nrgSMART Integrated Controller 

Amphenol Network Solutions 

All rights reserved. 4.16.2021 151881 A0

 

509.926.6000 

— amphenol-ns.com

 

 

h.  Change your setting from 

Obtain an IP Address Automatically

 to 

Use the Following IP 

Address.

 In the subnet range of 169.254.xxx.xxx, you must increment the last octet(3 digits) 

by 1 from what is displayed in the LCD screen of the controller; no gateway or DNS needed.  

i.  Hit OK on the next two screens to complete the change. 
j.  Connect to nrgSMART Controller via a browser by typing its IP address of 169.254.xxx.xxx 

Note: Chrome and Firefox are recommended. 

k.  The Configuration webpage will be displayed 

 

3.  The controller can be operated in the following modes simultaneously:  

HTML User Interface Mode: 

  The controller will present data from all panel sensors within the panel itself, and from any 

nrgSMART SENS panels that are connected to it over the nrgNET serial interface. 

  Summary data from the Controller 

can be viewed from the controller’s front LCD screen.  It will 

scroll through the following parameters.  (If additional nrgSMART SENS panels are connected to 
the controller, their data will not be shown on the display, other than the “number of active panels” 
this will reflect how many panels are being monitored by the controller.). 

 

o

  Integrated Controller Name 

o

  nrgOS version 

o

  Number of active panels 

o

  IP address 

o

  Integrated Panel name 

o

  Integrated Panel serial number 

o

  Feed Current A and B 

o

  Feed Voltage A and B 

o

  Temperature 1 and 2 

 

  The Integrated Controller will indicate alarms by flashing between white and black backgrounds.  

When in alarm, a bell symbol will be displayed next to the Integrated Controller Name.  If the alarm 
is from the Integrated Panel, a bell will also be displayed next to the value in alarm.  For example, if 
Temperature 1 of the Controller Panel is in alarm, there will be a bell symbol next to the "Temp 1" 
on the display. 

  Note that if an interconnected nrgSMART SENS panel is in alarm, the Controller display will flash, 

however, the Controller will not indicate which interconnected nrgSMART SENS panel is in alarm.  
You will need to check the front panel LEDs of the interconnected SENS panels (locally), or connect 
to the Controller’s HTML User Interface, or your NMS system, to determine which panel is in alarm, 
and what the specific alarm condition is. 
 

SNMP Mode:  

  The LAN port must be connected and configured to operate on the same subnet as the customer 

defined Simple Network Management Protocol (SNMP)/ Network Management Server (NMS) 
server address.  

  The nrgSMART Management Information Base (MIB) table is available for download at the 

following URL: 

https://amphenol-ns.com/Product/nrgsmart-controller

 

Summary of Contents for nrgSMART CTRL

Page 1: ...nrgSMART Integrated Controller CTRL SENS versions System Configuration Guide...

Page 2: ...he data and communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and rack management We...

Page 3: ...ensor Panel designation 5 1 2 3 Legacy nrgSMART Compatibility 5 1 3 Specifications 6 Section Two Operation 7 2 1 Operation Guidelines 7 2 1 1 nrgSMART Connectivity CTRL Versions 7 2 3 Parts Accessorie...

Page 4: ...umes no liability from the application or use of these products Amphenol Network Solutions does not convey a license under its patent rights nor the patent rights of others This document and the produ...

Page 5: ...be a nrgSMART panel with an integrated controller CTRL or to a legacy nrgCONTROL BT external controller or to a nrgBDFB XLW 1 2 3 Legacy nrgSMART Compatibility The new nrgSMART architecture differs fr...

Page 6: ...d power rating 12V 18mA 0 22W 24V 20mA 0 48W 48V 30mA 1 44W Alarm wire size 24 AWG typical 26 to 20 AWG Terminals Wire wrap or mates with TE Connectivity 3 640428 3 Compliance Specifications UL Listed...

Page 7: ...are release See Figure 1 Figure 1 CTRL Panel Connectivity Ports 2 The integrated nrgSMART Controller is set to DHCP client by default Connect an ethernet cable from the network to the LAN port on fron...

Page 8: ...being monitored by the controller o Integrated Controller Name o nrgOS version o Number of active panels o IP address o Integrated Panel name o Integrated Panel serial number o Feed Current A and B o...

Page 9: ...Interface 5 The nrgNET serial connectors nrgTEMP connectors and dry contact alarm terminals are located in the rear center of the panel Refer to Figure 2 Figure 2 Rear Connections nrg240GT54 panel sho...

Page 10: ...eable Controller Card nrgSMART 400822 Replaceable Sensor Card nrgSMART 307607 Faceplate for Sensor Card nrgSMART 150158S E2 Faceplate for Controller Card nrgSMART 150619S E2 SENS to CTRL conversion co...

Page 11: ...2 ICES 003 Class A Notice Avis NMB 003 Class A This Class A digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe A est conforme la norme NMB 003 du Canada ELECTROSTATI...

Reviews: