11

(for Frequency only)

2. Measuring Frequency by using ac Voltage function

Step 1: Turn the rotary switch to 

  position.

Step 2: Connect test leads to the circuit. Connect the common (COM) test 
lead to the circuit before connecting the live lead (connecting diagram 
refer to “Measuring AC Voltage”).
Primary display shows ac Voltage measurement reading. 
Secondary display shows Frequency measurement reading.

Summary of Contents for AM-540-EUR

Page 1: ...AM 560 Advanced HVAC Multimeter AM 570 Industrial Multimeter AM 540 EUR AM 550 EUR Digital Multimeter Users Manual ...

Page 2: ......

Page 3: ...AM 560 Advanced HVAC Multimeter AM 570 Industrial Multimeter AM 540 EUR AM 550 EUR Digital Multimeter Users Manual 4 2012 4252998 A 2012 Amprobe Test Tools All rights reserved Printed in China English ...

Page 4: ...lem or the service requested and include the test leads with the meter Non warranty repair or replacement charges should be remitted in the form of a check a money order credit card with expiration date or a purchase order made payable to Amprobe In Warranty Repairs and Replacement All Countries Please read the warranty statement and check your battery before requesting repair During the warranty ...

Page 5: ...n functions 4 AM 570 AM 550 EUR Low impedance button AM 560 AM 540 EUR Backlight button 5 Rotary switch 6 SELECT button 7 Input terminal for voltage diode capacitance resistance continuity and temperature measurement 8 COM return terminal for all measurements 9 Input terminal for AC DC mA uA measurement 10 Input terminal for AC DC A measurement to10A 6 7 1 2 3 4 4 6 5 7 8 9 10 ...

Page 6: ... Measurement units for Current 6 9 5 2 4 3 7 10 19 20 11 21 26 16 17 13 12 14 15 18 28 27 25 24 8 1 22 23 16 Measurement units for Capacitance 17 Duty cycle 18 Auto power off 19 Maximum minimum reading memory 20 Positive negative peak reading memory 21 Measurement unit for temperature 22 Low pass filter 23 400KΩ low impedance test AM 570 AM 550 EUR only 24 Temperature measurement T1 or T2 25 Tempe...

Page 7: ...MEASUREMENT 5 Rotary Switch Positions 6 Function Buttons 6 Measuring AC and DC Voltage 9 Low Pass Filter 9 Measuring Frequency Duty Cycle 11 Measuring AC and DC Current 13 Measuring Resistance 14 Measuring Continuity 15 Measuring Capacitance 16 Measuring Diode 17 Measuring Temperature C F 18 Non Contact Voltage Detection 19 SPECIFICATIONS 20 MAINTENANCE 24 BATTERY AND FUSE REPLACEMENT 25 ...

Page 8: ...cler SAFETY INFORMATION The meters comply with IEC EN 61010 1 3rd Edition Pollution Degree 2 Measurement Category IV 600V and Measurement Category III 1000V IEC EN 61010 2 31 for test leads EMC IEC EN 61326 1 Measurement Category IV CAT IV is for measurements performed at the source of the low voltage installation Examples are electricity meters and measurements on primary overcurrent protection d...

Page 9: ...suring on a known voltage source Do not apply more than the rated voltage as marked on the Meter between the test probe or between any test probe and earth ground Use the Meter with caution for voltages above 30 V ac rms 42 V ac peak or 60 Vdc These voltages pose electrical shock hazards Disconnect circuit power and discharge all high voltage capacitors before testing resistance Do not use the Met...

Page 10: ...e on systems affected by harmonics built in flashlight allows you to identify wires while working in dark conditions and non contact voltage detection allows for quick go no go checks without the need for an additional tool The AM 570 AM 550 EUR also features dual input temperature measurement a low impedance function to detect stray voltage and a low pass filter to accurately take measurements on...

Page 11: ... from the circuit 4 Symbol OL is displayed on LCD when the measurement is out of range Rotary Switch Positions Switch Position Measurement Function AC voltage measurement Low pass filter 1kHz Use SELECT button to select alternate function NCV DC voltage measurement Non contact Voltage detection Use SELECT button to select alternate function DC millivolt measurement Frequency Duty cycle Use SELECT ...

Page 12: ...ng T1 or T2 or T1 T2 function switching for temperature measurement REL Relative mode Press 2 seconds to turn ON or turn OFF flash light MAX MIN PEAK 1ms Press to enter maximum minimum reading memory mode Press again for maximum reading press again for minimum reading Press 2 seconds to exit maximum minimum reading mode Press 2 seconds to enter Peak MAX Peak MIN mode Press again for Peak MAX readi...

Page 13: ...rn OFF flash light MAX MIN PEAK 1ms Press to enter Maximum minimum reading memory mode Press again for naximum reading press again for minimum reading Press 2 seconds to exit maximum minimum reading mode Press 2 seconds to enter Peak MAX Peak MIN mode Press again for Peak MAX reading press again for Peak MIN reading Press 2 seconds to exit Peak MAX Peak MIN reading mode HOLD Display freezes presen...

Page 14: ...ored value when set to related mode Display value under REL Mode Measured Value Reference Value Note Entering relative mode is not allowed when the Meter displays OL Incorrect Input Terminal Connection Warning To alert you about the incorrect connection of input terminals the Meter will display Warning and buzzer will sound when test leads are falsely inserted to terminals which are not for measur...

Page 15: ...nction to verify the presence of hazardous voltage in the circuit Always use Voltage function to verify hazardous voltages Do not apply voltage higher than 1000V Measuring AC voltage with Low Pass Filter Turn rotary switch to position and press SELECT button for Low Pass Filter mode symbol is displayed on screen Making measurement under ac voltage mode by a low pass filter can block voltage above ...

Page 16: ...ter option Measuring Frequency Duty Cycle X To avoid personal injury or damage to the Meter do not apply voltage higher than 1000V 1 Frequency Duty Cycle function Step 1 Turn the rotary switch to Hz position Use SELECT button for Hz or duty cycle measurement Step 2 Connect test leads to the circuit Connecting diagram see below ...

Page 17: ... switch to position Step 2 Connect test leads to the circuit Connect the common COM test lead to the circuit before connecting the live lead connecting diagram refer to Measuring AC Voltage Primary display shows ac Voltage measurement reading Secondary display shows Frequency measurement reading ...

Page 18: ...To avoid personal injury or damage to the Meter 1 Do not attempt to make an in circuit current measurement when the open circuit potential to earth ground exceeding 1000V 2 Switch to proper function and range for your measurement 3 Do not place the test probe in parallel with a circuit when the test leads are connected to the current terminals 4 Connect the test leads to the correct input 10A mA µ...

Page 19: ...nnect circuit power and discharge all high voltage capacitors before testing resistance Note On a higher resistance measurement 1Me the measurement may take a few seconds to get stable reading Over range or open circuit indication OL ...

Page 20: ...testing continuity Press SELECT button for continuity function Measuring Capacitance X Disconnect circuit power and discharge all high voltage capacitors before measuring capacitance Use dc Voltage function to check the capacitors are discharged Press SELECT button for capacitance measurement function ...

Page 21: ...15 Measuring Diode X Disconnect circuit power and discharge all high voltage capacitors before testing diode Note A typical junction Voltage drops 0 5 V to 0 8 V ...

Page 22: ...446 F Measurement steps Step 1 Turn the rotary switch to C F position The display will show OPEN Press SELECT button for conversion to F measurement Step 2 Connect the temperature probe K type to the Meter and to the surface to be measured Two temperature surface points can be measured at the same time by using the provided temperature probes Step 3 Press RANGE button to select temperature measure...

Page 23: ...3 Do not test on hazardous live wires higher than 750V ac 4 Before and after hazardous voltage measurements test the Meter by approaching to a known source such as a line ac Voltage or outlet to determine proper operation 5 At NCV mode no test lead connections are required for NCV measurement Buzzer will sound when the detected voltage is 90V and the buzzer will be on The distances between the wir...

Page 24: ...nge Automatic and Manual Altitude Operating 2000m Operating temperature 0 C 40 C 32 F 104 F Relative humidity 0 C 30 C 32 F 86 F 75 30 C 40 C 86 F 104 F 50 Storage temperature 10 C 50 C 14 F 122 F Electromagnetic compatibility In an RF filed of 1V m Specified accuracy 5 Battery 9V 6F22 NEDA1604 or equivalent Low battery indication Dimensions L x W x H 182 mm x 90 mm x 45 mm 7 2 in x 3 5 in x 1 8 i...

Page 25: ...True rms indication rms indication AM 570 AM 550 EUR True rms Note Frequency on secondary display may not be displayed if the measured voltage is below 20 of the display voltage range 3 Low Pass Filter Range Resolution Accuracy 6 000V 0 001V 45 to 200Hz 2 40 LSD 200 to 440Hz 6 40 LSD 60 00V 0 01V 600 0V 0 1V 1000V 1V Block ac voltage signals above 1KHz Overload protection 1000Vp 4 Frequency Measur...

Page 26: ...mm 7 AC Current Measurement Range Resolution Accuracy 45Hz 400Hz AM 560 AM 570 AM 540 EUR AM 550 EUR 400Hz 1KHz AM 570 AM 550 EUR μA 600 0μA 0 1μA 1 2 5 LSD 2 5 LSD 6000μA 1μA mA 60 00mA 10μA 1 5 5 LSD 3 5 LSD 600 0mA 0 1mA 10 A 10 00A 10mA 2 5 LSD 4 5 LSD Overload protection μA mA range F1 0 5A H 1000V fast fuse 6 3 32 mm 10 A range F2 11A H 1000V fast fuse 10 38 mm Frequency response 45Hz 400Hz ...

Page 27: ...on Accuracy 0 1Ω Open circuit voltage is around 3V dc Resistance 50Ω buzzer will not sound Resistance 10Ω buzzer will sound G 1mV Display range is 0V to 2 8V Normal voltage is around 0 5V to 0 8V for silicon PN junction Overload protection 1000Vp 10 Capacitance Measurement Range Resolution Accuracy 60 00nF 10pF Under REL status 3 5 LSD 600 0nF 100pF 3 5 LSD 6 000μF 1nF 60 00μF 10nF 600 0μF 100nF 4...

Page 28: ...ouble check the following 1 Replace the fuse or battery if the meter does not work 2 Review the operating instructions for possible mistakes in operating procedure Quick check on 0 5A FUSE Step 1 Turn the rotary switch to mA position Step 2 Use a multimeter with continuity function to verify the fuse continuity for the fuse of mA µA terminal Connect the test leads to mA µA terminal and COM termina...

Page 29: ... the fuse is burnt Replace the fuse as specified F2 11A H 1000V fast fuse 10 38 mm Except for the replacement of the battery repair of the meter should be performed only by an Authorized Service Center or by other qualified instrument service personnel The front panel and case can be cleaned with a mild solution of detergent and water Apply sparingly with a soft cloth and allow to dry completely b...

Page 30: ...F22 or equivalent The battery cover provides the correct polarity fitting construction design Install the battery in the battery cover 5 Put the battery cover back and re fasten the screw Battery 9V 6F22 Battery or equivalent Replacing FUSE follow below steps 1 Disconnect the test lead probe from measuring circuit 2 Turn the Meter to OFF position 3 Remove the screws from the enclosure and open the...

Page 31: ...25 F1 9 V b a tt e ry F2 ...

Page 32: ......

Page 33: ...info amprobe com Everett WA 98203 Tel 877 AMPROBE 267 7623 Amprobe Europe Beha Amprobe In den Engematten 14 79286 Glottertal Germany Tel 49 0 7684 8009 0 Visit www Amprobe com for Catalog Application notes Product specifications User manuals ...

Reviews: