Pre-Installation
9
AXB-PT10/15/30 PosiTrack Camera Controllers
The RS-232 factory default communications settings are:
9600 baud, No Parity, 8 bits, and 1 stop
bit
. The following table lists the RS-232 Port DB-9 (male) pinouts.
The following table lists the RS-232 DIP switch settings.
Setting the AXlink Device DIP switch (S5)
The eight-position Device DIP switch (S5), shown in FIG. 5, must match the number assigned in
the Axcess software program. The Device DIP switch example is set to 90 (2 + 8 + 16 + 64 = 90),
the factory default setting.
RS-232 Port DB-9 (male) Pinouts
Pin
Signal
Function
1
N/A
N/A
2
RXD
RXD
3
TXD
TXD
4
N/A
N/A
5
GND
GND
6
N/A
N/A
7
RTS
RTS
8
CTS
CTS
9
N/A
N/A
RS-232 DIP Switch (S2) Settings
Position
1
2
3
4
5
6
7
8
Function
Stop Bits
Data Bits
Parity
Baud Rates
Off
Off
Off
Off
Off
Off
Off
Off
2 bits
7 bits
Unused
300
On
On
On
Off
Off
On
Off
Off
1 bit
8 bits
Unused
600
Off
On
Off
Off
On
Off
Unused
1,200
On
On
Off
On
On
Off
Unused
2,400
Off
Off
On
Off
Off
On
Unused
4,800
On
Off
On
On
Off
On
Even
9,600
Off
On
On
Off
On
On
Odd
19,200
On
On
On
On
On
On
None
38,400
FIG. 5
AXlink device DIP switch (S5) (default value of 90)
AXlink
DIP switch
(S5)
1 2 3 4 5 6 7 8