Installation
2-14
TM-F1OP-C1XN-01
Load Wiring Length for Operation with Sense Lines
For applications using remote sensing, you must limit the voltage drop
across each load line.
shows some allowable wire lengths for a
given load current and wire size. We recommend that you use the larger
load wiring to ensure a smaller voltage drop (1 V typical maximum),
although
units will compensate for up to 5 V drop in each line. See also
.
Table 2-4
Current Carrying Capacity for Load Wiring
Wire Size
(AWG)
Max. Current (A)
Wire Size
(AWG)
Max. Current (A)
20
2.5
6
61
18
4
4
97
16
6
2
155
14
10
1
192
12
16
1/0
247
10
21
2/0
303
8
36
Figure 2-3
Maximum Load Wire Length for 1 V Line Drop
WIRE GAUGE (AWG)
16
14
12
10
8
6
4
2
1/0
1
2/0
WIRE LENGTH (FEET)
100
90
80
70
60
50
40
30
20
10
LOAD CURRENT (AMPS)
1
2
3
4
5
6 7
8
9 10
20
30
40
50
60
70 80 90 100
200
300
400
500
1000
TM-F1OP-C1XN-01.book Page 14 Thursday, October 25, 2007 9:04 PM
Summary of Contents for Sorensen XFR 1200 Watt Series
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...This page intentionally left blank ii...
Page 8: ...This page intentionally left blank iv...
Page 10: ...This page intentionally left blank vi...
Page 16: ...xii TM F1OP C1XN 01 book Page xii Thursday October 25 2007 9 04 PM...
Page 18: ...xiv TM F1OP C1XN 01 book Page xiv Thursday October 25 2007 9 04 PM...
Page 30: ...1 12 TM F1OP C1XN 01 book Page 12 Thursday October 25 2007 9 04 PM...
Page 58: ...2 28 TM F1OP C1XN 01 book Page 28 Thursday October 25 2007 9 04 PM...
Page 82: ...4 8 TM F1OP C1XN 01 book Page 8 Thursday October 25 2007 9 04 PM...
Page 94: ...5 12 TM F1OP C1XN 01 book Page 12 Thursday October 25 2007 9 04 PM...