High-Power GMT
Series Fuse Panel
1.1.2.2 Power-Line Noise Filter
The filter characteristics under load are such that high-frequency transients are suppressed below effective
interference levels for telecommunications equipment used with the panel. With this filter option, the maximum
bus current is 75A.
1.2 Inspection
Please read these instructions carefully before beginning installation. If you need assistance, call Amphenol
Network Solutions Technical Support at 509.926.6000 or email us at [email protected].
Inspect equipment after unpacking and compare it to the packing list.
Immediately report any shipping damage, defects or missing parts to Amphenol Network Solutions at
509.926.6000. Keep all documentation that comes with your shipment.
Amphenol Network Solutions is not liable for shipping damage. If the product is damaged, notify the carrier and
call the Amphenol Network Solutions Customer Service Department at 509.926.6000 for further recourse.
NOTE: For service or warranty information, please visit the “Support” section of amphenol-ns.com, email us at
[email protected] or call us at 509.926.6000.
1.3 Installation Consideration
•
Elevated Operating Ambient Temperature:
If you install the rack in a closed or multi-unit rack
assembly, the operating ambient temperature of the rack environment may be greater than room
ambient. Take care to install the equipment in an environment compatible with the maximum operating
temperature.
•
Reduced Air Flow:
Maintain the amount of air flow required for safe operation when installing the
equipment in a rack.
•
Mechanical Loading:
Ensure mechanical loading is even to prevent hazardous conditions.
•
Circuit Overloading:
Overloading circuits may affect your overcurrent protection and supply wiring. Use
equipment nameplate ratings.
•
Circuit Breaker:
Unit should be protected by listed circuit breaker or branch-rated fuse rated maximum
75A (for 60A feeds) and maximum 125A (for 100A feeds).
•
Reliable Earthing:
Maintain reliable earthing of rack-mounted equipment. Pay attention to supply
connections other than direct connections to the branch circuit (e.g., use of power strips).
•
Disconnect Device:
Incorporate a readily accessible disconnect device in the building installation wiring.