background image

21

IMPORTANT: 

After completion of wiring, check all

electrical connections, including factory wiring within the
unit, and ensure all connections are tight. Replace and
secure all electrical box covers and access doors before
leaving unit or connecting power to circuit supplying unit.

After all electrical wiring is complete, SET THE ZONE
SENSOR SWITCH TO THE OFF POSITION AND THE
FAN SWITCH TO AUTO SO COMPRESSOR AND FAN
WILL NOT RUN, and apply power by closing the system
main disconnect switch. This will activate the compressor
crankcase heaters. Do not change the zone sensor
setting until power has been applied long enough to
evaporate any liquid refrigerant in the compressor. It is
recommended the crankcase heaters be energized for 8
hours prior to starting.

Pre-Start Quick Check List

[ ] Is unit properly located and level with proper clear-

ances? See Figure 2.

[ ] Is the duct work correctly sized, run, taped, insulated

and weather proofed with proper unit arrangement?
(See duct work installation)

[ ] Is the gas piping correctly sized, run, trapped and

purged of air? (See gas piping)

[ ] Is condensate line properly sized, run trapped and

pitched?

[ ] Is the filter of the correct size and number, clean and

in place?

[ ] Is the wiring properly sized and run in according to the

unit wiring diagram?

[ ] Are all wiring connections tight including those in unit

and compressor electrical boxes?

[ ] Has the unit been properly grounded and fused with

the recommended fuse size? (See wiring data)

[ ] Is the zone sensor correctly wired and in a good

location?

[ ] Have the air conditioning systems been checked at

the service ports for charge and leak tested if neces-
sary?

[ ] Does the condenser fan and indoor blower turn freely

without rubbing and are they tight on the shafts?

[ ] Is the indoor fan rotation correct?

[ ] Has the indoor blower speed been determined and

the proper speed been set? (See air flow performance
data)

[ ] Has all work been done in accordance with applicable

local and national codes?

[ ] Are all covers and access panels in place to prevent

air loss and safety hazards?

The following warning complies with State of California law, Proposition 65.

!

 START-UP

Power-up Initialization

The “initialization” by the Unitary Control Processor (UCP)
occurs each time the system is powered-up. The UCP performs
internal self-diagnostics checks, which include identifying the
equipment components of its system, and the configuring of
itself to that system. It also checks itself to be sure it is function-
ing correctly. On units with the optional economizer, the damper
is driven open for 15-20 seconds and then fully closed. The UCP
system indicator LED is turned to “ON” within one second of
start-up if operation is correct.

Starting the Unit in the Heating Mode

Note: See “Sequence of operation” in the unit Service Facts for
a complete description of heating operating sequence.

1. Check to ensure all grilles and registers are open and all unit

access doors are closed before start-up.

2. Purge the gas supply line of air by opening the union ahead

of the unit. When the odor of gas is detected, re-tighten
union and wait 5 minutes before proceeding.

3. Place the zone sensor system switch in the heat position.

4. Position the heating setpoint approximately 10 degrees

above room temperature and place the fan switch in “Auto”
or “On” position.

5.  Open the main gas valve(s) and turn on unit main power

supply.

Note:  

To bypass time delays, and verify the operation of this

unit from the roof, use the “Test mode procedure” on page 3
and 4 of this manual.

1. The combustion blower motor and ignitor should energize.

The main burners should light within one minute from the
time the combustion blower starts. Initial start may be
delayed somewhat if unit is not purged and air is trapped in
gas line.

2. If burners fail to ignite after 3 tries the ignition system will

lockout. Reset by disconnecting and re-applying unit power.

3. Unit will start in the high fire mode. After a short run cycle it

will switch to low fire.

Note:  

Blue smoke produced by the heat exchanger during the

initial burner firing is caused by a thin film of oil on the surface of
the heat exchanger. This oil will burn off quickly.

Check control operation and burner operating conditions through
the sight glass in burner assembly cover.

Bodily injury can result from

high voltage electrical components. If operating checks
must be performed with the unit operating, it is the
technician’s responsibility to recognize these hazards and
proceed safely. Failure to do so could result in severe
personal injury or death due to electrical shock or contact
with moving parts.

Hazardous Gasses!

