background image

20

plannInG the vent sYsteM

Plan the route of the vent system from the discharge of the blower 

to the planned location of the vent terminal. Refer to VAA instruction 

on page 26 while planning the vent system.
1.  Layout total vent system to use a minimum of vent pipe and elbows.

2.  This water heater is capable of venting  flue gases equivalent to 

25’ (7.6 m) of 2” pipe, 65’ (19.8 m) of 3” pipe, or 128’ (39.0 m) of 

4” pipe as listed in Table 2.

taBle 2.

 

Number of 

2” Maximum 

3” Maximum 

4” Maximum

  90° Elbows  Pipe - ft. (m) 

Pipe - ft. (m) 

Pipe - ft. (m)

 

20 (6.1) 

60 (18.3) 

120 (36.6)

 

15 (4.6) 

55 (16.8) 

112 (34.1)

 

10 (3.0) 

50 (15.2) 

104 (31.7)

 

-- 

45 (13.7) 

96 (29.3)

 

-- 

40 (12.2) 

88 (26.8)

 

-- 

35 (10.7) 

80 (24.3)

The minimum vent lengths for each of the pipe sizes is one 90° on top of 

 

the unit plus 2’ (61cm) of straight pipe and the appropriate termination.

  note:

  The equivalent feet (m) of pipe listed above are exclusive 

of  the  termination. That is, the termination, with an installed 

screen, is assumed to be in the system and the remainder of the 

system must not exceed the lengths discussed above.

3.  The blower discharge adapter is made to accept only straight 

sections of 2”  pipe.  To start, a minimum of 2 inches (5.1 cm) of 2” 

pipe must be attached to the blower discharge, see Figure 17.

  If using 2” inch vent pipe:

  A minimum of 2 inches (5.1 cm) must be attached to the blower 

before  the  first  elbow. After  the  first  elbow  add  the  additional 

venting  required  for  the  installation. The  total  system  cannot 

exceed the lengths discussed above, where each elbow is equal 

to 5 feet (1.5 m) of straight pipe.

  If using 3” or 4” inch vent pipe:

  Two inches (5.1 cm) of pipe must be attached to blower discharge before 

adding a reducer to acquire desired pipe diameter. An appropriately 

sized 45 degree schedule 40 DWV elbow (field supplied) vent terminal 

must be obtained with an equivalent screen (supplied in vent kit). 

The total system cannot exceed equivalent pipe lengths discussed 

above where each elbow is equal to 5 feet (1.5 m) of straight pipe 

 

(3” vent pipe) or 8 feet (2.4 m) of straight pipe (4” vent pipe).

note: 

This  unit  can  be  vented  with  PVC  pipe  materials  (DWV 

ASTM-D2665 or CSA B181.2; Schedule 40, 80, 120 ASTM-D1785 or 

CSA B137.3; or SDR Series ASTM-D2241 or CSA B137.3), CPVC pipe 

materials (CPVC41 ASTM-D2846 or CSA B137.6; Schedule 40, 80 

ASTM-F441 or CSA B137.6; or SDR Series ASTM-F442), ABS pipe 

materials (Schedule 40 DWV ASTM-D2661 or CSA B181.1). Fittings, 

other than TERMINATION

 should be equivalent to PVC-DWV fittings 

meeting ASTM D-2665 (Use CPVC fittings, ASTM F-438 for CPVC 

pipe and ABS fittings, ASTM D-2661/3311 for ABS pipe). If CPVC or 

ABS pipe and fittings are used, then proper cement must be used for 

all joints, including joining pipe to Termination (PVC Material). If local 

codes do not allow use of PVC termination when a material other than 

PVC is used for venting, then an equivalent fitting of that material may 

be substituted if screen in PVC terminal is removed and inserted 

into new fitting.

PVC  Materials  should  use ASTM  D-2564  Grade  Cement;  CPVC 

Materials should use ASTM F-493 Grade Cement and ABS Materials 

should use ASTM D-2235 Grade Cement.
If water heater is being installed as a replacement for an existing power 

vented heater in pre-existing venting, a thorough inspection of existing 

venting system must be performed prior to any installation work. Verify 

that correct material as detailed above has been used, and that minimum 

or maximum vent lengths and terminal location as detailed in this manual 

have been met. Carefully inspect entire venting system for any signs 

of cracks or fractures, particularly at joints between elbows and other 

fittings and straight runs of vent pipe. Check system for signs of sagging 

or other stresses in joints as a result of misalignment of any components 

in system. If any of these conditions are found, they must be corrected in 

accordance with venting instructions in this manual before completing  

installation and putting water heater into service.

note:

 

a.

  For  water  heaters  in  locations  with  high  ambient 

temperatures (above 100°F) it is recommended that CPVC or ABS 

pipe and fittings be used. 

B.

 A 22.5 degree elbow (2” vent pipe) or a 

45 degree elbow (3” and 4” vent pipe) with an installed screen VENT 

TERMINAL must be used in all cases.
4.  There will be some installations where condensate will be formed 

in the horizontal runs of the vent system. This condensate will 

run into the condensate boot attached to the blower and out the 

fitting. The water heater is shipped with condensate hose that 

attaches to the fitting on the condensate boot. No other Tee or 

fitting is required. See Figures 17, 20 and 21.

condensate

This water heater is a condensing unit and requires a drain to be 

located in close proximity to allow condensate to drain safely. One hose 

from blower housing, two flexible hoses from blower outlet adaptor, 

along with another flexible hose from VAA if installed, run to barb fittings 

on vent pipe assembly #2. Hose is clamped by rubber clips and flexible 

hoses by a clamp on jacket top cover. See Figure 17. Condensate 

drains from the unit at the exhaust tee located at the bottom of the unit 

(see figure 16). Condensate from this water heater is mildly acidic. 

Please note that some local codes require that condensate is treated 

by using a pH neutralizing filter prior to disposal.
NOTE: It is important that the field supplied drain lines beyond the 1/2” 

adaptor of vent pipe assembly #1 should be installed continuously 

tilted downward toward an appropriate drain. See Figure 16. If these 

instructions are not followed or if condensate drain line is blocked, water 

will spill from condensate trap. Do not block the holes in the hex plug on 

top of a small tee in vent pipe assembly #1. As with every water heater 

installation, a drain pan should be used to prevent water damage to 

surrounding area. If necessary, a condensate pump with an incorporated 

reservoir may be used to pump water to an appropriate drain. To avoid 

condensate spillage, select a pump with an overflow switch.

Caution must be used to ensure that drain is free and clear of debris 

and  will  not  allow  backflow  through  the  condensate  drain  line. 

Consideration must be given to avoid freezing of the condensate lines 

which could result in excessive build up of condensate inside the water 

heater. Waterproof heat tape may be required to prevent freezing of 

condensate lines. Please ensure that the outlet of condensate drain 

does not create a slippery condition which could lead to personal 

injury. Care should be taken to ensure there is no kink or twist in any 

condensate hose. If a VAA is not installed, the unused barb fitting in 

vent pipe assembly #2 should be plugged using one of the break-

away plugs.

Breathing Hazard - Carbon Monoxide Gas

• 

Do NOT block the holes in the hex plug of vent pipe 

  assembly #1.

• 

Do NOT elevate any portion of the field supplied drain 

  line beyond the 1/2" adaptor above the adaptor. This 

  must be true for entire length of the drain line including 

  the exit into an appropriate drain.

• 

Condensate lines must be free and clear of debris and 

 

must not allow back flow through drain line. Condensate 

 

lines must be able to flow freely to an appropriate drain.

• 

Do not allow condensate lines to become crimped closed.

• 

Analyze entire vent system to make sure that condensate

  will not become trapped in a section of vent pipe and 

  therefore reduce open cross sectional area of vent.

Breathing carbon monoxide can cause brain damage or death.

Always read and understand instruction manual.

Summary of Contents for vG6250t76nv

Page 1: ... WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER RESIDENTIAL GAS WATER HEATERS For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER Low Lead Content www americanwaterheater com American Water Heater Johnson City TN 37605 POWER VENTED GAS MODELS W HOT SURFACE IGNITION NOT FOR USE IN MANUFACTUR...

Page 2: ...y alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoid the risk of injury The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California...

Page 3: ...3 GENERAL SAFETY INFORMATION ...

Page 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk ...

Page 5: ...ction Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local codes the National Electrical Code NFPA 70 4 If after reading this manual you have any questions or do not understand any portion of the instructions call the local gas utility or the manufacturer whose name appears on the rating pla...

Page 6: ... feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructions Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation...

Page 7: ...tting 4 Places Shown DD Plastic Top EE On Off Switch FF Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shuttoff Valve H Ground Joint Union J Dirt Leg K Outer Door L Union M Inlet Water Shuttoff Valve N Cold Water Inlet O Inlet Dip Tube P Temperature Pressure Relief Valve HH Bushing II Nipple JJ Co...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1A ...

Page 9: ... time to burn relationship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use then special precautions must be taken In addition to using lowest possible temperature setting that satisfies demand of application a Mixing Valve sho...

Page 10: ...stalled Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shuttoff device used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to...

Page 11: ...orine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater The results can be hazardous and also cause product failure INSULATION BLANKETS Insulation blankets are available to the general public for external use on gas water heaters but are not necessary w...

Page 12: ...e size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air should be provided to replace the exhausted air When an exhaust fan is installed in the same space with a water heater sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan Undersized openin...

Page 13: ... a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 18 27 for complete venting installation instructions FIGURE 9 The confined space should be provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing with...

Page 14: ...ode requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water system to be a closed system CHEMICAL VAPOR CORROSION CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILURE...

Page 15: ...on 6 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along the length of the insulation to ensure that it is fully seated around the pipe Also ensure that the base of the insulation is flush with the water heater Once seated secure the insulation with duct tape electrical tape or equivalent 7 Repeat steps 5 and 6 for the hot water outlet pipe 8 Add...

Page 16: ...excessive temperatures and pressures in the storage tank The T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems and Thermal Expansion on page 14 and 15 If you do not understand these instructions or have any questions regarding the Temperature Pre...

