background image

269 

11.  Installation Instruction 

11.1  Select The Best Location 

11.1.1  Outdoor Unit 

  If an awning is built over the unit to prevent direct 

sunlight or rain, be careful that heat radiation from 
the condenser is not obstructed. 

  There should not be any animal or plant which 

could be affected by hot air discharged. 

  Keep the spaces indicated by arrows from wall, 

ceiling, fence or other obstacles. 

  Do not place any obstacles which may cause a 

short circuit of the discharged air. 

 

Refrigerant piping size 

Outdoor Unit 

CU-4Z80*** 

CU-5Z90*** 

Liquid - side 

ø 6.35 t0.8 

ø 6.35 t0.8 

Gas - side 

ø 9.52 t0.8 

*(ø 12.7 t0.8) 

ø 9.52 t0.8 

*(ø 12.7 t0.8) 

*In case of indoor is CS-Z71***, CS-TZ71***, 
CS-TZ60***, CS-TE60***, CS-E21***, then ø 12.7 t0.8 
gas-pipe size must be used together with CZ-MA2P 
(pipe size expander)

 

 

Table A

 

 

MODEL

Maximum Total Piping

Length for Add. Gas

(m)

Additional

Refrigerant

(g/m)

Wall

Mounted

Indoor

A

min

(m²)

Mini Cassette

Indoor

A

min

(m²)

Ducted

Indoor

A

min

(m²)

CU-4Z80***

45

20

9.89

6.62

6.62

45

20

11.15

7.46

7.46

CU-5Z90***

 

  If total piping length of all indoor units exceed the 

maximum total length listed above, additionally 
charge with 20 g of refrigerant (R32) for each 
additional meter of piping. 
 

A

min

 = (M / (2.5 × (LFL)

(5/4) 

× h

0

))

2

 

 

A

min

 = Required minimum room area, in m

2

 

M

 = Required charge amount in appliance, in kg 

LFL

 = Lower flammable limit (0.306 kg/m

3

h

0

 = Installation height of the appliance (1.8 m for Wall 

Mounted, 2.2 m for Mini Cassette & Ducted). 

This illustration is for explanation purposes only.

3/8" Gas side piping (

)

1/4" Liquid side piping (

)

Additional drain hose (

)

Connection cable (

)

Power supply cord (

)

Outdoor Unit Installation Diagram

Installation parts you
should purchase (

)

*

Note:

Respective indoor unit installation procedure shall

refer to instruction manual provided in the indoor unit

packaging.

It is advisable to avoid

more than 2 blockage

directions. For better

ventilation & multiple-

outdoor installation,

please consult

authorized dealer/

specialist.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Allowable piping length 

Outdoor Unit 

CU-4Z80*** 

CU-5Z90*** 

Allowable piping length of each indoor unit (min. ~ max.) 

3 m ~ 25 m 

3 m ~ 25 m 

Allowable total piping length of all indoor unit 

70 m or less 

80 m or less 

Outdoor unit located on upper side 

 

15 m or less 

15 m or less 

Height difference between indoor and outdoor unit 

Outdoor unit located otherwise 

 

7.5 m or less 

7.5 m or less 

Outdoor unit located on upper side 

 

7.5 m or less 

7.5 m or less 

Height difference between indoor unit 

Outdoor unit located otherwise 

 

15 m or less 

15 m or less 

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for CU-4Z80 Series

Page 1: ...iping Amin M 2 5 LFL 5 4 h0 2 Amin Required minimum room area in m2 M Required charge amount in appliance in kg LFL Lower flammable limit 0 306 kg m3 h0 Installation height of the appliance 1 8 m for...

Page 2: ...Unit Installation Diagram 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut 10 mm 2 When installing at roof please consider strong wind and earthquake Please fasten the ins...

Page 3: ...side of CS MZ16 CS TZ25 CS MTZ16 CS TZ35 CS Z20 CS TZ42 CS Z25 CS TZ50 CS Z35 CS TE20 CS Z42 CS TE25 CS Z50 CS TE35 CS XZ20 CS TE42 CS XZ25 CS TE50 CS XZ35 CS E9 CS XZ50 CS E12 CS TZ20 CS E18 Liquid s...

Page 4: ...if there is a constant pressure drop Move to next step Step 2 Refrigerant leak detection if there is any pressure drop Otherwise release the Nitrogen gas and move to Step 3 Evacuation of the equipmen...

Page 5: ...ptor Outdoor unit Liquid side Gas side OPEN Vacuum pump Liquid side 3 way valve Gas side 3 way valve Liquid side Gas side Tube connector Tube connector Tube connector Tube connector Close Close Indoor...

Page 6: ...s at the interface point are sufficient for the installation of the equipment CU 4Z80 Unit D Unit C Unit A Unit B Indoor Outdoor connection cable Power Supply Cord Isolating Devices Indoor Unit A Indo...

Page 7: ...remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder entering the pipe 3 Please make flare after in...

Reviews: