ZONESENSE EN54
INSTALLATION COMMISSIONING & OPERATION
2
Introduction
The
ZoneSense
Fire Alarm Control Panel (FACP) is supplied in an ABS (with a surround for
recessed mounting) or metal cabinet as a two, four or eight zone Conventional FACP and can
have up to four (4) remote LED Annunciator Cards (LAM
’s) Order Code 43100-0037 and / or one
(1) 8 Way Relay Board Order Code 4310-0050 [internal] 4310-0055 [external].
ZoneSense
meets the EN54-2 and EN54-4 standards, complies with the optional clauses 7.8
(Output to fire alarm devices), 7.11 (Delays to outputs) 10 (Test condition) and offers limited on
site programming and operational test facilities.
Features include;
Controls that have tactile and audible feedback of operation.
On-site programming.
Terminals cater for up to 2.5mm diameter cables.
Buzzer Operation
The buzzer provides audible:
Indication at system start-up (3 tone bursts of increasing frequency)
Indication of a fire condition. Tone is continuous, until the buzzer is silenced or the fire
condition is cleared by reset.
Indication of a fault condition. Tone is 1 second on, 1 second off, until the fault condition
clears.
Feedback when a key is pressed.
Feedback when multiple keys are pressed simultaneously or illegal key press (for
example RESET when at access level 1) or there is a timeout condition entering the
password.
The buzzer:
Is silenced by SILENCE BUZZER but will resound on any new alarm or fault condition.
Sounds during a lamp test.
Sounds (fault indication), when the power supply is not calibrated.
Sounds when calibration is successful (same tone bursts as at system start-up)