Copyright 2021 Ampt LLC.
All rights reserved.
27
String Optimizer V600-32 Platform
Installation Manual: 57070021-1 A
8.
Connect the set of PV strings for Input 2 to the INPUT 2 connectors of the String
Optimizer. Ensure that the locking mechanisms on the connectors are fully engaged.
Figure 16: Connecting Input 2
9.
Follow your safety procedures and protocols to measure the output voltage of the
String Optimizer. It should be equal to the maximum value of the Output Voltage
Range on the product label (+/- 1.5%). If it is not, replace the unit.
Figure 17: Verify proper installation
10.
If you are connecting the output now, then proceed to the next section. Otherwise,
use MC4-Evo 2 Sealing Caps to protect the connectors until the output is connected.
Optimizer
output
from PV
from PV
Output Voltage Range
on the product label
MC4-Evo 2 male connectors
have a non-conductive tip