Page 17: ...closing its individual manual Shuttoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping to the gas control valve of water heater can be accomplished by either of two methods shown in Figures 12 and 13 FIGURE 12 GAS PIPING WITH FLEXIBLE CONNECTOR FIGURE 13 GAS PIPING WITH ALL BLACK IRON ...

Page 18: ... PVC parts should be assembled with ASTM D 2564 grade cement Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may be rotated to a different orientation as needed for the specific installation requirements Note the rotational orientation of each part by marking ...

Page 19: ... L Clearance above paved sidewalk or paved driveway located on public property 7 feet 2 13 m F Clearance to outside corner 2 feet 60 cm M Clearance under veranda porch deck or balcony 12 inches 30 cm G Clearance to inside corner 18 inches 45 cm In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is lo...

Page 20: ...or signs of sagging or other stresses in joints as a result of misalignment of any components in system If any of these conditions are found they must be corrected in accordance with venting instructions in this manual before completing installation and putting water heater into service NOTE A For water heaters in locations with high ambient temperatures above 100 F it is recommended that CPVC or ...

Page 21: ... tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 6 Make sure the ON OFF switch is in the OFF position and that the outer harness is connected from the blower control box to the connector on the bottom side of the gas valve 7 If the outer harness is not fact...

Page 22: ...line This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLATIONS FIGURE 18 Cut a length of PVC pipe about 3 5 inches 8 9 cm longer than wall thickness at the opening Glue vent terminal to this section of pipe Slide the wall plate over the pipe to stop agains...

Page 23: ...highest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with the additional vent pipe when calculating maximum equivalent feet of venting INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe where it exits the roof Th...

Page 24: ... cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4 Make sure the VAA and vent pipe is supported securely to a permanent fixture stud or wall Use standard support straps not supplied with kit that may be found at a local hardware store Failure to pro...

Page 25: ...A and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for Vertical Vent with 3 or 4 inch Pipe Installation of VAA with 3 4 inch Pipe for Horizontal Vent Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths...

Page 26: ... above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC or CPVC surfaces A chemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10 20 by weight virgin PVC mater...

Page 27: ...d make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and prepares the PVC or CPVC for the solvent cementing step Move quickly and without hesitation to the cementing procedure while the surfaces are still wet with primer E Application of solvent cement Apply...

Page 28: ...28 ...

Page 29: ... located in an area where the general public does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing the COOLER button decreases temperature and pressing the HOTTER button increases the temperature Setting water heater temperature at 120 F 49 C Approx mark on...

Page 30: ...eriod of time generally two weeks or more Hydrogen gas is extremely flammable and explosive To prevent the possibility of injury under these conditions we recommend the hot water faucet located farthest away be opened for several minutes before any electrical appliances which are connected to the hot water system are used such as a dishwasher or washing machine If hydrogen gas is present there wil...

Page 31: ...rod which will slowly deplete due to electrolysis prolonging the life of the water heater by protecting the glass lined tank from corrosion Adverse water quality hotter water temperatures high hot water usage and water softening methodscanincreasetherateofanoderoddepletion Oncetheanoderod is depleted the tank will start to corrode eventually developing a leak Certain water conditions will cause a ...

Page 32: ...ressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death DRAINING AND FLUSHING It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup The water heater should be drained if being shut down during freezing temperatures See Typical Installation secti...

Page 33: ...oose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances water lines or ground seepage should also be checked To check where threaded portion enters tank insert cotton swab between jacket opening and fitting If cotton is wet follow Draining instructions in th...

Page 34: ...Sheet 34 Wire Screen 3 35 Wire Screen 4 36 Wall Plate 4 37 Flexible Tubing REPAIR PARTS LIST Nowthatyouhavepurchasedthiswaterheater shouldaneedeverexistfor repairpartsorservice simplycontactthecompanyitwaspurchasedfromor direct from the manufacturer listed on the rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on reque...

Page 35: ...r 3 Ensure maximum number of elbows or maximum equivalent feet of vent or intake air pipe has not been exceeded per the installation instructions in the manual that came with the water heater 4 Ensure there are no obstructions in the vent or intake air pipe 5 The gas control valve thermostat has detected an open igniter circuit 1 Check wiring to the hot surface igniter assembly replace igniter ass...

Page 36: ...valve s immersion probe is either open or shorted 1 Turn the power off for 10 20 seconds then on again to clear these error codes 2 Replace the gas control valve thermostat if the error code persists 14 Self diagnostic check has detected a problem with black resistor wire on the ignitor assembly plug resistor wire is open or shorted 1 Turn off power to the water heater Ensure black resistor wire i...

Page 37: ...37 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES ...

Page 38: ...38 TROUBLESHOOTING GUIDELINES NOTES ...

Page 39: ...pply the heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method SERVICE AND REPAIR EXPENSES 4 Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is respon...

Page 40: ...40 American Water Heater Product Service and Support PO Box 1597 500 Princeton Road Johnson City TN 37605 Phone 800 999 9515 Copyright 2010 American Water Heater Company All rights reserved ...

Reviews: