American Standart 4A6H4 Installer'S Manual Download Page 6

PAGE 6 

Pub. No. 11-BC08D1-7

INSTALLER'S GUIDE

American Standard has always recommended installing  approved 

matched indoor and outdoor systems. 
All American Standard split systems are AHRI rated with only 

TXV indoor systems. 
The  benefits  of  installing  approved  indoor  and  outdoor  split 

systems are maximum efficiency, optimum performance and the 

best overall system reliability. 
The  following  charging  methods  are  therefore  prescribed  for 

systems with indoor TXV’s. 
1.    Subcooling (in the cooling mode) is the only recommended 

method of charging above 55°F outdoor ambient temperatures. 
2.    For best results -  the indoor temperature should be kept 

between 70°F to 80°F.  Add system heat if needed. 
3.     At startup, or whenever charge is removed or added, the 

system must be operated for a minimum 20 minutes to stabilize 

before accurate measurements can be made.
4.    Measure Liquid Line Temperature and Refrigerant Pressure 

at service valve.
5.    Determine total refrigerant line length, and height (lift) if 

indoor section is above the condenser. 
6.    Determine the Design Subcool Charging Temperature from 

the unit nameplate. 
7.    Locate this value in the appropriate column of the Subcool-

ing Charging Table. Locate your liquid line temperature in the 

left column of the table, and the intersecting liquid line pressure 

under your nameplate subcool value column. Add refrigerant to 

raise the pressure to match the table, or remove refrigerant to 

lower the pressure.  Again, wait for 20 minutes for the system 

conditions to stabilize before adjusting charge again.
8.    When system is correctly charged, you can refer to System 

Pressure  Curves  (in  Service  Facts)  to  verify  typical  perfor-

mance.

SUbcooLING cHARGING IN cooLING AbovE 55°f oD AMbIENT 

R-410A SUbcooLING cHARGING TAbLE

LIQUID 

TEMP. (°F)

DESIGN SUBCOOLING VALUES (°F)

8

10

12

14

LIQUID LINE PRESSURE (psi)

55

179

185

191

198

60

195

201

208

215

65

211

218

225

232

70

229

236

243

251

75

247

255

263

271

80

267

275

283

291

85

287

296

304

313

90

309

318

327

336

95

331

341

351

360

100

355

365

376

386

105

381

391

402

413

110

407

418

429

441

115

435

446

458

470

120

464

476

488

501

125

495

507

520

533

From Dwg. D154557P01 Rev. 1

1.    The Subcool Charging Method in cooling is not recommended 

below 55°F outdoor ambient.

2.    The only recommended method of charging at outdoor am-

bients below 55°F, is to weigh in the charge in the heating 

mode.

3.    Use Nameplate charge plus standard charge adders for line 

length. 

SUbcooLING cHARGING bELow 55°f oD AMbIENT - IN HEATING oNLy

SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE

60
50
40
30
25

Add 10 psig to Subcool Charging Table Pressure

20
15

Use Design Subcool Value from Table

10

0

Subtract 10 psig from S.C. Table Pressure

10

20

25

30

40

60

80

TOTAL REFRIGERANT LINE LENGTH  (FEET)

REFRIGERANT

LINE LIFT (FEET)

4.    Check  liquid  line  temperature  and  pressure  (at  the  OD 

valves) to obtain a minimum of 10°F subcooling. 

5.    Add charge if a minimum of 10°F subcooling is not obtained 

with the nameplate charge plus line length correction.

6.    It is important to return in the spring or summer to accurately 

charge the system in the cooling mode at outdoor ambients 

above 55°F.

Summary of Contents for 4A6H4

Page 1: ...inted a Rose color to indicate the type of refrigerant and may contain a dip tube to allow for charging of liquid refrigerant into the system All R 410A systems use a POE oil that readily absorbs mois...

Page 2: ...ational Electri cal Code Also the unit location must be far enough away from any structure to prevent excess roof runoff water from pouring directly on the unit Do not locate unit s close to bedroom s...

Page 3: ...alve is full open with a 1 4 turn See Figure 4 Brazing Refrigerant Lines 1 Remove lower access cover to access service valves 2 Before brazing remove plugs from external copper stub tubes Clean intern...

Page 4: ...ise basic safety precautions to avoid the possibility of electric shock 1 Power wiring and grounding must comply with local codes 2 Power supply must agree with equipment nameplate 3 Install a separat...

Page 5: ...rost Defrost Terminates on Time Unit Icing Up W H A T T O C H E C K M O D E P O W E R S U P P L Y H IG H V O L T A G E W IR IN G C O M P R E S S O R IO L R U N C A P A C IT O R S T A R T C A P A C IT...

Page 6: ...tes for the system conditions to stabilize before adjusting charge again 8 When system is correctly charged you can refer to System Pressure Curves in Service Facts to verify typical perfor mance Subc...

Page 7: ...5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4A6H4030B 3 1 1035 40 3 4 829 32 5 8 756 29 3 4 3 4 5 16 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4A6H4036B 4 1 943 37 1 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 9...

Page 8: ...d 3 Have all Refrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Veri...

Reviews: