background image

Carbon Monoxide Warning

Follow all the local and state codes or, in 
the absence of local and state codes, the 
"National Fuel Gas Code", ANSI Z223.1 
(NFPA 54)- latest edition to properly 
install vent system.
Failure to do so can result in death, 
explosion, or carbon monoxide poisoning.

Important:

  Air for combustion and ventilation must not 

come from a corrosive atmosphere. Any failure due to 
corrosive elements in the atmosphere is excluded from 
warranty coverage.

The following types of installation (not limited to the 
following) will require outdoor air for combustion due to 
chemical exposure and may reduce but not eliminate 
the presence of corrosive chemicals in the air:

!

beauty shops

!

photo processing labs

!

buildings with indoor pools 

Nominal Iron Pipe                                                               

Length of Pipe, Feet

Size, in.

1/2
3/4

1

1-1/4
1-1/2

132
278
520

1050
1600

92

190
350
730

1100

73

152
285
590
890

63

130
245
500
760

56

115

215
440
670

50

105
195
400
610

46
96

180
370
560

43
90

170
350
530

40
84

160
320
490

38
79

150
305
460

34
72

130
275
410

31
64

120
250
380

28
59

110

225
350

26
55

100
210
320

10

20

30

40

50

60

70

80

90

100

125

150

175

200

Table 1

Natural Gas Pipe Capacity Table (Cu. Ft./Hr.)

Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity
of 0.60 (natural gas).

After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the water heater. By formula:

Gas Input of Water Heater (BTU/HR) 

Heating Value of Gas (BTU/FT³) 

3

The gas input of the water heater is marked on the water heater data plate. The heating value of the gas (BTU/FT )
may be determined by consulting the local natural gas utility.

 Cu. Ft. Per Hr. Required=

Nominal Iron Pipe

Size, in.

Length of Pipe, Feet

3/4

1/2

1

1-1/4

275
576

1071
2205

189
393
732

1496

152
315
590

1212

129
267
504

1039

114

237
448
913

103
217
409
834

96

196
378
771

89

185
346
724

83

173
322
677

78

162
307
630

69

146
275
567

63

132
252

511

10

20

30

40

50

60

70

80

90

100

125

150

Table 2

LP Gas Capacity Table

Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column pressure). Based on a pressure drop of 0.5 inch water column.

   Example:

Input BTU requirement of the water heater 100,000 BTUH. 

Total pipe length, 80 feet = 3/4" IPS required.

                

Additional tables are available in the latest edition of the "National Fuel Gas Code", ANSI Z223.1.

Combustion Air Supply and
Ventilation

!

water heaters installed in laundry, hobby, or 
craft rooms

!

water heaters installed near chemical storage 
areas

Combustion air must be free of acid-forming chemicals 
such as sulfur, fluorine, and chlorine. These elements 
are found in aerosol sprays, detergents, bleaches, 
cleaning solvents, air fresheners, paint, and varnish 
removers, refrigerants, and many other commercial and 
household products. When burned, vapors from these 
products form highly corrosive acid compounds. These 
products should not be stored or used near the water 
heater or air inlet.

Combustion and ventilation air requirements are 
determined by the location of the water heater. The 
water heater may be located in either an open 
(unconfined) area or in a confined area or small 
enclosure such as a closet or small room. Confined 
spaces are areas with less than 50 cubic feet for each 
1,000 BTUH of the total input for all gas-using 
appliances.

7

Summary of Contents for Flame Guard Safety System

Page 1: ...ctly a fire or explosion may result causing property damage personal injury or death Gas Water Heater with the Flame Guard Safety System Installation Instructions and Use Care Guide Table of Contents 2 To obtain technical warranty or service assistance during or after the installation of this water heater visit our website at or call toll free 1 800 999 9515 When calling for assistance please have...

Page 2: ...h as air escaping through the faucet as water begins to flow Do not smoke or have any open flame near the faucet at the time it is open The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential ...

Page 3: ...to properly install this water heater or you have difficulty following the instructions you should not proceed but have a qualified service technician perform the installation of this water heater Massachusetts code requires this water heater to be installed in accordance with Massachusetts Plumbing and Fuel Gas Code 248 CMR Section 2 00 and 5 00 A data plate identifying your water heater can be f...

Page 4: ...sources have been extinguished Site Location Select a location near the center of the water piping system The water heater must be installed indoors and in a vertical position on a level surface Locate the water heater as close to the chimney or gas vent as practical Consider the vent system piping and combustion air supply requirements when selecting the water heater location The venting system m...

