Telaire T5100-LED Series CO

and Temperature Sensor  

User Instructions

Installing  the Sensor

 

!WARNING!

Before performing service or maintenance opera-

tions on the systems, turn OFF main power switch-

es to the unit. Electric shock can cause personal 

injury. Please read and follow the wiring instructions 

precisely;  miswiring may cause permanent damage 

to the product.

Basic Installation

1.  Separate the case into its front and rear sections.
2.  Secure the rear section of the case to the wall or 

junction box using the supplied screws, and make 
necessary wire connections.

3.  Select Voltage or Current output option and Voltage 

range (0-10 V or 0-5 V) using the SW1 as shown on 
the internal label (Figure 1) and Table 1.

Note:

  

SW1 controls both CO

2

 and Temperature  

 

outputs simultaneously.

Factory default setting is Voltage outputs 0-10V.

Table: 1 
Voltage and Current Output Options

Switch 

#1

Switch 

#2

Configuration

Down, 
Low

Down, 
Low

Factory default setting
CO

2

 0-10 V / 0 - 2000 ppm

Temperature 0-10 V/ 0 - 50 °C

Up, High

Up, High

CO

2

 0-5V/ 0 - 2000 ppm

Temperature 0-5 V/ 0 - 50°C

Down, 
Low

Down, 
Low

CO

2

 4-20 mA/ 0 - 2000 ppm

Temperature 4-20 mA/ 0 - 
50°C

Up, High

Up, High

RESERVED

4.     Mount the Controller on the base by aligning the top 
        clips and then securing to the bottom clips. 
        Secure the Ventostat with the supplied set screw.  
        A one-minute stabilization warm up will take place.