AMG Systems Ltd. reserves the right to make changes to this
document without notice. The information herein is believed to
be accurate. No responsibility is assumed by AMG for its use.
Page 10 of 12
AMG5713A6B9-DIN Instruction Sheet
D17375-00.doc
Data Interface Connections
Connector
Pin No.
Data Channel
RS-485
[switch top]
RS-422
[switch middle]
RS-232
[switch bottom]
1
IN + (A)
IN
2
IN - (B)
3
GND
GND
GND
4
5
6
7
IN/OUT + (A)
OUT + (A)
8
IN/OUT - (B)
OUT - (B)
OUT
Note: (A) or (B) in brackets in the above table refers to RS-485 / RS-422 data specification.
Alarm Channel Configuration
The
AMG5713A6B9-DIN
provides 1 Bi-directional alarm output / contact closure input.
The alarm input is typically connected to a contact closure switch. An ALARM IN+ input incorporates a
330R pull-up resistor to the in3V3 supply.
The alarm output can receive an on/off signal from an
AMG5714A6B9
and is typically used to convey
contact closure status. An alarm output uses a solid-state relay, with a maximum load current of
150mA at 125Vac/dc and
Ron < 6.5Ω.
Alarm Interface Connections
Connector
Pin No.
Alarm Interface
Alarm IN
Alarm OUT
1
2
3
GND
4
ALARM IN +
5
ALARM OUT -
6
ALARM OUT +
7
8