Page 5: ...an must not restrict combustion air flow Locate the water heater near a suitable indoor drain Outside drains are subject to freezing temperatures which can obstruct the drain line The piping should be at least 3 4 ID and pitched for proper drainage Under no circumstances will the manufacturer or seller of this water heater be held liable for any water damage which is caused by your failure to foll...

Page 6: ...lution bubbles forming indicate a leak or other approved method Gas Pressure Important The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater s data plate The minimum supply pressure is for the purpose of input adjustment Gas Pressure Testing Important This water heater and its gas connection must be leak tested before placing the appliance in operation I...

Page 7: ... the water heater data plate The heating value of the gas BTU FT may be determined by consulting the local natural gas utility Cu Ft Per Hr Required Nominal Iron Pipe Size in Length of Pipe Feet 3 4 1 2 1 1 1 4 275 576 1071 2205 189 393 732 1496 152 315 590 1212 129 267 504 1039 114 237 448 913 103 217 409 834 96 196 378 771 89 185 346 724 83 173 322 677 78 162 307 630 69 146 275 567 63 132 252 51...

Page 8: ...size of each opening free area is determined by the total BTUH input of all gas utilization equipment i e water heaters furnaces clothes dryers etc and the method by which the air is provided The BTUH input can be found on the water heater data plate Additional air can be provided by two methods Figure 4 Opening Locations Confined Spaces 12 maximum Permanent openings to the outside or additional r...

Page 9: ...ipment so that they are opened automatically during equipment operation Keep louvers and grilles clean and free of debris or other obstructions Direct to outdoors Vertical ducts Horizontal ducts Figure 6 Figure 7 Figure 8 Table 4 Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply All Air from Outdoors Only Based on the total BTUH input rating for all gas utilizing eq...

Page 10: ... Screws four provided Drafthood Jacket top Install the drafthood with the four screws provided Vent Pipe Size It is important that you follow the guidelines in these instructions for sizing a vent pipe system If a transition to a larger vent size is required the vent transition connection must be made at the drafthood outlet Vent Connectors 1 Type B Doublewall U L Listed Vent Pipe 2 Singlewall Ven...

Page 11: ...anufacturer s instructions Gas vents must be supported to prevent damage joint separation and maintain clearances to combustible materials Figures 11 and 12 Important This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent Figure 12 Common combined...

Page 12: ...s shown in Figure 14 These valves reduce the point of use temperature of the water by mixing cold and hot water and are readily available for use 4 If installing the water heater in a closed water system install a relief valve or expansion tank in the cold water line as specified under Closed System Thermal Expansion Page 13 5 Install a shut off valve in the cold water inlet line It should be loca...

Page 13: ...s DO NOT add any chemicals to the system piping which will contaminate the potable water supply Closed System Thermal Expansion Periodic discharge of the temperature and pressure relief valve may be due to thermal expansion in a closed water supply system The water utility supply meter may contain a check valve backflow preventer or water pressure reducing valve This will create a closed water sys...

Page 14: ...erature and pressure relief valve should be used with your water heater Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater Do not place any valve between the relief valve and the tank The Temperature Pressure Relief Valve Must not be in contact with any electrical part Must be connected to an adequate discharge line Must not be...

Page 15: ...piping and fittings must be compatible with potable water A properly installed flow control valve is required to prevent thermosiphoning Thermosiphoning is the result of a continuous flow of water through the air handler circuit during the off cycle Weeping blow off of the temperature and pressure relief valve T P or higher than normal water temperatures are the first signs of thermosiphoning The ...

Page 16: ...gs Installation Checklist Vent Pipe System Drafthood properly installed Vent connectors securely fastened with screws and supported properly to maintain six inch clearance Vent connector made of approved material and sized correctly Vent pipe system must be installed according to all local and state codes or in the absence of local and state codes the National Fuel Gas Code ANSI Z223 1 NFPA54 late...

Page 17: ...for about 1 minute after the pilot is lit Release the reset button and it will pop back up Pilot should remain lit If the pilot light goes out repeat steps2 6 TO TURN OFF GAS TO APPLIANCE 2 Turn the gas control knob clockwise to the OFF position OPERATING YOUR WATER HEATER Lighting Instructions Read and understand these directions thoroughly before attempting to light or re light the pilot Make su...

Page 18: ... WAR M H O T 120 F Bar 130 F Bar Index Bars Gas Control Knob Figure 19 Robertshaw Gas Valve Thermostat Settings W ARNIN G Dial Stop 130 F Bar Reset Button Note During low demand periods when hot water is not being used a lower thermostat setting will reduce energy losses and may satisfy your normal hot water needs If hot water use is expected to be more than normal a higher thermostat setting may ...

