Pre-Installation

1. Visually inspect for any damage. Ensure expansion tank is sized 

properly for the application (Figure 1).

2.  With tank empty of water, remove plastic cap from air stem (Figure 2).
3.  Check precharge pressure and adjust if necessary, charging with air 

to match boiler fill valve setting.

4.  Replace cap and tighten snugly, ensuring the cap is flush against the 

tank surface.

Installation

1. Drain the boiler system or isolate the area where the EXTROL will  

be installed.

2.  Install the EXTROL on the supply side of the boiler, on the suction-side 

of the heating circulator(s) (Figure 3).

3.  Pressurize the system and check for leaks. Repair as necessary.
4.  Restart the boiler system and check for relief valve discharge. If the 

relief valve drips, the tank may be improperly charged or undersized.

FAILURE TO PROPERLY SEAL CAP WILL 

RESULT IN LOSS OF PRECHARGE CAUSING 

PRODUCT TO FAIL.

Mount tank vertically in downward position only. 

Ensure the piping can support the entire weight of 

the tank when full of water.

 

Models SX-30V through SX-160V are floor 

standing and may not be hung from the piping.

 

Do not install the EXTROL on a dead-end pipe or 

wherever air can collect. This can cause corrosion 

and possible leakage.

Figure 1.

System

Supply

Flow-Check

Valve

Circulator

Air Purger

Air Vent

EXTROL

Fill Valve Assembly

Boiler

System

Return

Inspection

Cap

Relief

Valve

Drain Valve

System

Supply

Flow-Check

Valve

Circulator

Fill Valve Assembly

Boiler

System

Return

Relief

Valve

EXTROL

Air

Separator

Air Vent

Drain Valve

In-Line Models: EX-15 through EX-90

Stand Models: SX-30V through SX-160V

PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY FOR

IMPORTANT GENERAL SAFETY INFORMATION AND ADDITIONAL SPECIFIC SAFETY ALERTS.

VISIT www.amtrol.com TO VIEW HELPFUL VIDEOS

.

Boiler

Net Output

in 1000’S

of BTU/Hr.

Type of Radiation

Finned Tube

Baseboard or 

Radiant Panel

Convectors

or Unit

Heaters

Radiators

Cast Iron

Baseboard

Cast Iron

25

EX-15

EX-15

EX-15

EX-15

50

EX-15

EX-15

EX-30

EX-30

75

EX-30

EX-30

EX-30

EX-60

100

EX-30

EX-30

EX-60

EX-60

125

EX-30

EX-60

EX-60

EX-90

150

EX-30

EX-60

EX-90

EX-90

175

EX-60

EX-60

EX-90

EX-90

200

EX-60

EX-60

EX-90

EX-90

250

EX-60

EX-90

EX-90

EX-90

300

EX-90

SX-30V

SX-30V

SX-40V

350

SX-30V

SX-30V

SX-40V

SX-60V

400

SX-30V

SX-40V

SX-40V

SX-60V

450 

SX-40V

SX-40V

SX-60V

SX-90V

500

SX-40V

SX-40V

SX-60V

SX-90V

550

SX-40V

SX-60V

SX-60V

SX-90V

600

SX-40V

SX-60V

SX-90V

SX-90V

650

SX-60V

SX-60V

SX-90V

SX-90V

700

SX-60V

SX-60V

SX-90V

SX-90V

750

SX-60V

SX-60V

SX-90V

SX-110V

800

SX-60V

SX-90V

SX-90V

SX-110V

850

SX-60V

SX-90V

SX-90V

SX-110V

900

SX-60V

SX-90V

SX-110V

SX-110V

950

SX-90V

SX-90V

SX-110V

SX-110V

1,000 

SX-90V

SX-90V

SX-110V

SX-110V

1,100

SX-90V

SX-90V

SX-110V

SX-130V

1,200

SX-90V

SX-90V

SX-110V

SX-130V

1,300

SX-90V

SX-110V

SX-130V

SX-160V

1,400

SX-110V

SX-130V

SX-160V

SX-160V

1,500

SX-110V

SX-130V

SX-160V

(2)SX-110V

Sizi

ng based on: 12 psig Fill; 30 psig Relief Valve; 200°F Average Temperature.

Figure 2.

Figure 3.

Maintenance

A professional plumber should check the complete system, including 

the expansion tank, yearly and more frequently as the system ages. 

Checking the precharge allows a small quantity of air to escape and can 

result in an insufficient air charge. Always check the precharge while 

the tank is isolated and empty of water, and be sure to maintain the 

proper precharge whenever the tank is inspected. Monitor the tip of the 

inspection cap for discoloration (Figure 4) in addition to regular product 

inspection. Contact the installer or a plumbing professional if inspection 

cap is discolored; tank replacement required. Do not rely on cap as sole 

indication of tank condition.

Warranty

EX Models: Five (5) Year Limited Warranty 

SX Models: One (1) Year Limited Warranty

Visit www.amtrol.com for complete warranty details.

Figure 4.

Clear / White

Normal

Operation

Discolored

Replace

Tank

Remove cap and 

charge to system 

fill pressure.

Replace cap and 

tighten until flush 

with tank.

Precharge Adjustment: In-Line Models Shown