background image

En-6

7) Remote controller signal code

Change the indoor unit Signal Code, depending on the remote controllers.

( ...  Factory setting)

Setting description 

Function 

number 

Setting  

value 

A

44

00

B

01

C

02

D

03

8) External input control

“Operation/Stop” mode or “Forced stop” mode can be selected.

( ...  Factory setting)

Setting description 

Function 

number 

Setting  

value 

Operation/Stop mode

46

00

(Setting forbidden)

01

Forced stop mode

02

9) Room temperature control switching

(Only for Wired remote controller)
This setting is used to set the room temperature control method when the 
wired remote controller is selected by the Indoor Room Temperature  
Sensor Switching Function.

( ...  Factory setting)

Setting description 

Function 

number 

Setting  

value 

Control by the sensors of both 

the indoor unit and the wired 

remote controller.

48

00

Control only by the sensor of 

the wired remote controller

01

10) Setting record

Record any changes to the settings in the following table.

Setting description 

Setting value 

Filter sign

Static pressure

Cooler room temperature correction

Heater room temperature correction

Auto restart

Indoor room temperature sensor switching 
function

Remote controller signal code

External input control

Room temperature control switching

After completing the FUNCTION SETTING, be sure to turn off the power 
and turn it on again.

11.   SELECTING THE REMOTE  

   CONTROLLER SIGNAL CODE

When 2 or more air conditioners are installed in a room and the remote 
controller is operating an air conditioner other than the one you wish to 
set, change the signal code of the remote controller to operate only the air 
conditioner you wish to set (4 selections possible).

When two or more air conditioners are installed in a room, please contact 
your retailer to set the individual air conditioner signal codes.

Selecting the Remote Controller Signal Code

Use the following steps to select the signal code of the remote controller. 
(Note that the air conditioner cannot receive a signal code if the air 
conditioner has not been set for the signal code.)

1

  Press the START/STOP button until only the clock is displayed on the 

remote controller display.

2

  Press the MODE button for at least 5 seconds to display the current 

signal code (initially set to  ).

3

  Press the SET TEMP. (

) (

)  button to change the signal code 

between 

 

Match the code on the display to the air conditioner signal code.

4

  Press the MODE button again to return to the clock display. The signal 

code will be changed.

10°C HEAT

If no buttons are pressed within 30 seconds after the signal code is 
displayed, the system returns to the original clock display. In this case, 
start again from step 1.

The air conditioner signal code is set to A prior to shipment. Contact your 
retailer to change the signal code.

The remote controller resets to signal code A when the batteries in the 
remote controller are replaced. If you use a signal code other than signal 
code A, reset the signal code after replacing the batteries.

If you do not know the air conditioner signal code setting, try each of the 
signal codes (

) until you find the code which operates the air 

conditioner.

12.   TEST OPERATION

The outdoor unit may not operate depending on the room temperature. In 

this case, press the test run button on the remote controller while the air 

conditioner is running. (Point the transmitter section of the remote controller 

toward the air conditioner and press the test run button with the tip of a 

ballpoint pen, etc.)

Transmitter section

Test run button

To end test operation, press the remote controller START/STOP button.

9378626041-03_IM.indb   6

14/5/2555   9:07:13

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for UTY-LRHYM

Page 1: ...kά Português Русский Tϋrkçe PART NO 9378626041 03 INSTALLATION MANUAL For authorized service personnel only AIR CONDITIONER IR RECEIVER UNIT UTY LRHYM 9378626041 03_IM indb 1 14 5 2555 9 07 09 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 2: ...fore touching electrical components For the air conditioner to operate satisfactorily install it as outlined in this installation manual Installation work must be performed in accordance with national wiring standards by authorized personnel only Do not cut shorten or extend the cable in the standard parts Do not turn on the power until all installation work is complete CAUTION This mark indicates...

Page 3: ...al reception angle Indoor unit Ceiling 120 Remote controller Max 10m 5m Receiver unit Signal reception angle 6 INSTALLING THE RECEIVER UNIT CAUTION Do not touch the PCB or PCB parts of receiver unit directly with your hands Fixing of the holder cover with the screws in the standard parts may be unsuitable if the wall or ceiling material is weak If so prepare screws suitable for the wall or ceiling...

Page 4: ...NECT Tape 6 1 Select the wiring pattern Pattern A From the top of the receiver unit No additional work is necessary Pattern B From behind the receiver unit Perform the following procedure to route the wiring behind the receiver unit 1 2 Holder PCB Holder cover Screw 1 1 Remove the screw 2 Remove holder PCB from holder cover 1 Route the wiring as shown in the figure 2 1 Hook Holder cover Screw 1 Re...

Page 5: ...each indoor unit for details EXAMPLE Connect the wires and then use heat shrink tubing to protect the connection from dust and water droplets Provide a trap in the receiver unit wiring To prevent water droplets from entering the receiver unit and the connector If the wiring length is 10m replace with receiver unit wire C optional parts Receiver unit wire A 5m CONNECT Receiver unit Heat shrink tubi...

Page 6: ...ng description Function number Setting value No 42 00 Yes 01 If setting value is 00 Room temperature is controlled by the indoor unit temperature sensor If setting value is 01 Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor The air conditioner signal code is set to A prior to shipment Contact your retailer to change the signal code The remot...

Page 7: ...act your retailer to set the individual air conditioner signal codes Selecting the Remote Controller Signal Code Use the following steps to select the signal code of the remote controller Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code 1 Press the START STOP button until only the clock is displayed on the remote controller disp...

Page 8: ... unit Indoor unit fan motor error 5 3 Indoor unit Water Drain error 5 15 Indoor unit Indoor unit error 6 2 Outdoor unit Outdoor unit main PCB error 6 3 Outdoor unit Inverter PCB error 6 4 Outdoor unit Active filter error PFC circuit error 6 5 Outdoor unit IPM error 6 10 Outdoor unit Display panel error 7 1 Outdoor unit Discharge thermistor error 7 2 Outdoor unit Compressor thermistor error 7 3 Out...

Page 9: ...Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired Remote Controller Display Error code 9378626041 03_IM indb 8 14 5 2555 9 07 16 AMP Air Conditioning www ampair co uk sales ampair co uk ...