19

water heater installation

This  water  heater  is  provided  with  a  properly  rated/sized  and 

certified combination temperature - pressure (T&P) relief valve 

by  the  manufacturer.  See  Temperature-Pressure  relief  Valve 

on  pages  13-14  for  information  on  replacement  and  other 

requirements.

Water Damage Hazard

Temperature-Pressure Relief Valve discharge

pipe must terminate at adequate drain.

CAUTION

Install a discharge pipe between the T&P valve discharge opening 

and  a  suitable  floor  drain.  Do  not  connect  discharge  piping 

directly to the drain unless a 6” (15.2 cm) air gap is provided. 

To prevent bodily injury, hazard to life, or property damage, the 

relief  valve  must  be  allowed  to  discharge  water  in  adequate 

quantities should circumstances demand. If the discharge pipe is 

not connected to a drain or other suitable means, the water flow 

may cause property damage.

t&p Valve discharge pipe requirements:

•  Shall not be smaller in size than the outlet pipe size 

of the valve, or have any reducing couplings or other 

restrictions.

•  Shall not be plugged or blocked.
•  Shall not be exposed to freezing temperatures.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both 

the Temperature-Pressure relief Valve and the discharge 

pipe.

•  Must terminate a maximum of six inches above a floor 

drain or external to the building. In cold climates, it is 

recommended that the discharge pipe be terminated at an 

adequate drain inside the building.

•  Shall not have any valve or other obstruction between the 

relief valve and the drain.

The  type,  size  and  location  of  the  relief  valves  must  be  in 

accordance with local codes. The locations of the relief valves 

shown in the installation diagrams are typical. See pages 34-48.  

The heater has a factory installed high temperature limit switch 

and temperature and pressure relief valve.
Cold  water  lines  to  heater  should  be  installed  as  shown  in 

order  to  minimize  gravity  circulation  of  hot  water  to  building 

cold water lines.
A listed temperature and pressure relief valve of adequate capacity 

is installed on the heater.  The locations shown in the installation 

diagrams on pages 34-48 are typical.
The  discharge  opening  of  the  temperature  and  pressure  relief 

valve must be piped to an open drain and should not be subject 

to freezing temperatures.
Install in accordance with all local codes.

water line connections

This manual provides detailed installation diagrams (see pages 

34-48 of this manual) for typical methods of application for the 

water heater(s).

water (potaBle) heating and space heating

1.    All  piping  components  connected  to  this  unit  for  space 

heating applications shall be suitable for use with potable 

water.

2.    Toxic chemicals, such as those used for boiler treatment, 

shall NeVer be introduced into this system.

3.    This  unit  may  NeVer  be  connected  to  any  existing 

heating system or component(s) previously used with a 

non-potable water heating appliance.

4.    When  the  system  requires  water  for  space  heating  at 

temperatures  higher  than  required  for  domestic  water 

purposes, a tempering valve must be installed.  Please 

refer to installation diagrams on pages 34-48 of this manual 

for suggested piping arrangements.

thermometers (not supplied)

Thermometers should be obtained and field installed as shown in 

the installation diagrams.
Thermometers are installed in the system as a means of detecting 

the temperature of the outlet water supply.

water piping diagrams

This manual provides detailed water piping diagrams for typical 

methods of application for the water heaters, see Water Piping 

Diagrams beginning on page 34.
The water heater may be installed by itself, or with a separate 

storage tank, on both single and two-temperature systems.  When 

used with a separate storage tank, the circulation may be either 

by gravity or by means of a circulating pump.  When a circulating 

pump is used it is important to note that the flow rate should be 

slow so that there will be a minimum of turbulence inside the heater.
Adjust  flow  by  throttling  a  full  port  ball  valve  installed  in  the 

circulating line on the outlet side of the pump. Never throttle flow 

on the suction side of a pump.

t&p ValVe discharge pipe

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

Summary of Contents for (A)BCG3 85T500-8N

Page 1: ...0 121 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do no...

Page 2: ...ms 34 Manifold Kits 49 COMMERCIAL STORAGE TANK warranty 50 notes 51 Table Of Contents Safe Installation Use and Service 3 APPROVALS 3 General Safety Information 4 Precautions 5 Grounding Instructions 5 Hydrogen Gas Flammable 5 Introduction 6 Abbreviations Used 6 Qualifications 6 features and components 7 The Eliminator self cleaning system 7 High Limit Switch 7 Electronic Ignition Control 7 Exhaus...

Page 3: ...cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can cause low level exposure to some of the substances listed in the Act DANGER WARNING CAUTION CAUTION DANGER indicates an imminently ...

Page 4: ...iment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or service agency for installation and service Excessive gas pressure to gas valve can cause serious injury or death Do not use water heater with any gas other than the gas shown on the rating label Turn o...

Page 5: ...system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at the time it is open General Safety Information Verify the power to the water heater is turned off before performing any service procedures Read and understand this instruction manual and the safety messag...

Page 6: ...gas supply and electrical supply are required in addition to electrical testing skills when performing service ANSI Z223 1 2006 Sec 3 3 83 Qualified Agency Any individual firm corporation or company that either in person or through a representative is engaged in and is responsible for a the installation testing or replacement of gas piping or b the connection installation testing repair or servici...

Page 7: ...d manual resetting of high limit control preceded by higher than usual water temperature is evidence of high limit switch operation The following is a possible reason for high limit switch operation A malfunction in the thermostatic controls would allow the gas valve to remain open causing water temperature to exceed the thermostat setting The water temperature would continue to rise until high li...

Page 8: ...CG385T500 8P 147 322 207 44 196 171 69 53 3 171 20 70 1 50 1 50 1 50 1 50 1 50 1 50 368 389 Model Input Rate Btu Hr Kw Hr Approximate Tank Cap G L Recovery Rating Capacities GPH and LPH at temperature rise indicated 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F 130 F 140 F 17 C 22 C 28 C 33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C A BCG385T500 8N A BCG385T500 8P 500 000 85 1616 1212 970 80...

Page 9: ...E 5 MINIMUMCLEARANCESTONONCOMBUSTIBLECONSTRUCTION MODEL A RIGHT SIDE B LEFT SIDE C BACK D CEILING A BCG385T500 8N A BCG385T500 8P 0 0 0 12 30 5 cm Locating the Water Heater Property Damage Hazard All water heaters eventually leak Do not install without adequate drainage CAUTION When installing the heater consideration must be given to proper location Location selected should be as close to the sta...

Page 10: ... burners DO NOT allow insulation to come within 9 inches 23 cm of floor within 2 inches 5 cm of bottom cover to prevent blockage of combustion air flow to the burners DO NOT cover the instruction manual Keep it on the side of the water heater or nearby for future reference DO obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing lab...

Page 11: ... Call the local gas or utility company to verify Btu per cubic foot content before calling for technical assistance and have that information available Note The actual firing rate of the water heater must not exceed the input rating on the water heater s rating label under any circumstances Note Due to the input rating reduction at high altitudes the output rating of the appliance is also reduced ...

Page 12: ...60 C Less than 5 seconds 130 F 54 C About 30 seconds 120 F 49 C More than 5 minutes Gas Pressure Requirements Natural gas models require a minimum gas supply pressure of 4 5 W C Propane gas models require a minimum gas supply pressure of 11 W C The minimum supply pressure is measured while gas is not flowing static pressure AND while gas is flowing dynamic pressure The supply pressure static and d...

Page 13: ...mal expansion tank installed See Water Line Connections on page 19 and the Water Piping Diagrams beginning on page 34 Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized temperature pressure relief valve must be installed in opening provided Can result in overheating and excessive tank pressure Can c...

Page 14: ...tems and Thermal Expansion on page 13 If you do not understand these instructions or have any questions regarding the Temperature Pressure Relief Valve call the toll free number listed on the back cover of this manual for technical assistance Contaminated Air Breathing Hazard Carbon Monoxide Gas Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN CSA B149 1 To avoid i...

Page 15: ...sually Tight Construction In unconfined spaces in buildings infiltration may be adequate to provide air for combustion ventilation and dilution of flue gases However in buildings of unusually tight construction for example weather stripping heavily insulated caulked vapor barrier etc additional air must be provided using the methods described in the Confined Space section that follows Confined Spa...

Page 16: ...0 square inches 645 cm2 Outdoor Air Through One Opening Figure 15 Alternatively a single permanent opening commencing within 12 inches 300 mm of the top of the enclosure shall be provided See Figure 15 The water heater shall have clearances of at least 1 inch 25 mm from the sides and back and 6 inches l50 mm from the front of the appliance The opening shall directly communicate with the outdoors o...

Page 17: ...e aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 Outdoor Air Through Two Vertical Ducts The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Venting Installa...

Page 18: ... 8 8 7 500 000 2 Ft 10 10 10 9 9 8 8 7 500 000 3 Ft 10 10 9 9 9 8 7 7 Multiple Fan Assisted Water Heaters Total Vent Height Feet Number of 500 Heaters Combined Input btu hr 6 8 10 15 20 30 50 100 Manifold and Common Vent Diameter Inches 2 1 000 000 14 14 12 12 10 10 9 8 3 1 500 000 16 16 14 14 14 12 12 10 4 2 000 000 18 18 16 16 14 14 12 12 Combination of Multiple Fan Assisted and Natural Draft Wa...

Page 19: ...ation diagrams on pages 34 48 are typical The discharge opening of the temperature and pressure relief valve must be piped to an open drain and should not be subject to freezing temperatures Install in accordance with all local codes Water Line Connections This manual provides detailed installation diagrams see pages 34 48 of this manual for typical methods of application for the water heater s Wa...

Page 20: ...allations in the state of North Carolina due to the material of the tube Polypropylene Where such code restrictions exist use only lower inlet tank connection This may also require a heat trap check local codes The Top Outlet connection may still be used on these applications Plug or cap all unused openings in the tank before filling with water TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPER...

Page 21: ...ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION If any of the original wire as supplied with the appliance must be replaced use only type 105 C thermoplastic or equivalent and 2500 C type F must be used for the flame sensor and igniter leads The controls of this water heater are polarity sensitive Be certain to properly wire the hot and neutral connection...

Page 22: ...VERSION OF THE NATIONAL FUEL GAS CODE To prevent damage care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet Apply joint compounds pipe dope sparingly and only to the male threadsofpipejoints Donotapplycompoundstothefirsttwothreads Use compounds resistant to the action of liquefied petroleum gases BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEA...

Page 23: ... and avoid unnecessary service calls However the user should not attempt repairs which are not listed under the USER column General NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS CONTROL ...

Page 24: ...rt of the control system and any gas control which has been under water Do not touch any electric switch do not use any telephone in your building Immediately call your gas supplier from a neighbor s telephone Follow the gas suppliers instructions FOR YOUR SAFETY READ BEFORE OPERATING STOP Read the safety information above on this label Set thermostat to lowest setting 5 1 3 3 4 Turn off all elect...

Page 25: ...by the normal method or if a suitable draft cannot be obtained a blower type flue gas exhauster must be employed to assure proper venting and correct combustion Check the Igniter Assembly At least once a year check the igniter assembly Figure 23 and the main burner Figure 24 for proper operation Refer to the following igniter assembly and main burner sections Igniter Assembly For access to igniter...

Page 26: ...385T500 8N heater T 7 56 seconds H 1050 Btu Btuh 3600 7 56 X 1050 500 000 Btuh Compare with the BCG385T500 8N model and rating Should it be necessary to adjust the gas pressure to the burners to obtain the full input rate the steps below should be followed 3 Remove the regulator adjustment sealing cap fig 25 and adjust the pressure by turning the adjusting screw with a screwdriver Clockwise to inc...