Exposure to fuel substances or by-products of incomplete
fuel combustion is believed by the state of California to
cause cancer, birth defects, or other product reproductive
harm.

Summary of Contents for YKD063C

Page 1: ...ventional units Refer to the TEST MODES and START UP PROCEDURES before attempting to operate or perform maintenance on this unit Models 50 Hz YK D H 063C YK D H 073C YK D H 089C INSTALLATION OPERATION MAINTENANCE Customer Property Contains wiring service and operation information Please retain Packaged Gas Electric YK 063 YK 089 YK IOM 1 Since the manufacturer has a policy of continuous product im...

Page 2: ...the factory is designed to use natural gas only Do not connect gas piping to the unit until a line pressure test has been completed Pressure in excess of 34 8 mbar 14 inches water column 1 2 PSIG will damage to the gas valve resulting in an unsafe condition All power legs to the electrical components may not be broken by contactors See the wiring diagram on the unit control box cover Note Warnings...

Page 3: ...ry component Replaces thermostat provides operator controls and the zone temperature sensor for the UCP A complete line of ZSMs is available with various combinations of features A zone sensor module or a CTI is required for each system UEM Unitary Economizer Module standard component on economizer accessory This module provides the hardware necessary to connect the economizer accessory to the UCP...

Page 4: ...box cover must be closed Failure to ensure that the evaporator access panel and control box cover is in place could result in severe personal injury or death TEST MODE PROCEDURE Operating the unit from the roof using the test mode The Unitary Control Processor UCP has a red indicator light in the lower left corner When power is applied to the unit the light will glow if the UCP is functioning corr...

Page 5: ...its With Optional Accessory With Heat Pump Note Steps for optional accessories and modes not present in unit will be skipped The unit can be left in this step for up to one hour If allowed to remain in any test step for more than one hour the test mode will terminate and control will revert to the zone sensor To terminate the test mode remove the resistance and cycle the unit power at the unit dis...

Page 6: ...86 DOWNFLOW UNIT SI mm TOP VIEW SHOWING DUCT OPENINGS IN THE BASE UNITS mm A B C D E F G YK 063 089 895 386 572 329 83 86 1013 DIMENSIONAL DATA Unit Dimensions SI mm UNITS A B C D E F G H J YK 063 089 889 1259 2211 1062 151 155 211 60 48 Downflow and or Horizontal Figure 1 063 089 Ton Downflow 063 089Ton Horizontal ...

Page 7: ...4 1170 356 365 556 438 551 464 1076 25 46 919 2073 1178 Dimensions when round ductwork is used Figure 2 Table 3 Field Fabricated Duct Dimensions SI mm UNIT A B C D E F G H J K YK 063 089 1048 38 905 429 1124 575 1124 581 457 457 Curb Dimensions SI mm ...

Page 8: ...vertical condenser discharge They can be located either at ground level or on a roof in accordance with local and national codes Since these units are designed exclusively for outdoor operation additional flue venting systems are not required Each unit contains an operating charge of Refrigerant as shipped Select a location that will permit unobstructed airflow into the condenser coil and away fro...

Page 9: ...o a horizontal unit provide a flexible water tight connection to prevent noise trans mission from the unit to the ducts The flexible connec tion must be indoors and molded out of heavy canvas Note Do not draw the canvas taut between the solid ducts See Figure 1 for duct connections Figure 4 Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 2...

Page 10: ...he burner fan then switches into high speed and the heating capacity is raised to maximum When the temperature of the zone has reached the setpoint the UCP de engerizes the relays K5 K6 H and IGN the burner then stops If the indoor fan is set to auto operation it will stop 90 seconds after the burner has stopped in order to recover as much heat as possible from the exchanger To reset the ignition ...

Page 11: ...11 Figure 5 Figure 6 Detail of the Gas Section ...

Page 12: ... burning simulate a flame failure by disconnecting a wire of the flame detection sensor quick connect The ignition controller should immediately stop the burner and close the gas valve 4 Reconnect the sensor and re ignite the burner Once the burner is ignited simulate a high temperature failure by disconnecting a wire from the sensor TC01 The gas valve should close and stop the flaem re connect TC...

