AMPAC INDUSTRIES LTD
NZ 100 OPERATORS MANUAL
Page 8
Doc No: g0097wo1.doc
Dir No: L:\manuals
Date: 10/5/00
Rev: 1
3.12 MAINS ON INDICATOR
This LED is illuminated when the mains supply is connected and operational.
3.13 FUSING
The NZ100 has five fuses:
F1
Door holder circuit fuse
0.25 Amp M205
F2
Bell circuit fuse
3 Amp M205
F3
Battery circuit fuse
0.8 Amp M205
F4
Power supply fuse
0.8 Amp M205
Mains fuse
0.5 Amp M205
3.14 BATTERIES
The NZ100 system is designed to accept one 12V, 7 AH sealed lead acid battery. This should
provide more than 240 hours of backup capacity leaving sufficient capacity to drive the alarm load
for the required 30 minutes.