background image

Pre-Installation

1.  Visually  inspect  the  Surge-Trol  for  any  damage.  If 

damage exists return product for replacement.

2.  Remove air cap.
3.  For  applications  with  pump  start-up  creating  water 

hammer adjust the factory pre-charge setting to 15% 
below static pressure.

4.  For  applications  with  surge  issues  created  by  pump 

shut  down  adjust  the  factory  pre-charge  setting  to 
50% below static pressure.

5.  For  applications  with  quick  closing  valves,  please 

consult manufacturer for tank location and pre-charge 
settings. (401) 535-1216.

6.  Replace and tighten cap on air valve.

If adjusting the pre-charge pressure 
higher than 55 PSIG the  unit must be 

tied to the system immediately. Failure to do so could 
damage the bladder and void all warranties.

Installation

1.  The  Surge-Trol  should  be  installed  as  close  to  the 

offending  fixture  as  possible  in  applications  where 
there are issues with a quick closing valve.

2.  The  Surge-Trol  should  be  installed  as  close  to  the 

pump as possible in surge applications. 

3.  Once  the  Surge-Trol  is  installed  and  the  pre-charge 

adjusted properly, check for any leakage. Make repairs 
if necessary

Maintenance

1.  A  qualified  professional  should  check  the  complete 

system,  including  the  Surge-Trol,  yearly  and  more 
frequently as the system ages.

Operation

1.  The Surge-Trol is designed to provide surge protection 

as well as provide a cushion to prevent water hammer 
depending on its application.

2.  Water  temperature  is  not  to  exceed  240°F.  or  fall  

below 35°F.

3.  The factory pre-charge setting is 25 PSIG and should 

only be adjusted   at the time of the installation.

4.  System velocity shall not exceed 22 fps.

TYPICAL INSTALLATION

PUMP

CHECK VALVE

TO SYSTEM

SURGE-TROL

Diagram 1

EXPLOSION  OR  RUPTURE  HAZARD

  A 

relief  valve  must  be  installed  to  prevent 

pressure  in  excess  of  local  code  requirement  or  maximum 

working pressure designated in the Product Manual, whichever 

is  less.    Do  not  expose  Product  to  freezing  temperatures  or 

temperatures  in  excess  of  240°  F.    Do  not  exceed  maximum 

allowable  working  pressure  275  psig.  Do  not  adjust  the  pre-

charge  or  re-pressure  this  Product  except  for  any  adjustments 

required at the time of initial installation, especially if Product is 

corroded, damaged or with diminished integrity.  Adjustments to 

pre-charge must be done at ambient temperature only.  Failure 

to  properly  size  the  Product  or  follow  these  instructions  may 

result  in  excessive  strain  on  the  system  leading  to  Product 

failure, serious or fatal personal injury, leakage and/or property 

damage. 

This  Product,  like  most  Products  under 

pressure, may over time corrode. weaken and 

burst  or  explode,  causing  serious  or  fatal  injury,  leaking  or 

flooding and/or property damage.  To minimize risk, a licensed 

professional must install and periodically inspect and service the 

Product.    A  drip  pan  connected  to  an  adequate  drain  must  be 

installed if leaking or flooding could cause property damage.  Do 

not locate in an area where leakage of the tank or connections 

could  cause  property  damage  to  the  area  adjacent  to  the 

appliance or to lower floors of the structure.

Chlorine  &  Aggressive  Water.

  The  water 

quality  can  significantly  influence  the  life  of 

this product. You should test for corrosive elements, acidity, total 

solids  and  other  relevant  contaminants,  including  chlorine  and 

treat your water appropriately to insure satisfactory performance 

and prevent premature failure.

Note:

  Inspect  for  shipping  damage  and  notify  freight  carrier 

or  store  where  purchased  immediately  if  damage  present.  If 

the  product  appears  to  be  malfunctioning  or  shows  signs  of 

corrosion,  call  a  qualified  professional.  Current  copies  of  the 

product manual can be viewed at www.amtrol.com. Use proper 

safety equipment when installing.

GENERAL  SAFETY  INFORMATION  - 

ADDITIONAL  SPECIFIC  SAFETY  ALERTS 

APPEAR IN THE FOLLOWING INSTRUCTIONS.

CALIFORNIA PROPOSITION 65 WARNING:

 

This  product  contains  a  chemical  known  by 

the State of California to cause cancer and to cause birth defects 

or  other  reproductive  harm.  (California  Installer/Contractor  - 

California law requires that this notice be given to consumer/end 

user  of  this  product.)  For  more  information:    www.amtrol.com/

prop65/htm.

DO  NOT  USE  OXYGEN  -  EXPLOSIVE!

 

Protect against freezing temperatures. Never 

pre-charge below 50% of maximum system pressure.

INSTALLATION AND OPERATION INSTRUCTIONS

IMPORTANT GENERAL SAFETY INFORMATION

 

ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS

Summary of Contents for SURGE-TROL SPT-11

Page 1: ...L VOID THE PRODUCT WARRANTY THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED PROFESSIONAL FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS IN THE ABSENCE OF SUCH CODES FOLLOW THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE West Warwick Rhode Island 02893 INSTALLATION OPERATION INSTRUCTIONS SURGE TROL Surge Arrestor SPT 7 thru SPT 70 MARK OF THE O...

Page 2: ...ments required at the time of initial installation especially if Product is corroded damaged or with diminished integrity Adjustments to pre charge must be done at ambient temperature only Failure to properly size the Product or follow these instructions may result in excessive strain on the system leading to Product failure serious or fatal personal injury leakage and or property damage This Prod...

Page 3: ...it Gal mm ins mm ins ins ins ins ins kg lbs SPT 7 200 53 1245 487 8 610 24 4 19 16 83 16 19 166 367 SPT 11 300 80 1600 627 8 610 24 4 19 16 83 16 19 208 459 SPT 14 400 106 1956 767 8 610 24 4 19 16 83 16 19 282 618 SPT 18 500 132 2311 907 8 610 24 4 19 16 83 16 19 333 731 SPT 21 600 158 1893 7411 16 762 30 4 13 8 71 4 24 433 950 SPT 28 800 211 2365 931 8 762 30 4 13 8 71 4 24 513 1125 SPT 35 1000 ...

Page 4: ...IES INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE SPECIFICALLY DISCLAIMED Some states do not allow limitations on how long an implied Warranty lasts so the above limitation may not apply to you Limitations of Remedies THE REMEDIES CONTAINED IN THIS WARRANTY ARE THE PURCHASER S OR FIRST USER S EXCLUSIVE REMEDIES IN NO CIRCUMSTANCES WILL AMTROL BE LIABL...

Reviews: