Group Address Setting

In group mode the XP95 Base VAD and Sounder VAD variants respond to an additional address referred 

to as the group address, which is used to activate groups of base variants, Integrated Base Sounders and/

or 100dB sounders simultaneously. Individual units continue to respond to their own addresses and report 

their status in the normal way. A group address is set on a four-segment DIL switch which is factory set to 

0000. A group address may be any spare address within–and only within–the range 112 to 126 inclusive. 

The required group address is set in accordance with the following table. For an illustrated example, please 

see Fig. 2. 

 

 

DIL switch 

 

DIL switch 

 

DIL switch

  setting 

 setting 

  setting

 addr 

1234 addr 

1234 addr 

1234

 

112 1111 

117 0101 

122  1010

 

113 0111 

118 1001 

123  0010

 

114 1011 

119 0001 

124  1100

 

115 0011 

120 1110 

125  0100

 

116 1101 

121 0110 

126  1000

Note: group mode is disabled if the group address DIL switch is set to 0000, 

irrespective of the protocol message.

Functional Test Data

The product is controlled by the control panel using the output bits in the communication protocol.

Protocol bit use:

 

Output Bit 

Function 

Input Bit  

Function

 

group mode 

group mode con

fi

 rmed

 

 

1 = off 

 

1 = group

 

 

0 = on 

 

0 = individual

 

Alert tone 

Alert tone con

fi

 rmed

 

 

1 = on 

 

1 = on

 

 

0 = off 

 

0 = off

 

Evacuation tone 

Evacuation tone con

fi

 rmed

 

  

1 = on 

 

1 = on

 

 

0 = off 

 

0 = off

Address Setting

The address of the XP95 Base VAD and Sounder VAD variants are set using seven segments of the eight-seg-

ment DIL switch. The eighth seg ment is used to adjust the volume output. Segments 1-7 of the switch are set 

to “0” (ON) or “1”, using a small screwdriver or similar tool. A complete list of address settings is shown below. 

If a detector is to be 

fi

 tted, set the address as described on page 4.

 

 

DIL switch  

 

DIL switch 

 

DIL switch 

 

DIL switch 

 

DIL switch

  setting 

 setting 

  setting 

 setting 

 setting

 addr 1234567 addr 1234567 addr 1234567 addr 1234567 addr 1234567

 1 1000000 

11 1101000 

21  1010100 

31 1111100 

41 1001010

 2 0100000 

12 0011000 

22  0110100 

32 0000010 

42 0101010

 3 1100000 

13 1011000 

23  1110100 

33 1000010 

43 1101010

 4 0010000 

14 0111000 

24  0001100 

34 0100010 

44 0011010

 5 1010000 

15 1111000 

25  1001100 

35 1100010 

45 1011010

 6 0110000 

16 0000100 

26  0101100 

36 0010010 

46 0111010

 7 1110000 

17 1000100 

27  1101100 

37 1010010 

47 1111010

 8 0001000 

18 0100100 

28  0011100 

38 0110010 

48 0000110

 9 1001000 

19 1100100 

29  1011100 

39 1110010 

49 1000110

 

10 0101000 

20 0010100 

30  0111100 

40 0001010 

50 0100110

 

51 1100110 

61 1011110 

71  1110001 

81 1000101 

91 1101101

 

52 0010110 

62 0111110 

72  0001001 

82 0100101 

92 0011101

 

53 1010110 

63 1111110 

73  1001001 

83 1100101 

93 1011101

 

54 0110110 

64 0000001 

74  0101001 

84 0010101 

94 0111101

 

55 1110110 

65 1000001 

75  1101001 

85 1010101 

95 1111101

 

56 0001110 

66 0100001 

76  0011001 

86 0110101 

96 0000011

 

57 1001110 

67 1100001 

77  1011001 

87 1110101 

97 1000011

 

58 0101110 

68 0010001 

78  0111001 

88 0001101 

98 0100011

 

59 1101110 

69 1010001 

79  1111001 

89 1001101 

99 1100011

 

60 0011110 

70 0110001 

80  0000101 

90 0101101  100 0010011

 

101 1010011  106 0101011  111  1111011  116 0010111  121 1001111

 

102 0110011  107 1101011  112  0000111  117 1010111  122 0101111

 

103 1110011  108 0011011  113  1000111  118 0110111  123 1101111

 

104 0001011  109 1011011  114  0100111  119 1110111  124 0011111

 

105 1001011  110 0111011  115  1100111  120 0001111  125 1011111

   

  

   

  

126 0111111

1   2  3  4  5  6   7  8

1  

2   3   4   5   6  

7   8

 

O

N

 = 0  1  0  1  0  1  0 

0 = 58–73dB(A)
1 = 71–88dB(A)

 = Address 42 

Individual Address

1   2  3  4

1  

2   3   4

O

N

 0  1  1  1 = Address 113 

Group Address

ON = 0

Fig. 2- Address example

Commissioning

It is important that the base variants be fully tested after installation. 

Fault Finding

 

Problem Possible 

Cause

 

No response or missing 

Incorrect address setting

 

 

Incorrect loop wiring (polarity reversed)

 

 

Too many bases between isolators

 

Analogue value 1 

Sounder failed

 

Analogue value 2 

VAD failed

 

Analogue value 3 

Sounder and VAD failed

 

Analogue value 4 

Incorrect group address or address setting

 

Failure to operate 

Control panel has incorrect cause and effect programming 

 

 

Incorrect group address setting

Fig. 1- Sounder VAD Base with isolator wiring

EARTH 

© Apollo Fire Detectors Limited 2004–2006/JDR/JLC/JDR/JLC

Volume control

Group address
setting

Address & tone
setting

L1 OUT 

L1 IN 

L2 

L2 

– 

– 

Position of Isolator LED 

–R

+R

Remote LED