Page 27: ...ting properly Expansion on page 13 The Temperature Pressure Relief Valve is not intended for the constant relief of thermal expansion Temperature Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG TH...

Page 28: ...ater Do not smoke or have open flame or sparks in vicinity of heater Do not mix UN LIME with other chemicals Do not allow contact with magnesium aluminum or galvanized metals RecommendedProcedureforPeriodicRemoval of Lime Deposits from Tank Type Commercial Water Heaters The amount of calcium carbonate lime released from water is in direct proportion to water temperature and usage see chart The hig...

Page 29: ...tion for contact with eyes Keep out of reach of children NOTE THE USE OF RUBBER OR NEOPRENE GLOVES IS RECOMMENDED ESPECIALLY IF YOU HAVE ANY OPEN SORES OR CUTS TO AVOID UNNECESSARY IRRITATION OR DISCOMFORT 1 Turn off fuel and or power supply to heater Also turn off power to any electrical device or equipment which is attached or part of the system 2 Open hot water side of faucet closest to heater ...

Page 30: ...EL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING Start Up Conditions SMOKE ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start up This is due to burning off of oil from metal parts and will disappear in a short while STRANGE SOUNDS Possible noises ...

Page 31: ...ox Turn on the water heater If this fails to correct the problem contact your plumber or service representative further information regarding anode replacement and this chlorination treatment If the smelly water persists after the anode replacement and chlorination treatment we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem Do not re...

Page 32: ...32 Sequence of Operation Flow Chart Description of this flow chart can be found in the SEQUENCE OF OPERATION section found on page 23 FIGURE 29 ...

Page 33: ...outside of tank normal Rumbling Sediment accumulation on bottom of tank Drain a quantity of water through drain valve If rumbling persists call a service agent Delime heater Ticking or metallic sounds Expansion and contraction normal Pounding Air chambers in piping have become waterlogged Drain piping system and refill Heater must be off while this is being done Combustion noises Too much primary ...

Page 34: ... s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WIT...

Page 35: ...mostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES A...

Page 36: ...s and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS TE...

Page 37: ...ump between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WA...

Page 38: ...stat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ...

Page 39: ...stat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ...

Page 40: ...at should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ...

Page 41: ...TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS BOOSTER WATER RETURN PRE HEATED WATER TO BOOSTER BOOSTER WATER TO FIXTURES HOT WATER T...

Page 42: ...F VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS EXPANSION TANK BOOSTED WATER OUTLET TYPICAL BOOSTER HEATER PRE HEATER PRE HEATER MUST BE IDENTICAL HEATERS FINISHED FLOOR COLD WATER S...

Page 43: ... LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WATER TO FIXTURES HOT WATER RETURN COLD WATER SUPPLY EXPANSION TANK PIPE T...

Page 44: ... than the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENT...

Page 45: ...er than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIRE...

Page 46: ...URE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS EXPANSION TANK COLD WATER SUPPLY HOT WATER TO FIXTURES FINISHED FLOOR HOT WATER RETURN PIPE T ...

Page 47: ...Temperature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WATER TO ...

Page 48: ...k Temperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS HOT WATER...

Page 49: ...nifold Kits MANIFOLD KITS TWO UNIT MANIFOLD KIT PART NO 9003426205 THREE UNIT MANIFOLD KIT PART NO 9003427205 FOUR UNIT MANIFOLD KIT PART NO 9003428205 DIMENSION A MODEL 81 5 A BCG385T500 8N A BCG385T500 8P ...

Page 50: ...lect or accident or b The storage tank has not been installed in accordance with the applicable local plumbing and or building code s and or regulations or c The storage tank is not installed operated and maintained in accordance with the printed Manufacturers instructions or d The storage tank or any part has been under water or e The storage tank is exposed to highly corrosive atmospheric condit...

Page 51: ...notes ...

Page 52: ...P O Box 1597 Johnson City TN 37605 Phone 800 456 9805 Fax 800 999 5210 www americanwaterheater com Copyright 2010 American Water Heater Company All rights reserved ...

Reviews: