PECIFICATIONS
Inputs
Field Contacts
Normally Open (N.O.) or Normally Closed (N.C.)
Input selection through Software or Field Selectable Jumper
Wet (voltage supplied) or dry (voltage free) contacts
Field Contact Voltage (FCV)
Common FCV or FCV Isolated Input to Input (Jumper Selectable)
12, 24, 48, 125 VDC, 120 VAC or 24VDC open collector
Input Current Requirement: 0.0018 mA per input
FCV Disconnect for an alarm when the I/O Module is removed (other alarms
unaffected)
Input Isolation
Each input is optically isolated
Input Response
1 millisecond
(Fast Response, Option FR. Also used with SER
option)
50 milliseconds
Standard Response
50 msec to 250 seconds
Adjustable in Software in 50 msec or 1 second
increments
Display
Window Sizes
Full Size (1 per Cell):
3.0 x 3.0”
(76 x 76mm)
Half Size (2 per Cell):
1.5 x 3.0”
(38 x 76mm)
Third Size (3 per Cell):
1.0 x 3.0”
(25 x 76mm)
Quad Size (4 per Cell):
1.5 x 1.5” (38 x 38mm)
Illumination
White LED 20 mA @5VDC
Full Size Windows 8 LED’s / Input
Half Size Windows 4 LED’s / Input
Third Size Windows
2 LED’s / Input
Quad Size Windows
2 LED’s / Input
Window Color
White, Red, Yellow, Amber, Green, Blue
Legends
Laser printed on transparency film or Engraved