Group Address Setting
In group mode the XP95 Base VAD and Sounder VAD variants respond to an additional address referred
to as the group address, which is used to activate groups of base variants, Integrated Base Sounders and/
or 100dB sounders simultaneously. Individual units continue to respond to their own addresses and report
their status in the normal way. A group address is set on a four-segment DIL switch which is factory set to
0000. A group address may be any spare address within–and only within–the range 112 to 126 inclusive.
The required group address is set in accordance with the following table. For an illustrated example, please
see Fig. 2.
DIL switch
DIL switch
DIL switch
setting
setting
setting
addr
1234 addr
1234 addr
1234
112 1111
117 0101
122 1010
113 0111
118 1001
123 0010
114 1011
119 0001
124 1100
115 0011
120 1110
125 0100
116 1101
121 0110
126 1000
Note: group mode is disabled if the group address DIL switch is set to 0000,
irrespective of the protocol message.
Functional Test Data
The product is controlled by the control panel using the output bits in the communication protocol.
Protocol bit use:
Output Bit
Function
Input Bit
Function
2
group mode
2
group mode con
fi
rmed
1 = off
1 = group
0 = on
0 = individual
1
Alert tone
1
Alert tone con
fi
rmed
1 = on
1 = on
0 = off
0 = off
0
Evacuation tone
0
Evacuation tone con
fi
rmed
1 = on
1 = on
0 = off
0 = off
Address Setting
The address of the XP95 Base VAD and Sounder VAD variants are set using seven segments of the eight-seg-
ment DIL switch. The eighth seg ment is used to adjust the volume output. Segments 1-7 of the switch are set
to “0” (ON) or “1”, using a small screwdriver or similar tool. A complete list of address settings is shown below.
If a detector is to be
fi
tted, set the address as described on page 4.
DIL switch
DIL switch
DIL switch
DIL switch
DIL switch
setting
setting
setting
setting
setting
addr 1234567 addr 1234567 addr 1234567 addr 1234567 addr 1234567
1 1000000
11 1101000
21 1010100
31 1111100
41 1001010
2 0100000
12 0011000
22 0110100
32 0000010
42 0101010
3 1100000
13 1011000
23 1110100
33 1000010
43 1101010
4 0010000
14 0111000
24 0001100
34 0100010
44 0011010
5 1010000
15 1111000
25 1001100
35 1100010
45 1011010
6 0110000
16 0000100
26 0101100
36 0010010
46 0111010
7 1110000
17 1000100
27 1101100
37 1010010
47 1111010
8 0001000
18 0100100
28 0011100
38 0110010
48 0000110
9 1001000
19 1100100
29 1011100
39 1110010
49 1000110
10 0101000
20 0010100
30 0111100
40 0001010
50 0100110
51 1100110
61 1011110
71 1110001
81 1000101
91 1101101
52 0010110
62 0111110
72 0001001
82 0100101
92 0011101
53 1010110
63 1111110
73 1001001
83 1100101
93 1011101
54 0110110
64 0000001
74 0101001
84 0010101
94 0111101
55 1110110
65 1000001
75 1101001
85 1010101
95 1111101
56 0001110
66 0100001
76 0011001
86 0110101
96 0000011
57 1001110
67 1100001
77 1011001
87 1110101
97 1000011
58 0101110
68 0010001
78 0111001
88 0001101
98 0100011
59 1101110
69 1010001
79 1111001
89 1001101
99 1100011
60 0011110
70 0110001
80 0000101
90 0101101 100 0010011
101 1010011 106 0101011 111 1111011 116 0010111 121 1001111
102 0110011 107 1101011 112 0000111 117 1010111 122 0101111
103 1110011 108 0011011 113 1000111 118 0110111 123 1101111
104 0001011 109 1011011 114 0100111 119 1110111 124 0011111
105 1001011 110 0111011 115 1100111 120 0001111 125 1011111
126 0111111
1 2 3 4 5 6 7 8
1
2 3 4 5 6
7 8
O
N
= 0 1 0 1 0 1 0
0 = 58–73dB(A)
1 = 71–88dB(A)
= Address 42
Individual Address
1 2 3 4
1
2 3 4
O
N
0 1 1 1 = Address 113
Group Address
ON = 0
Fig. 2- Address example
Commissioning
It is important that the base variants be fully tested after installation.
Fault Finding
Problem Possible
Cause
No response or missing
Incorrect address setting
Incorrect loop wiring (polarity reversed)
Too many bases between isolators
Analogue value 1
Sounder failed
Analogue value 2
VAD failed
Analogue value 3
Sounder and VAD failed
Analogue value 4
Incorrect group address or address setting
Failure to operate
Control panel has incorrect cause and effect programming
Incorrect group address setting
Fig. 1- Sounder VAD Base with isolator wiring
EARTH
© Apollo Fire Detectors Limited 2004–2006/JDR/JLC/JDR/JLC
Volume control
Group address
setting
Address & tone
setting
L1 OUT
L1 IN
L2
L2
–
+
–
+
Position of Isolator LED
–R
+R
Remote LED