alarm relay connection - Closed relay 

activates preset 126. Other control is locked out until 

relay opens. Supports daisy chaining of up to 20 

dimmers for this connection, with a maximum current 

requirement of 200mA when daisy-chained.

• Failsafe connection - Works with a toggle switch - 

opening the switch triggers preset 128, closing the 

switch triggers preset 127. Supports daisy chaining of 

up to 20 dimmers for this connection with a maximum 

current requirement of 200mA when daisy-chained.

BTU/hr

300 single feed (2400 W); 600 dual feed (4800 W)

Mounting

Jumper

Load out

Neutral

Chokes

High

Voltage

Mounting

 

Ex12V
Aux Power

AXLink

 

DIP Switch

Dry Closures

AXlink Connector

 

 

 

Power Devices

points

Connections

Address

points

 

4-Pin Connectors
to RDM series
Modules

Line In

Class 1 wiring

Class 2 wiring

RE-DM4 Specifications (Cont.)

Idle current draw

75 mA @ 120 VAC, 50 mA @ 240 VAC, 100 mA @ 13.5 
VDC

RDM control current

2 at 200 mA @ 12 VDC with no additional power supply

Certifications

• FCC
• CE
• UL North America
• IEC-60950 Safety

Operating Temp Range

• 0° to 40°C (32° to 104°F)

Included Accessories

• 2 4-pin 3.5mm captive wire connector (

41-5047

)

• 4 #8-32x1/2” F-point mounting screws

Required Enclosures

• RDA-ENC2 (

FG606-10

)

• RDA-ENC4 (

FG606-11

)

• RDA-ENC6/6B (

FG606-12/13/15

)

• RDA-ENC12B (

FG606-14/16

)

Dimmed

Switched

Incandescent

Motors

Neon, cold-cathode

Fans

FIG. 2  

High-voltage connections

FIG. 3  

Line-in Connections

Neutral

Line in

Load

Load

 

Dual 2400 W Inputs without jumper

Single 2400 W Input with jumper