Page 19: ...n burner and pilot light in the event a flammable vapor incident occurs or due to poor combustion caused by a blocked vent or insufficient combustion air If the fuse opens the water heater cannot be used unless the thermocouple is replaced by a qualified service technician Contact the Product Service and Support Department for service information at A high temperature limit switch or ECO Energy Cu...

Page 20: ...old water inlet valve 3 Open a nearby hot water faucet 4 Connect a hose to the drain valve and terminate it to an adequate drain Note The drain hose should be rated for at least 200 F If the drain hose does not have this rating open the cold water inlet valve and a nearby hot faucet until the water is no longer hot 5 Open the water heater drain valve and allow all the water to drain from the tank ...

Page 21: ... is dirty or clogged The burner may be cleaned with soap and hot water Figure 23A L P Gas Burner 1 Separate the pilot bracket from the L P burner by removing screw 2 Loosen set screw located on top of the L P burner near the manifold door Carefully pull the burner away from the manifold door assembly 3 Check the burner to see if it is dirty or clogged The burner may be cleaned with soap and hot wa...

Page 22: ...e Thermocouple contains a thermal fuse Do not bend in the location shown below Figure 25 Be sure igniter wire is positioned through the small opening of the two piece wire connector 6 See Replacing Manifold Assembly Page 23 Notice The thermocouple contains a thermal fuse which is used as a safety device Notice Thermocouple must not be bent in this location Figure 24 Two Piece Wire Connector Assemb...

Page 23: ...flame trap 3 Reassemble following the procedure under Replacing the Manifold Assembly Replacing the Manifold Assembly 1 Check the door gasket for damage or imbedded debris prior to installation 2 Inspect the viewport for damage and replace as required 3 Insert the manifold assembly into the burner compartment making sure that the tab of the manifold tube engages in the slot of the bracket inside t...

Page 24: ...ipe joint compound on the gas piping connections and fitting on the back of the gas valve that screws into tank Be sure to remove the pilot ferrule nut from the new gas control valve thermostat Turn gas supply on and check for leaks Use a chloride free soap and water solution bubbles forming indicate a leak or other approved method Be sure tank is completely filled with water before lighting and a...

Page 25: ...ecessary skills to perform the adjustment properly you should not proceed but get help from a qualified service technician 1 Remove the manifold assembly using the instructions on page 21 2 Remove the two screws securing the burner to the manifold assembly then separate the burner from the manifold assembly see figure 29 3 While holding the burner loosen the air shutter set screw and rotate the ai...

Page 26: ...rmocouple 7 Locate source and correct 8 Replace thermostat 9 Call 1 800 999 9515 10 Replace igniter pilot assembly 11 Replace water heater eliminate flammable vapors source Call 1 800 999 9515 12 Check with gas utility company 13 See maintenance section for inspection and cleaning of flame trap HIGH OPERATION COSTS 1 Thermostat set too high 2 Sediment or lime in tank 3 Water heater too small for j...

Page 27: ...4 Defective thermostat 5 Heater installed in a confined area 6 Burner flame yellow lazy 1 Insufficient secondary air 2 Flue clogged 3 Heater installed in a confined area 1 Provide ventilation to water heater Check flue way flue baffle and burner 2 Clean locate source and correct 3 Provide fresh air ventilation 1 Temperature setting too low 1 Increase the temperature setting 1 Replace thermostat 2 ...

Page 28: ...AFTHOOD 2 REDUCER RING SOME MODELS 3 FLUE BAFFLE 4 HEAT TRAP COLD SOME MODELS 5 HEAT TRAP HOT SOME MODELS 6 COLD WATER DIPTUBE 7 ANODE ROD 8 TEMPERATURE PRESSURE RELIEF VALVE LOCATED TOP OR SIDE 9 DRAIN VALVE 10 GAS VALVE THERMOSTAT 11 PILOT ASSEMBLY THERMOCOUPLE KIT Natural Gas 12 PILOT ASSEMBLY THERMOCOUPLE KIT L P Gas 13 OUTER DOOR 14 15 MANIFOLD DOOR ASSEMBLY Natural Gas Low Nox BURNER Natural...

Page 29: ...sembly which contains the manifold tube gasket door pilot tube thermocouple two piece wire connector with retainer clip and pilot assembly Natural Gas Low Nox Item 17 Manifold door assembly which contains the manifold tube gasket door pilot tube thermocouple two piece wire connector with retainer clip and pilot assembly L P Gas Item 18 Contains two piece wire connector with retainer clip and pilot...

Reviews: