The Model 851 Transmitter can be calibrated 

out-of-system.

Figure 4-2 shows an out-of -system piping 

diagram.

CALIBRATION INSTRUMENTATION

NOTE

 – Calibration equipment should be 

accurate to five times the accuracy of the 

transmitter.

The Model 851 Transmitter can be calibrated 

using an ammeter or voltmeter Figure 4-3.

Use an ammeter with internal shunt impedance 

greater than 10 ohms will give erroneous 

readings.

Use a voltmeter with a 10 ohm precision resistor 

connected as shown in Figure 4-3.

1. Apply 0 psi pressure to input.

2.  Adjust “Zero” pot to obtain 4mA (40 mV)

output.

3.  Apply pressure which corresponds to “full

scale” pressure to input.

4.  Adjust “span” pot to obtain 20 mA (200

mV) output

5.  Repeat steps 1 through 4 until output

values are achieved.

6.  If “span” required differs from previous

span by more than 10%, adjust

“turndown” pot prior to “span” pot and

proceed to step 4.