DNET-IP2 USER MANUAL ISSUE 4
-24-
Modbus
Word
IP
Byte
Description
Machine Type Setting
34 37
(MACHINE_TYPE)
1 = DrgL - Dragline
2 = Shvl - Shovel
3 = Dril - Drill
4 = pSTx – Portable Starting
Transformer
5 = Wpmp - Water Pump
6 = Blank
35 38
Machine Number Setting
(MACHINE_NUM)
1 – 40 Sets the RTU MC Number
Under Voltage Trip Setting
(UV_TRIP_PARAM)
36 39
U/V Trip %
1 = None
2 = 30
3 = 40
4 = 50
5 = 60
6 = 70
7 = 80
37 40
Pilot Latch Setting
(PILOT_LATCH)
1 = On
2 = Off
Earth Fault Lockout Time Setting
(EF_LOCKOUT_TIME)
38 41
EF Lockout Time Seconds
1 = 10
2 = 15
3 = 20
4 = 25
39 42
Reserved
40 43
Reserved
41 44
Reserved
42 45
Reserved
43 46
Reserved
44 47
Reserved
45 48
RTU Digital Inputs
(RTU_DIG_IN)
Bit 0 = HTU Run
Bit 1 = HTU Online
46
49
Relay Status (RELAT_STAT)
Bit 0 = RELAY 4 (closed if bit set)
Bit 1 = CBR RELAY (closed if bit
set)
Bit 2 = MCR RELAY (closed if bit
set)
Bit 3 = RL3 RELAY (closed if bit
set)
Bit 4 = Reserved
Bit 5 = Undefined
Bit 6 = Heart Beat LED Drive
Bit 7 = MCF Trip Flag
47 50
Reserved
48 51
Reserved
49 52
Reserved
Modbus
Word
IP
Byte
Description
50 53
EC
Time
(ECTIME_ADJ)
1 = 300ms
2 = 400ms
3 = 500ms
4 = 600ms
5 = 800ms
6 = 1s
7 = 1.2s
8 = 1.5s
9 = 2s
51 54
Reserved
52 55
Reserved
53 56
Reserved
54 57
Reserved
55 58
Reserved
56 59
Reserved
57 60
Reserved
58 61
Reserved
59 62
Reserved
60 63
Checksum (Low order byte of sum
of all IP bytes