RADIANT EXTROL

®

 is designed for closed, low temperature systems 

with a maximum operating temperature of 200° F. The product can be 

used in glycol applications and features a plastic liner that is compatible 

with barrier and non-barrier tubing.

Pre-Installation

1. Visually inspect for any damage. Ensure expansion tank is sized 

properly for the application (Figure 1).

2. With tank empty of water, remove plastic cap from air stem (Figure 2).
3. Adjust air precharge to desired system fill pressure. Unit is shipped at 

12 PSIG.

4. Replace cap and tighten snugly, ensuring the cap is flush against the 

tank surface.

FAILURE TO PROPERLY SEAL VALVE CAP 

WILL RESULT IN LOSS OF PRECHARGE 

CAUSING PRODUCT TO FAIL.

Installation

1. Drain the boiler system or isolate the area where the Radiant Extrol will 

be installed.

2. Install the Radiant Extrol on the supply side of the boiler, on the 

suction-side of the heating circulator(s) (Figure 3).

 

Mount tank vertically only.  Ensure the piping 

can support the entire weight of the tank when 

full of water.

3. Once the Radiant Extrol is installed, re-pressurize the system and 

check for leaks. Repair as necessary.

4. Restart the boiler system and check for relief valve discharge. If the 

relief valve drips, the tank may be improperly charged or undersized.

5. The Radiant Extrol is now operational and will absorb expanded water 

during boiler operation.

Operation

1. The Radiant Extrol is installed on the supply-side of the boiler system. 

Its sealed-in air precharge prevents water from entering the tank until 

the system pressure begins to rise.

2.  As the water temperature rises, water enters the Radiant Extrol.
3. As the system cools, the diaphragm is forced downward. Water is 

expelled from the Radiant Extrol, back into  the heating system.

NOTE:

Although the Radiant Extrol does not have to be installed at the base of 

an air purger, this installation is recommended to reduce air in the system 

and provide a compact installation. Some method of air elimination is 

required to ensure an oxygen-free system.

Maintenance

A licensed professional should check the complete system, including 

the expansion tank, yearly and more frequently as the system ages. 

Checking the precharge allows a small quantity of air to escape and can 

result in an insufficient air charge. Always check the precharge while the 

tank is isolated and empty of water, and be sure to maintain the proper 

precharge whenever the tank is inspected. Monitor the tip of the InSight

 

Service Indicator Cap for discoloration (Figure 4) in addition to regular 

product inspection. Contact the installer or a plumbing professional if 

indicator cap is discolored; tank replacement required. Do not rely on cap 

as sole indication of tank condition.

Warranty

RX Models: Seven (7) Year Limited Warranty 

Visit www.amtrol.com for complete warranty details.

PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY

IMPORTANT GENERAL SAFETY INFORMATION - 

ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.

Figure 2.

Remove cap and 

charge to system 

fill pressure.

Replace InSight™

Service Indicator Cap 

and tighten until flush 

with tank.

Precharge Adjustment: In-Line Models Shown

Clear / White

Normal

Operation

Discolored

Replace

Tank

Figure 4.

InSight

 Service Indicator Cap (Inline models only)

Figure 1.

Radiant Extrol Sizing

Feet of 

Tubing

Nominal Pex Tubing Size

3/8"

1/2"

5/8"

3/4"

1"

1,000

RX-15

RX-15

RX-15

RX-15

RX-15

5,000

RX-15

RX-15

RX-15

RX-30

RX-30

7,500

RX-15

RX-15

RX-30

RX-30

RX-60

10,000

RX-15

RX-30

RX-30

RX-60

RX-60

14,000

RX-15

RX-30

RX-60

RX-60

18,000

RX-30

RX-60

RX-60

RX-60

22,000

RX-30

RX-60

RX-60

30,000

RX-30

RX-60

Sizing based on: Fill Pressure 12 psig; Relief Pressure 30 psig; Average Temperature 120° F; System 

filled with water. For glycol applications, consult AMTROL Technical Support.

Contact Amtrol

Figure 3.

Heating Zone(s)

Air Eliminator

Boiler

Return

System Fill

Relief

Valve

Radiant

EXTROL

InSight Cap