Innovative Circuit Technology Ltd.
Set the max charge current to be supplied to the battery by setting SW
3, and SW 4 on the back panel according to the following chart: (note
that actual current flow to the battery may be less than the setting, and
is determined by the battery state of charge and temperature)
Max
Charge
(% of
Output)
Max
Charge
(100A
Models)
Max
Charge
(50A
Models)
Max
Charge
(25A
Models)
Max
Charge
(12A
Models)
BAT
SW3
Setting
BAT
SW4
Setting
100%
(Default)
100A
50A
25A
12.5A
1
1
75%
75A
38A
19A
9.4A
1
0
50%
50A
25A
12.5A
6.3A
0
1
25%
25A
12.5A
6.3A
3.1A
0
0
Maximum Charge Current – Switch Settings (1 = UP, 0 = Down)
Set the low voltage disconnect (LVD) disconnect and reconnect voltage
points, by setting SW 1, and SW 2 on the back panel according to the
following chart:
LVD Setting
12V
24V
48V
BAT SW1
Setting
BAT SW2
Setting
Disconnect V
(Default)
11.5
23
46
x
1
Disconnect V (low setting)
10.5
21
42
x
0
Reconnect V
(Default)
12.5
25
50
1
x
Reconnect V (low setting)
12
24
48
0
x
LVD Disconnect/Reconnect V – Switch Settings (1 = UP, 0 = Down, x = either)
INSTALLATION
Mount the unit in a standard 19 inch equipment rack, (ensuring side air vents are
not blocked) using rack mounting screws (not supplied), then make the following
connections using wire and connectors appropriately rated for the maximum
input and output current rating of the unit:
Remove the plastic bus bar cover by removing the two screws holding it in
place
Connect the supply POS output bus bar to the load positive input (using a
supplied bus bar bolt/washer/nut set for the bus bar connection) (NOTE: do
not connect the load directly to the battery, as this will defeat the battery
charging and low voltage disconnect functions)