Introduction

Medical Facility Responsibility

  

   

www.amico.com

 

    3

As required by NFPA 99 (National Fire Protection Association) “Health Care Facilities”, oxygen systems having the source 
of supply outside the building shall have an inlet to connect a temporary, auxiliary source of supply for emergency or 
maintenance situations. This connection shall include necessary valves and to allow for an emergency supply of oxygen 
and isolation of the normal source of supply. The inlet connection shall be a 1” female npt connection and be provided 
with a plug to prevent entry of foreign matter into the oxygen system when not in use.

Amico Emergency Oxygen Inlet Station will perform in conformity with the descriptions contained in this manual and 
accompanying  labels  and/or  inserts,  when  assembled,  operated,  maintained  and  repaired  in  accordance  with  the 
instructions provided.

Emergency Oxygen Inlet Stations must be inspected periodically. A defective product should not be used. Parts that 
are broken, missing, plainly worn, distorted or contaminated, should be replaced immediately. Should such repairs or 
replacements become necessary, please contact your local distributor.