March 2011
RP Series
2
2.
Specifications
All specifications at 25 5 C unless noted otherwise.
2.1.
Electrical
2.1.1.
Input
Line Voltage:
85V to 264V maximum.
100V to 240V nominal.
Line Current:
15 A RMS max.
Line Frequency:
47-63 Hertz.
Efficiency:
80% (typical) depending on line and load.
Power Factor:
0.95 or greater typical.
Inrush Current:
70 A peak max. at 260V input.
Hold-Up Time:
20 ms (with no effect on output).
Isolation Voltage:
Input to output = 2200 VAC, input to chassis = 1350 VAC.
2.1.2.
Output
Voltage Range:
0 to 135 V rms or 270 V rms
Voltage Resolution:
0.1 volt
Voltage Accuracy:
1% of range, 50 to 60 Hz.
2% at 400 Hz
Line & Load Regulation: 1% of FS on low range, 0.5% of FS on high range.
Voltage Distortion:
0.5% typical. THD at 50/60 Hz.
Total Power:
800 VA maximum at full scale voltage, either range (Model
801RP).
1250 VA maximum at full scale voltage either range (Model
1251RP).
Note: On the 1251RP, the maximum output power is limited to 1000VA when the input
voltage is below 120VAC.