Page 13: ...Conditioner 50 Hz EEC Voyager G20 41 4 92 49 1 91 70 6 90 77 4 91 G25 35 0 92 38 3 89 59 4 88 60 3 90 G31 37 7 92 48 6 90 57 3 88 78 2 92 YK 063CD X YK 073CD X YK 073DD X YK 085CD X YK 089CD X YK 100CD X YK 100BD X YK 125CD X YK 155BD X YK 175CD X YK 200BD X YK 250BD X Gas Module Heating Capacity kW PCI Output ...

Page 14: ...e Gas Flow 15 C 1013 mbar m3 h 4 7 5 3 8 3 8 2 Heat Rate kW 38 0 43 0 67 4 67 0 Reduce Rate Gas Flow 15 C 1013 mbar m3 h 4 5 4 9 7 8 7 9 Heat Rate kW 36 5 40 0 63 4 64 0 Natural Gas G31 30 37ou 50 mbar 88 00 MJ m3 15 C 1013 Injector diameter mm 5 40 6 67 7 37 8 50 Heating Capacity kW 37 7 48 6 57 3 78 2 Minimum Gas Pressure Trip out mbar 20 0 20 0 20 0 20 0 Normal Rate Gas Flow 15 C 1013 mbar m3 h...

Page 15: ...ediment that may be deposited in the line 4 Before connecting the piping circuit to the unit bleed the air from the supply line Then cap or plug the line and test the pressure at the tapped shut off cock The pressure reading should not exceed 34 8 mbar 14 inches water column 5 Connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or equivalent Figu...

Page 16: ...n the unit c Add the total accessory static pressure drop from Step 1b to the design external static pressure The sum of these two values is the total system external static pressure 2 Use the table s in the Service Facts to find the external static pressure in inches water column that most closely approximates total system external static pressure Then locate the appropriate airflow rate in cfm f...

Page 17: ... diagram for location Figure 10 Typical Field Wiring Diagram Control Wiring Note Some models have a 24 volt transformer with an integral circuit breaker If the breaker trips open unit disconnect before attempting to reset breaker Models with a 50VA transformer do not have this circuit breaker Remove compressor access panel and control box panel to access transformer Reset by pressing in on the bla...

Page 18: ... no longer R W Y G B etc they are now 1 2 3 4 5 etc Connections should be made using 1 to 1 2 to 2 3 to 3 4 to 4 and so on See example below Zone Sensor Module Low Voltage Terminal Strip ZSM LTB 1 1 2 2 3 3 4 4 5 5 Zone Temperature Sensor Terminal Strip Terminal Terminal I D 1 ZTEMP 2 SIGNAL COMMON 3 CSP 4 MODE 5 HSP 6 LED COMMON 7 HEAT LED 8 COOL LED 9 SYS ON LED 10 SERVICE LED ...

Page 19: ...19 Figure 11A Zone Sensor Interconnecting Diagram ...

Page 20: ...20 Figure 11B Conventional Thermostat Interconnections ...

Page 21: ...tics checks which include identifying the equipment components of its system and the configuring of itself to that system It also checks itself to be sure it is function ing correctly On units with the optional economizer the damper is driven open for 15 20 seconds and then fully closed The UCP system indicator LED is turned to ON within one second of start up if operation is correct Starting the ...

Page 22: ...ture rise noted is outside of the specified limits adjust the fan motor rpm to cause the temperature rise of the heat exchanger to fall within the required range Open and lock unit disconnect switch before continuing installation Failure to do so could result in severe personal injury or death due to electrical shock or contact with moving parts Do not operate the unit without the evaporator fan a...

Page 23: ...e Facts to deter mine the unit refrigerant charge The correct charge is shown on the unit nameplate To charge the system accurately use superheat charging or weigh the charge Voltage With the compressor operating check the line voltage at the unit The voltage should be within the range shown on the unit nameplate If low voltage is encountered check the size and length of the supply line from the m...

Page 24: ... duct connections to ensure they are physically sound and sealed to the unit casing 9 Inspect the unit mounting support to see that it is sound 10 Inspect the unit to ensure there is no obvious deterioration Final Installation Checklist Does unit run and operate as described in the Sequence of Operation in the unit Service Facts Is the condenser fan and indoor blower operating correctly with prope...

Reviews: